Eaton PSG Power supply unit, Three-phase, 320 - 600 V AC / 24 V DC, 5 A
Product Name |
Eaton PSG power supply unit
|
Catalog Number |
172883
|
EAN |
4015081694716
|
Product Length/Depth |
117 mm
|
Product Height |
121 mm
|
Product Width |
50 mm
|
Product Weight |
0.65 kg
|
Certifications |
Protection against electric shock: DIN 57100-410
2014/30/EU ITE: EN 55022, EN 61000-3-2, EN 61000-3-3, EN 55024 Electrical equipment of machines: IEC60204-1 (Overvoltage category III) Class2: UL1310 and CSA-C22.2 No. 223 RoHS SELV (EN 60950) EN 50178/IEC 62103 EN 55011 2014/35/EU Electrical Safety (of IT equipment) : SIQ to EN60950-1, UL/c-UL recognized to UL 60950-1, CSA-C22.2 No. 60950-1, CB scheme to IEC 60950-1 IEC/EN 61204-3 Mains harmonics limitation: EN 601000-3-2 PELV (EN 60204) UL 508 IEC Rated CSA Std. C22.2 EN Listed EAC |
Model Code |
PSG120F24RM
|
Electric connection type |
Screw connection
|
Enclosure material |
Aluminum
|
Features |
Mains overvoltage protection (against internal overvoltage)
Output voltage stabilized Short-circuit-proof Modular version Stabilized |
Fitted with: |
Not accessible internal input fuse (T3.15 AH/500 V, 600 V) for device protection
|
Functions |
Transient overvoltage protection (varistor)
Secondary voltage adjustable |
Number of phases |
3
|
Degree of Protection |
IP20
NEMA 1 |
Environmental class |
3K3 (Climatic class, according to EN 60721)
|
Mounting Method |
Rail mounting possible
|
Pollution degree |
2
|
Product category |
Power supply
|
Connection |
L1 +, L2 –, L3 nc, PE ㊏, Input characteristics, DC duty
L1 +, L2 nc, L3 –, PE ㊏, Input characteristics, DC duty |
Connection type |
Screw connection
|
LED indicator |
Status indication of "DC OK": Green LED
|
Power consumption |
200 VA
|
Rated operational current (Ie) |
Max. 0.5 A at 3 x 400 V AC
Max. 0.4 A at 3 x 500 V AC |
Shock resistance |
30 g (300 m/s²) in all directions, Mechanical, According to IEC/EN 60068-2-27
|
Vibration resistance |
10 - 500 Hz at 30 m/s² (3 G max ) for 60 min. in X-axis, Y-axis, Z-axis directions, (IEC/EN 60068-2-6)
|
Ambient operating temperature - min |
-25 °C
|
Ambient operating temperature - max |
80 °C
|
Ambient storage temperature - min |
-25 °C
|
Ambient storage temperature - max |
85 °C
|
Climatic proofing |
< 95 % relative humidity at +25 °C, no condensation
|
Terminal capacity (flexible with ferrule) |
Primary side: 0.82 - 3.3 mm²
Secondary side: 0.82 - 3.3 mm² |
Terminal capacity (flexible with ferrule AWG) |
Primary side: 18 - 12
Secondary side: 18 - 12 |
Stripping length (main cable) |
7 mm
|
Tightening torque |
0.9 Nm, Screw terminals, Primary side
0.6 Nm, Screw terminals, Secondary side |
Protection class |
1 (with PE connection)
|
Current limitation |
Overcurrent = 150 % of max. output power, at short-circuit, safety and safety features
|
Insulation resistance |
1.5 kV AC (output)
4 kV AC (input/output) 2 kV AC (input) |
Mean time between failures (MTBF) |
> 500,000 h
|
Input voltage at AC 50 Hz - min |
320 V
|
Input voltage at AC 50 Hz - max |
600 V
|
Input voltage at DC - min |
450 V
|
Input voltage at DC - max |
800 V
|
Inrush current |
Voltage source up to 18 kVA: < 60 A with 3 x 400 V AC & 3 x 500 V AC (Inrush current limitation I²t (+25 °C))
Voltage source up to 3 kVA: < 30 A with 3 x 400 V AC & 3 x 500 V AC (Inrush current limitation I²t (+25 °C)) |
Leakage current at ground IPE - max |
< 3.5 mA (at 500 V AC)
|
Mains failure bridging |
> 20 ms (with 3 x 400 V AC)
> 40 ms (with 3 x 500 V AC) |
Ramp/run-up time |
< 1000 ms
|
Short-term interruption |
100% voltage dip, 1 cycle (20 ms at 50 Hz), automatic start, Input characteristics
|
Supply frequency |
63 Hz, Input, max. Range
47 Hz, Input, min. Range 50/60 Hz, Input, Rated value |
Supply voltage at AC, 50 Hz - min |
320 VAC
|
Supply voltage at AC, 50 Hz - max |
600 VAC
|
Supply voltage at DC - min |
0 VDC
|
Supply voltage at DC - max |
0 VDC
|
Tripping characteristic |
B
|
Residual ripple |
< 50 mV / < 150 mV
|
Capacitive load |
10000 µF max. Capacitive load starting, Output characteristics
|
Efficiency |
> 87 % (3 x 400 V AC)
> 86 % (3 x 500 V AC) |
Output |
Parallel switching for redundancy, with O ring diode (PSG480R24RM/PSG960R24RM)
|
Output current at AC, 50 Hz - max |
5 A
|
Output voltage |
24 V
|
Output voltage at DC - min |
24 V
|
Output voltage at DC - max |
28 V
|
Rated output power |
120 W
|
Voltage tolerance |
± 2 %, Rated output voltage
|
Equipment heat dissipation, current-dependent Pvid |
0 W
|
Heat dissipation capacity Pdiss |
0 W
|
Heat dissipation per pole, current-dependent Pvid |
0 W
|
Rated operational current for specified heat dissipation (In) |
0 A
|
Static heat dissipation, non-current-dependent Pvs |
16.5 W
|
10.2.2 Corrosion resistance |
Meets the product standard's requirements.
|
10.2.3.1 Verification of thermal stability of enclosures |
Meets the product standard's requirements.
|
10.2.3.2 Verification of resistance of insulating materials to normal heat |
Meets the product standard's requirements.
|
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects |
Meets the product standard's requirements.
|
10.2.4 Resistance to ultra-violet (UV) radiation |
Meets the product standard's requirements.
|
10.2.5 Lifting |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.2.6 Mechanical impact |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.2.7 Inscriptions |
Meets the product standard's requirements.
|
10.3 Degree of protection of assemblies |
Meets the product standard's requirements.
|
10.4 Clearances and creepage distances |
Meets the product standard's requirements.
|
10.5 Protection against electric shock |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.6 Incorporation of switching devices and components |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.7 Internal electrical circuits and connections |
Is the panel builder's responsibility.
|
10.8 Connections for external conductors |
Is the panel builder's responsibility.
|
10.9.2 Power-frequency electric strength |
Is the panel builder's responsibility.
|
10.9.3 Impulse withstand voltage |
Is the panel builder's responsibility.
|
10.9.4 Testing of enclosures made of insulating material |
Is the panel builder's responsibility.
|
10.10 Temperature rise |
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
|
10.11 Short-circuit rating |
Is the panel builder's responsibility.
|
10.12 Electromagnetic compatibility |
Is the panel builder's responsibility.
|
10.13 Mechanical function |
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
|