Foto on esinduslik
Download
Eaton DM1 Variable frequency drive, 400 V AC, 3-phase, 23 A, 11 kW, IP20/NEMA0, Radio interference suppression filter, 7-digital display assembly, Setpoint potentiometer, Brake chopper, FS3
| Product Name |
Eaton DM1 Variable frequency drive
|
| Catalog Number |
3-5013-002A
|
| EAN |
4015081981052
|
| Product Length/Depth |
180 mm
|
| Product Height |
260 mm
|
| Product Width |
130 mm
|
| Product Weight |
3.7 kg
|
| Certifications |
EAC
UL 508C UL Listed CUL UL Category Control No.: NMMS, NMMS7 UkrSEPRO CSA-C22.2 No. 274-17 UL report applies to both US and Canada UL CSA-C22.2 No. 274-13 IEC/EN61800-3 IEC/EN61800-5 IEC/EN 61800-3 IEC/EN 61800-5-1 RoHS, ISO 9001 CE marking UL File No.: E134360 Certified by UL for use in Canada C-Tick CE IEC/EN 61800-2 |
| Model Code |
DM1-34023EB-S20S-EM
|
| Air volume capacity |
100 m³/h
|
| Cable length |
C3 ≤ 25 m, maximum motor cable length
C2 ≤ 5 m, maximum motor cable length |
| Communication interface |
BACnet TCP
SmartWire-DT, optional BACnet MS/TP, built in Modbus RTU, built in DeviceNet, optional CANopen®, optional PROFIBUS, optional Modbus TCP, built in Ethernet IP, built in |
| Connection to SmartWire-DT |
Yes
In conjunction with DXG-NET-SWD SmartWire DT module |
| Degree of protection |
IP20
NEMA Other |
| Electromagnetic compatibility |
1st and 2nd environments (according to EN 61800-3)
|
| Environmental class |
3C2, 3S2 (Air quality)
|
| Features |
Parameterization: Power Xpert inControl
Parameterization: Keypad Parameterization: Fieldbus Temperature-controlled fan |
| Fitted with: |
IGBT inverter
Radio interference suppression filter 7-digital display assembly Brake chopper Setpoint potentiometer Internal DC link Control unit PC connection |
| Frame size |
FS3
|
| Mounting position |
Vertical
|
| Number of slots |
1 (expansion)
|
| Overvoltage category |
III
|
| Pollution degree |
2
|
| Product Category |
Variable frequency drives
|
| Protection |
Finger and back-of-hand proof, Protection against direct contact (BGV A3, VBG4)
|
| Radio interference class |
C2, C3: depending on the motor cable length, the connected load, and ambient conditions. External radio interference suppression filters (optional) may be necessary.
Optional external radio interference suppression filter for longer motor cable lengths and for use in different EMC environments C1: with external filter |
| Safety function/level |
STO (Safe Torque Off, SIL2, PLc Cat 2)
|
| Shock resistance |
0.75 mm (peak) at 10 - 57 Hz, max. 1 g at 57 - 150 Hz, according to EN 61800-5-1, EN 60068-2-6: 10 - 150 Hz
|
| Suitable for |
Branch circuits, (UL/CSA)
|
| Altitude |
Above 1000 m with 1 % derating per 100 m
Max. 1000 m Max. 3000 m Max. 2000 m for Corner Grounded TN Systems |
| Ambient operating temperature - min |
-10 °C
|
| Ambient operating temperature - max |
50 °C
|
| Ambient storage temperature - min |
-40 °C
|
| Ambient storage temperature - max |
70 °C
|
| Climatic proofing |
< 95 average relative humidity (RH), no condensation, no corrosion
|
| Current limitation |
0.1 - 2 x IH (CT), motor, main circuit
|
| Heat dissipation at current/speed |
166.7 W at 25% current and 50% speed
170 W at 25% current and 0% speed 205.8 W at 100% current and 50% speed 223.4 W at 50% current and 90% speed 276.5 W at 50% current and 50% speed 326.5 W at 100% current and 0% speed 392.9 W at 100% current and 90% speed 520.8 W at 50% current and 0% speed |
| Input current ILN at 110% overload |
35.7 A
|
| Input current ILN at 150% overload |
26.5 A
|
| Mains current distortion |
40 %
|
| Mains switch-on frequency |
Maximum of one time every 60 seconds
|
| Mains voltage - min |
380 V
|
| Mains voltage - max |
500 V
|
| Operating mode |
Speed control with slip compensation
U/f control Sensorless vector control (SLV) Torque regulation PM motors |
| Output frequency - min |
0 Hz
|
| Output frequency - max |
400 Hz
|
| Output voltage (U2) |
400 V AC, 3-phase
480 V AC, 3-phase 500 V AC, 3-phase |
| Overload current IL at 110% overload |
34.1 A
|
| Overload current IL at 150% overload |
34.5 A
|
| Rated conditional short-circuit current (Iq) |
100 kA
|
| Rated control supply voltage |
10 V DC (Us, max. 10 mA)
|
| Rated frequency - min |
45 Hz
|
| Rated frequency - max |
66 Hz
|
| Rated operational current (Ie) at 110% overload |
31 A
|
| Rated operational current (Ie) at 150% overload |
23 A
|
| Rated operational power at 380/400 V, 50 Hz, 110% overload |
15 kW
|
| Rated operational power at 380/400 V, 50 Hz, 3-phase |
11 kW
|
| Rated operational power at 500 V, 50 Hz, 3-phase |
11 kW
|
| Rated operational power at 500 V, 50 Hz, 3-phase, 110% overload |
18.5 kW
|
| Rated operational voltage |
480 V AC, 3-phase
400 V AC, 3-phase 500 V AC, 3-phase |
| Resolution |
0.01 Hz (Frequency resolution, setpoint value)
|
| Short-circuit protection rating |
40 A, UL (Class CC or J), Safety device (fuse or miniature circuit-breaker), Power Wiring
|
| Starting current - max |
200 %, IH, max. starting current (High Overload), For 2 seconds every 20 seconds, Power section
|
| Supply frequency |
50/60 Hz
|
| Switching frequency |
4 kHz, 1 - 16 kHz adjustable, fPWM, Power section, Main circuit
|
| System configuration type |
TN-S, TN-C, TN-C-S, TT, IT
|
| Voltage rating - max |
500 V
|
| Assigned motor current IM at 400 V, 50 Hz, 110% overload |
29.3 A
|
| Assigned motor current IM at 400 V, 50 Hz, 150% overload |
21.7 A
|
| Assigned motor current IM at 440 - 480 V, 60 Hz, 150% overload |
21 A
|
| Assigned motor current IM at 440/480 V, 60 Hz, 110% overload |
27 A
|
| Assigned motor current IM at 500 V, 50 Hz, 110% overload |
28.9 A
|
| Assigned motor current IM at 500 V, 50 Hz, 150% overload |
17.4 A
|
| Assigned motor power at 460/480 V, 60 Hz |
15 HP
|
| Assigned motor power at 460/480 V, 60 Hz, 110% overload |
20 HP
|
| Braking resistance |
26 Ω
|
| Braking torque |
Max. 100 % of rated operational current Ie with external braking resistor - Main circuit
Max. 30 % MN, Standard - Main circuit Adjustable to 150 %, DC - Main circuit |
| Switch-on threshold for the braking transistor |
800 VDC
|
| Number of inputs (analog) |
1
|
| Number of inputs (digital) |
4
|
| Number of outputs (analog) |
1
|
| Number of relay outputs |
2 (parameterizable, 1 changeover contact and 1 N/O, 3 A (240 V AC) / 3 A (24 V DC))
|
| Rated control voltage (Uc) |
24 V DC (external, max. 100 mA options incl.)
|
| Equipment heat dissipation, current-dependent Pvid |
407.4 W
|
| Rated operational current for specified heat dissipation (In) |
31 A
|
| 10.2.2 Corrosion resistance |
Meets the product standard's requirements.
|
| 10.2.3.1 Verification of thermal stability of enclosures |
Meets the product standard's requirements.
|
| 10.2.3.2 Verification of resistance of insulating materials to normal heat |
Meets the product standard's requirements.
|
| 10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects |
Meets the product standard's requirements.
|
| 10.2.4 Resistance to ultra-violet (UV) radiation |
Meets the product standard's requirements.
|
| 10.2.5 Lifting |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.2.6 Mechanical impact |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.2.7 Inscriptions |
Meets the product standard's requirements.
|
| 10.3 Degree of protection of assemblies |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.4 Clearances and creepage distances |
Meets the product standard's requirements.
|
| 10.5 Protection against electric shock |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.6 Incorporation of switching devices and components |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.7 Internal electrical circuits and connections |
Is the panel builder's responsibility.
|
| 10.8 Connections for external conductors |
Is the panel builder's responsibility.
|
| 10.9.2 Power-frequency electric strength |
Is the panel builder's responsibility.
|
| 10.9.3 Impulse withstand voltage |
Is the panel builder's responsibility.
|
| 10.9.4 Testing of enclosures made of insulating material |
Is the panel builder's responsibility.
|
| 10.10 Temperature rise |
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
|
| 10.11 Short-circuit rating |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
| 10.12 Electromagnetic compatibility |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
| 10.13 Mechanical function |
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
|