Eaton Touch panel XV-102, 24 V DC, 7 Inch, 1 x USB, 1 x RS-232, 1 x RS-485, 1 x CAN, Linux, Resistive touch, PLC
Product Name |
Eaton XV-102 Touch panel
|
Catalog Number |
EP-401351
|
EAN |
7640130100145
|
Product Length/Depth |
210 mm
|
Product Height |
38 mm
|
Product Width |
135 mm
|
Product Weight |
0.6 kg
|
Certifications |
IEC/EN 61000-6-4
IEC/EN 61131-2 CE Certified by UL for use in Canada CUL IEC/EN 61000-6-3 UL UL 508 UL File No.: E205091 DNV DNV TAA00000NC |
Model Code |
XV-102-L6-70TWRC-10
|
10.10 Temperature rise |
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
|
10.11 Short-circuit rating |
Is the panel builder's responsibility.
|
10.12 Electromagnetic compatibility |
Is the panel builder's responsibility.
|
10.13 Mechanical function |
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
|
10.2.2 Corrosion resistance |
Meets the product standard's requirements.
|
10.2.3.1 Verification of thermal stability of enclosures |
Meets the product standard's requirements.
|
10.2.3.2 Verification of resistance of insulating materials to normal heat |
Meets the product standard's requirements.
|
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects |
Meets the product standard's requirements.
|
10.2.4 Resistance to ultra-violet (UV) radiation |
Please enquire
|
10.2.5 Lifting |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.2.6 Mechanical impact |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.2.7 Inscriptions |
Meets the product standard's requirements.
|
10.3 Degree of protection of assemblies |
Meets the product standard's requirements.
|
10.4 Clearances and creepage distances |
Meets the product standard's requirements.
|
10.5 Protection against electric shock |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.6 Incorporation of switching devices and components |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.7 Internal electrical circuits and connections |
Is the panel builder's responsibility.
|
10.8 Connections for external conductors |
Is the panel builder's responsibility.
|
10.9.2 Power-frequency electric strength |
Is the panel builder's responsibility.
|
10.9.3 Impulse withstand voltage |
Is the panel builder's responsibility.
|
10.9.4 Testing of enclosures made of insulating material |
Is the panel builder's responsibility.
|
Fitted with: |
1 x RS485 (built-in interface)
SW interfaces 1 x RS232 (built-in interface) Recipes Printer output Color display 1 x Ethernet 10/100 Mbps (built-in interfaces) 1 x USB host 2.0 (built-in interface) Message system (incl. buffer and confirmation) Message indication 1 x CAN (built-in interfaces) |
Fuse type |
Built-in fuse (not accessible)
|
Enclosure material |
Plastic
|
Supply voltage at AC, 50 Hz - max |
0 VAC
|
Supply voltage at AC, 50 Hz - min |
0 VAC
|
Supply voltage at AC, 60 Hz - max |
0 VAC
|
Supply voltage at AC, 60 Hz - min |
0 VAC
|
Supply voltage at DC - max |
30 VDC
|
Supply voltage at DC - min |
19.2 VDC
|
Width of the front |
210 mm
|
Product category |
XV-100
|
Resolution |
|
Air pressure |
795 - 1080 hPa (operation)
|
Display size |
152 x 91 mm
|
Backup time |
10 years, typ. (time at zero voltage)
|
Memory capacity |
512,000 kByte
|
Ambient operating temperature - max |
50 °C
|
Ambient operating temperature - min |
0 °C
|
Ambient storage temperature - max |
60 °C
|
Ambient storage temperature - min |
-20 °C
|
Built-in depth |
33 mm
|
Equipment heat dissipation, current-dependent Pvid |
9.5 W
|
Front height |
135 mm
|
Heat dissipation capacity Pdiss |
0 W
|
Heat dissipation per pole, current-dependent Pvid |
0 W
|
Number of buttons (programmable function) |
0
|
Number of buttons with LED |
0
|
Number of grey-scales/blue-scales of display |
0
|
Number of HW-interfaces (industrial ethernet) |
0
|
Number of HW-interfaces (other) |
1
|
Battery runtime |
Back-up of real-time clock: CR 1025 (30 mAh), zero maintenance (soldered)
|
Voltage type |
DC
|
Conditions of acceptability |
The unit must be supplied via a SELV source.
UL/CSA The following end-product enclosures are required: Fire The provided Ethernet Connection is only allowed to connect to inhouse networks. The investigated Pollution Degree is: 2 |
Operating system |
Linux
|
Software |
XSOFT-CODESYS-3, Visualization software, Engineering
GALILEO, Visualization software, Engineering XSOFT-CODESYS-3, PLC-Programming software, Engineering |
Mounting method |
Flush mounting - Inclination from vertical: ±45° (if using natural convection)
Flush mounting Flush mounting - Clearance: Width x Height x Depth ≥ 30 mm (1.18") |
Display contrast ratio |
300:1
|
Number of slots |
1 (for SD-Card)
|
Display lighting |
LED
Dimmable via software |
Display type |
TFT
Standard front with standard membrane (fully enclosed) Color display, TFT |
Protection against polarity reversal |
Yes
|
Relative humidity |
10 - 95 % (non-condensing)
|
Lifespan |
40,000 h (Service life of back-lighting)
|
Degree of protection |
IP65
IP20, rear |
Luminance intensity |
250 cd/m²
|
Degree of protection (front side) |
NEMA 4X
IP65 |
Number of colors of the display |
65536
|
Vibration resistance |
According to IEC/EN 60068-2-6
|
Processor |
RISC CPU, 32 Bit, 800 MHz
|
RoHs conformity |
Yes
|
Memory |
DRAM: 512 MByte RAM
NVRAM: 128kByte Retain SD card, Type: SDSC, SDHC (external memory) Flash: 4 Gbyte |
Functions |
Process default value (input) possible
Additional software components, loadable Process value representation (output) possible |
Touch technology |
Touch sensor (glass with foil), Resistive touch protective screen
Glass with film touch sensor Resistive touch |
Model |
Insulating enclosure and front plate
|
Interfaces |
RS485 (not galvanically isolated, 9-pin SUB-D plug, UNC)
CAN, not galvanically isolated (SUB-D plug 9 pole, UNC) Ethernet (100Base-TX/10Base-T) RS232 (not galvanically isolated, 9-pin SUB-D plug, UNC) USB 2.0 host (not galvanically isolated) |
Voltage dips |
5 ms from undervoltage (19.2 V DC)
≤ 10 ms from rated voltage (24 V DC) |
Number of HW-interfaces (parallel) |
0
|
Number of HW-interfaces (RS-232) |
1
|
Number of HW-interfaces (RS-422) |
0
|
Number of HW-interfaces (RS-485) |
1
|
Number of HW-interfaces (serial TTY) |
0
|
Number of HW-interfaces (USB) |
1
|
Number of HW-interfaces (wireless) |
0
|
Number of interfaces (PROFINET) |
0
|
Number of online/runtime languages |
100
|
Number of password levels |
200
|
Number of pixels (horizontal) |
800
|
Number of pixels (vertical) |
480
|
Number of system buttons |
1
|
Operating temperature - max |
50 °C
|
Operating temperature - min |
0 °C
|
Rated operational current for specified heat dissipation (In) |
0 A
|
Screen size (diagonal) |
7 in
|
Static heat dissipation, non-current-dependent Pvs |
9.5 W
|
Permissible voltage |
18.0 - 31.2 V DC, absolute with ripple
19.2 - 30 V DC, effective (rated operating voltage -20 %/+25 %) 18 - 31.2 V DC, battery powered (rated operating voltage -25 %/+30 %) 35 V DC (for a duration of < 100 ms) |
Potential isolation |
Power supply: no
|
Power consumption |
Max. 10 W
9.5 W total 2.5 W (USB Slave to USB Host) 7 W |
Protocol |
TCP/IP
CAN EtherNet/IP Other bus systems MODBUS |
Rated operational voltage |
24 V DC (power-supply - safety extra low voltage)
|
Shock resistance |
Mechanical, According to IEC/EN 60068-2-27
|