Tietohaku
Lataa dokumentti () / 20
We make what matters work*

192518

Eaton Moeller series NZMN2 PXR20 circuit breaker, 160 A, 3-pole, box terminal, UL/CSA

General specifications

Product Name
Eaton Moeller series NZM molded case circuit breaker electronic
Catalog Number
192518
EAN
4015081932467
Product Length/Depth
149 mm
Product Height
195 mm
Product Width
105 mm
Product Weight
2.345 kg
Compliances
RoHS conform
Certifications
UL 489
CSA-C22.2 No. 5-09
CSA certified
CSA (File No. 22086)
UL (Category Control Number DIVQ)
Specially designed for North America
IEC
CE marking
UL listed
UL (File No. E31593)
IEC 60947-2
UL/CSA
CSA (Class No. 1432-01)

Delivery program

Application
Branch circuits, feeder circuits
Type
  • Rated current = rated uninterrupted current: 160 A
  • Switches conform to UL/CSA as well as the IEC regulations. IEC switching performance values are contained on the rating plate.
Circuit breaker frame type
NZM2
Number of poles
Three-pole
Amperage Rating
160 A
Release system
Electronic release
Features
Protection unit
Motor drive optional
Special features
Circuit breaker

Technical Data - Electrical

Voltage rating
690 V - 690 V
Rated operating voltage Ue (UL) - max
600 V
Amperage Rating
160 A
Instantaneous current setting (Ii) - min
2 A
Instantaneous current setting (Ii) - max
18 A
Overload current setting (Ir) - min
64 A
Overload current setting (Ir) - max
160 A
Short delay current setting (Isd) - min
320 A
Short delay current setting (Isd) - max
1600 A
Short-circuit release delayed setting - min
128 A
Short-circuit release delayed setting - max
1600 A
Short-circuit release non-delayed setting - min
320 A
Short-circuit release non-delayed setting - max
2880 A
Rated short-circuit breaking capacity Ics (IEC/EN 60947) at 400/415 V, 50/60 Hz
50 kA
Electrical connection type of main circuit
Frame clamp
Handle type
Rocker lever

Technical Data - Mechanical

Mounting Method
Fixed
DIN rail (top hat rail) mounting optional
Built-in device fixed built-in technique
Mounting Method
Fixed
DIN rail (top hat rail) mounting optional
Built-in device fixed built-in technique
Degree of protection
IP20
Protection against direct contact
Finger and back-of-hand proof to DIN EN 50274/VDE 0106 part 110
Number of auxiliary contacts (change-over contacts)
0
Number of auxiliary contacts (normally closed contacts)
0
Number of auxiliary contacts (normally open contacts)
0
Position of connection for main current circuit
Front side
Special features
Circuit breaker

Design verification as per IEC/EN 61439 - technical data

Rated operational current for specified heat dissipation (In)
160 A
Equipment heat dissipation, current-dependent
21.12 W
Ambient operating temperature - min
-25 °C
Ambient operating temperature - max
70 °C
Ambient storage temperature - min
40 °C
Ambient storage temperature - max
70 °C

Design verification as per IEC/EN 61439

10.2.2 Corrosion resistance
Meets the product standard's requirements.
10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard's requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard's requirements.
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects
Meets the product standard's requirements.
10.2.4 Resistance to ultra-violet (UV) radiation
Meets the product standard's requirements.
10.2.5 Lifting
Does not apply, since the entire switchgear needs to be evaluated.
10.2.6 Mechanical impact
Does not apply, since the entire switchgear needs to be evaluated.
10.2.7 Inscriptions
Meets the product standard's requirements.
10.3 Degree of protection of assemblies
Does not apply, since the entire switchgear needs to be evaluated.
10.4 Clearances and creepage distances
Meets the product standard's requirements.
10.5 Protection against electric shock
Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and components
Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections
Is the panel builder's responsibility.
10.8 Connections for external conductors
Is the panel builder's responsibility.
10.9.2 Power-frequency electric strength
Is the panel builder's responsibility.
10.9.3 Impulse withstand voltage
Is the panel builder's responsibility.
10.9.4 Testing of enclosures made of insulating material
Is the panel builder's responsibility.
10.10 Temperature rise
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.12 Electromagnetic compatibility
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.13 Mechanical function
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.

Additional information

Functions
Systems, cable, selectivity and generator protection
Current limiting circuit breaker

Vientituotteen tekniset tiedot

Serial Number Verified :
Authenticated:
The product is verified as being authentic; however, this does not guarantee the condition or fit for purpose of the product.

Todenna tuote

Syötä 16–17 numeron sarjanumerosi
Antamasi sarjanumero ei saa sisältää erikoismerkkejä. Antamasi sarjanumero on virheellinen, sillä siinä pitäisi olla 16 tai 17 numeroa. Antamaasi sarjanumeroa ei löytynyt. Yritä uudelleen tai ilmoita tästä ongelmasta lisäavun saamiseksi. Antamasi sarjanumero ei vastaa tuotetta. Tarkista tuotteesi sarjanumero ja yritä uudelleen. Napsauta täältä jotta voit siirtyä antamasi sarjanumeron tuotesivulle Eatonin mukaan sarjanumero on epäilyttävä, yritä uudelleen tai ilmoita tästä ongelmasta lisäavun saamiseksi.
Sarjanumero
Nollaus Eatonin mukaan sarjanumero on epäilyttävä, yritä uudelleen tai ilmoita tästä ongelmasta lisäavun saamiseksi. Eaton ei tunnista sarjanumeroa, ja se on virheellinen. Käytä tätä lomaketta ilmoita tästä ongelmasta lisäavun saamiseksi.
Anna 6-numeroinen todennuskoodi
Antamasi tuote on epäilyttävä! Yritä uudelleen tai ilmoita tästä ongelmasta lisäavun saamiseksi. Antamasi todennuskoodi ei vastaa tämän sarjanumeron tietoja. Yritä uudelleen tai ilmoita tästä ongelmasta lisäavun saamiseksi. Virheellinen todennuskoodi. Pituuden on oltava 6 merkkiä ilmoita tästä ongelmasta lisäavun saamiseksi. Todennuskoodi vaaditaan ilmoita tästä ongelmasta lisäavun saamiseksi.
Suorita Captcha-vahvistus ennen todennusta.
Ota yhteyttä ongelmasta ilmoittamiseksi
x
Ilmoita ongelmasta
Anna koko nimesi.
x
Kiitos, ongelmasi on lähetetty. Tuotetiimimme ottaa sinuun pian yhteyttä.
Huom: Jos tiedosto/tiedostoja puuttuu .zip-latauksesta, joukkolataus ei tue tiedostotyyppiä.