Eaton Moeller® series MSC-D DOL starter, 380 V 400 V 415 V: 15 kW, Ir= 25 - 32 A, 24 V DC, DC voltage MSC-D-32-M32(24VDC)
Product Name |
Eaton Moeller® series MSC-D DOL starter
|
Catalog Number |
283170
|
EL Number |
3732170
|
EAN |
4015082831707
|
Product Length/Depth |
123.4 mm
|
Product Height |
228 mm
|
Product Width |
45 mm
|
Product Weight |
0.975 kg
|
Certifications |
CSA-C22.2 No. 60947-4-1-14
UL IEC/EN 60947-4-1 UL File No.: E36332 VDE 0660 CSA CSA Class No.: 3211-24 CE UL Category Control No.: NLRV CSA File No.: 012528 UL 60947-4-1 |
Fitted with: |
Short-circuit release
|
Functions |
Temperature compensated overload protection
|
Class |
CLASS 10 A
|
Connection |
Screw terminals
|
Connection to SmartWire-DT |
No
|
Coordination type |
2
|
Degree of protection |
IP00
NEMA Other |
Model |
IEC starter
|
Mounting method |
DIN rail
|
Number of auxiliary contacts (normally closed contacts) |
0
|
Number of auxiliary contacts (normally open contacts) |
1
|
Overload release current setting - min |
25 A
|
Overload release current setting - max |
32 A
|
Overvoltage category |
III
|
Pollution degree |
3
|
Rated impulse withstand voltage (Uimp) |
6000 V AC
|
Suitable for |
Also motors with efficiency class IE3
|
Type |
Starter with Bi-Metal release
|
Voltage type |
DC
|
Ambient operating temperature - min |
-25 °C
|
Ambient operating temperature - max |
55 °C
|
Rated operational current (Ie) |
29.3 A
|
Rated operational current (Ie) at AC-3, 380 V, 400 V, 415 V |
32 A
|
Rated operational power at AC-3, 220/230 V, 50 Hz |
7.5 kW
|
Rated operational power at AC-3, 380/400 V, 50 Hz |
15 kW
|
Rated operational voltage |
230 - 415 V AC
|
Switching capacity (auxiliary contacts, general use) |
1 A, 250 V DC, (UL/CSA)
15 A, 600 V AC, (UL/CSA) |
Switching capacity (auxiliary contacts, pilot duty) |
A600, AC operated (UL/CSA)
P300, DC operated (UL/CSA) |
Rated conditional short-circuit current (Iq), type 2, 380 V, 400 V, 415 V |
50000 A
|
Short-circuit current rating (basic rating) |
5 kA, SCCR (UL/CSA)
1 A, max. Fuse, SCCR (UL/CSA) 15 A, max. CB, SCCR (UL/CSA) |
Short-circuit release (Irm) - max |
496 A
|
Power consumption (sealing) at DC |
0.86 W
|
Rated control supply voltage (Us) at AC, 50 Hz - min |
0 V
|
Rated control supply voltage (Us) at AC, 50 Hz - max |
0 V
|
Rated control supply voltage (Us) at AC, 60 Hz - min |
0 V
|
Rated control supply voltage (Us) at AC, 60 Hz - max |
0 V
|
Rated control supply voltage (Us) at DC - min |
24 V
|
Rated control supply voltage (Us) at DC - max |
24 V
|
Equipment heat dissipation, current-dependent Pvid |
19.5 W
|
Heat dissipation capacity Pdiss |
0 W
|
Heat dissipation per pole, current-dependent Pvid |
6.5 W
|
Rated operational current for specified heat dissipation (In) |
32 A
|
Static heat dissipation, non-current-dependent Pvs |
0.9 W
|
10.2.2 Corrosion resistance |
Meets the product standard's requirements.
|
10.2.3.1 Verification of thermal stability of enclosures |
Meets the product standard's requirements.
|
10.2.3.2 Verification of resistance of insulating materials to normal heat |
Meets the product standard's requirements.
|
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects |
Meets the product standard's requirements.
|
10.2.4 Resistance to ultra-violet (UV) radiation |
Meets the product standard's requirements.
|
10.2.5 Lifting |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.2.6 Mechanical impact |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.2.7 Inscriptions |
Meets the product standard's requirements.
|
10.3 Degree of protection of assemblies |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.4 Clearances and creepage distances |
Meets the product standard's requirements.
|
10.5 Protection against electric shock |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.6 Incorporation of switching devices and components |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.7 Internal electrical circuits and connections |
Is the panel builder's responsibility.
|
10.8 Connections for external conductors |
Is the panel builder's responsibility.
|
10.9.2 Power-frequency electric strength |
Is the panel builder's responsibility.
|
10.9.3 Impulse withstand voltage |
Is the panel builder's responsibility.
|
10.9.4 Testing of enclosures made of insulating material |
Is the panel builder's responsibility.
|
10.10 Temperature rise |
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
|
10.11 Short-circuit rating |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
10.12 Electromagnetic compatibility |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
10.13 Mechanical function |
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
|