Reset
Eaton Moeller series NZM - Molded Case Circuit Breaker. Circuit-breaker, 3p, 18A, box terminals
Product Name |
Eaton Moeller series NZM molded case circuit breaker magnetic
|
Catalog Number |
107656
|
Model Code |
NZMB2-S18-BT-CNA
|
EAN |
4015081073221
|
Product Length/Depth |
149 mm
|
Product Height |
195 mm
|
Product Width |
105 mm
|
Product Weight |
2.345 kg
|
Compliances |
RoHS conform
|
Certifications |
Specially designed for North America
UL (Category Control Number DKPU2) UL/CSA CSA (Class No. 1432-01) CSA (File No. 22086) UL 489 CSA certified UL listed CSA-C22.2 No. 5-09 UL (File No. E31593) |
Voltage rating |
440 V - 440 V
|
Amperage Rating |
18 A
|
Short-circuit total breaktime |
< 10 ms
|
Electrical connection type of main circuit |
Frame clamp
|
Isolation |
300 V AC (between the auxiliary contacts)
500 V AC (between auxiliary contacts and main contacts) |
Overvoltage category |
III
|
Pollution degree |
3
|
Lifespan, electrical |
7500 operations at 400 V AC-1
6500 operations at 415 V AC-3 |
Direction of incoming supply |
As required
|
Amperage Rating |
18 A
|
Short-circuit total breaktime |
< 10 ms
|
Electrical connection type of main circuit |
Frame clamp
|
Isolation |
300 V AC (between the auxiliary contacts)
500 V AC (between auxiliary contacts and main contacts) |
Overvoltage category |
III
|
Pollution degree |
3
|
Lifespan, electrical |
7500 operations at 400 V AC-1
6500 operations at 415 V AC-3 |
Direction of incoming supply |
As required
|
Mounting Method |
DIN rail (top hat rail) mounting optional
Built-in device fixed built-in technique Fixed |
Degree of protection |
IP20
IP20 (basic degree of protection, in the operating controls area) |
Degree of protection (IP), front side |
IP66 (with door coupling rotary handle)
IP40 (with insulating surround) |
Degree of protection (terminations) |
IP00 (terminations, phase isolator and strip terminal)
IP10 (tunnel terminal) |
Shock resistance |
20 g (half-sinusoidal shock 20 ms)
|
Climatic proofing |
Damp heat, constant, to IEC 60068-2-78
Damp heat, cyclic, to IEC 60068-2-30 |
Lifespan, mechanical |
20000 operations
|