Reset
NZMH2-MX200-NA. NZM2 PXR20 circuit breaker, 200A, 3p, Screw terminal, UL/CSA
Product Name |
Eaton Moeller series NZM molded case circuit breaker electronic
|
Catalog Number |
192464
|
Model Code |
NZMH2-MX200-NA
|
EAN |
4015081931927
|
Product Length/Depth |
149 mm
|
Product Height |
195 mm
|
Product Width |
105 mm
|
Product Weight |
2.345 kg
|
Compliances |
RoHS conform
|
Certifications |
IEC 60947-2
UL 489 CSA (Class No. 1432-01) CSA certified Specially designed for North America IEC UL (File No. E31593) UL listed UL (Category Control Number DIVQ) CE marking UL/CSA UL508 CSA (File No. 22086) CSA-C22.2 No. 5-09 |
Voltage rating |
690 V - 690 V
|
Rated operating voltage Ue (UL) - max |
480 V
|
Rated insulation voltage (Ui) |
690 V
|
Amperage Rating |
200 A
|
Instantaneous current setting (Ii) - min |
400 A
|
Instantaneous current setting (Ii) - max |
3000 A
|
Overload current setting (Ir) - min |
80 A
|
Overload current setting (Ir) - max |
200 A
|
Short-circuit release non-delayed setting - min |
400 A
|
Short-circuit release non-delayed setting - max |
3000 A
|
Rated short-circuit breaking capacity Ics (IEC/EN 60947) at 400/415 V, 50/60 Hz |
150 kA
|
Rated short-circuit breaking capacity Ics (IEC/EN 60947) at 440 V, 50/60 Hz |
150 kA
|
Rated operating power at AC-3, 230 V |
55 kW
|
Rated operating power at AC-3, 400 V |
110 kW
|
Electrical connection type of main circuit |
Screw connection
|
Handle type |
Rocker lever
|
Direction of incoming supply |
As required
|
Amperage Rating |
200 A
|
Instantaneous current setting (Ii) - min |
400 A
|
Instantaneous current setting (Ii) - max |
3000 A
|
Overload current setting (Ir) - min |
80 A
|
Overload current setting (Ir) - max |
200 A
|
Short-circuit release non-delayed setting - min |
400 A
|
Short-circuit release non-delayed setting - max |
3000 A
|
Rated short-circuit breaking capacity Ics (IEC/EN 60947) at 400/415 V, 50/60 Hz |
150 kA
|
Rated short-circuit breaking capacity Ics (IEC/EN 60947) at 440 V, 50/60 Hz |
150 kA
|
Rated operating power at AC-3, 230 V |
55 kW
|
Rated operating power at AC-3, 400 V |
110 kW
|
Electrical connection type of main circuit |
Screw connection
|
Handle type |
Rocker lever
|
Direction of incoming supply |
As required
|
Mounting Method |
Built-in device fixed built-in technique
Fixed |
Degree of protection |
IP20
|
Switch off technique |
Electronic
|