Reset
Eaton Moeller® series EASY I/O expansion, For use with easyE4, 12/24 V DC, 24 V AC, Inputs expansion (number) digital: 8, screw terminal
| Product Name |
Eaton Moeller® series EASY I/O expansion
|
| Catalog Number |
197218
|
| EAN |
4015080892793
|
| Product Length/Depth |
58 mm
|
| Product Height |
90 mm
|
| Product Width |
72 mm
|
| Product Weight |
0.25 kg
|
| Certifications |
IEC/EN 61000-6-3
IEC 60068-2-27 IEC/EN 61000-6-2 IEC 60068-2-30 IEC/EN 61000-4-2 IEC/EN 61131-2 CSA-C22.2 No. 61010 IEC 60068-2-6 CULus per UL 61010 EN 50178 EN 61010 UL Listed UL Category Control No.: NRAQ, NRAQ7 UL File No.: E205091 DNV GL CE UL hazardous location class I UL hazardous location group B (hydrogen) UL hazardous location division 2 UL hazardous location group D (propane) UL hazardous location group A (acetylene) UL hazardous location group C (ethylene) |
| Catalog Notes |
fitted with two controlled relays
|
| Features |
Expansion device
Expandable |
| Fitted with: |
Relay output
|
| Indication |
LCD-display base unit used as status indication of Digital inputs 12 V DC
LCD-display base unit used as status indication of Digital inputs 24 V DC |
| Degree of protection |
IP20
|
| Input frequency |
50/60 Hz (Digital inputs, at 24 V DC)
|
| Insulation resistance |
According to EN 50178, EN 61010-2-201, UL61010-2-201, CSA-C22.2 NO. 61010-2-201
|
| Lifespan, electrical |
25,000 Operations (Filament bulb load at 500 W, 115/120 V AC)
25,000 Operations (Filament bulb load at 1000 W, 230/240 V AC) 25,000 Operations (Fluorescent lamp load 10 x 58 W at 230/240 V AC, with upstream electrical device) 25,000 Operations (Fluorescent lamp load 10 x 58 W at 230/240 V AC, uncompensated) 25,000 Operations (Fluorescent lamp load 1 x 58 W at 230/240 V AC, conventional, compensated) |
| Lifespan, mechanical |
10,000,000 Operations
|
| Mounting method |
Top-hat rail fixing (according to IEC/EN 60715, 35 mm)
Wall mounting/direct mounting Screw fixing using fixing brackets ZB4-101-GF1 (accessories) Front build in possible Rail mounting possible |
| Overvoltage category |
III
|
| Pollution degree |
2
|
| Product category |
Control relays easyE4
|
| Protection |
B16 circuit breaker or 8 A (T) fuse, Protection of an Output relay
|
| Protocol |
MODBUS
TCP/IP |
| Rated impulse withstand voltage (Uimp) |
6 kV (contact-coil)
|
| Residual ripple |
≤ 5 %
|
| Software |
EASYSOFT-SWLIC/easySoft
|
| Switching frequency |
10 Hz, Relay outputs
0.5 Hz, Inductive load, Relay outputs 2 Hz, Resistive load/lamp load, Relay outputs |
| Type |
easyE4 extension
|
| Utilization category |
B 300 Light Pilot Duty, UL/CSA Control Circuit Rating Codes AC
R 300 Light Pilot Duty, UL/CSA Control Circuit Rating Codes DC |
| Voltage type |
AC/DC
|
| Drop and topple |
50 mm Drop height, Drop to IEC/EN 60068-2-31
|
| Height of fall (IEC/EN 60068-2-32) - max |
0.3 m
|
| Mounting position |
Vertical
Horizontal |
| Shock resistance |
15 g, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 11 ms, 18 Impacts
|
| Vibration resistance |
According to IEC/EN 60068-2-6
10 - 57 Hz, 0.15 mm constant amplitude 57 - 150 Hz, 2 g constant acceleration |
| Air pressure |
795 - 1080 hPa (operation)
|
| Ambient operating temperature - min |
-25 °C
|
| Ambient operating temperature - max |
55 °C
|
| Ambient storage temperature - min |
-40 °C
|
| Ambient storage temperature - max |
70 °C
|
| Environmental conditions |
Clearance in air and creepage distances according to EN 50178, EN 61010-2-201, UL61010-2-201, CSA-C22.2 NO. 61010-2-201
Condensation: prevent with appropriate measures |
| Relative humidity |
5 - 95 % (IEC 60068-2-30, IEC 60068-2-78)
|
| Air discharge |
8 kV
|
| Burst impulse |
According to IEC/EN 61000-4-4
2 kV, Supply cable 2 kV, Signal cable |
| Contact discharge |
6 kV
|
| Electromagnetic fields |
10 V/m at 0.8 - 1.0 GHz (according to IEC EN 61000-4-3)
3 V/m at 1.4 - 2 GHz (according to IEC EN 61000-4-3) 1 V/m at 2.0 - 2.7 GHz (according to IEC EN 61000-4-3) |
| Immunity to line-conducted interference |
10 V (according to IEC/EN 61000-4-6)
|
| Radio interference class |
Class B (EN 61000-6-3)
|
| Surge rating |
1 kV, Supply cables, symmetrical, power pulses (Surge), EMC
2 kV, Supply cables, asymmetrical, power pulses (Surge), EMC According to IEC/EN 61000-4-5, power pulses (Surge), EMC |
| Voltage dips |
≤ 1 ms from rated voltage (12 V DC)
10 ms |
| Terminal capacity |
0.2 - 4 mm² (AWG 22 - 12), solid
0.2 - 2.5 mm² (22 - 12 AWG), flexible with ferrule |
| Screwdriver size |
3.5 x 0.8 mm, Terminal screw
|
| Tightening torque |
0.6 Nm, Screw terminals
|
| Conventional thermal current Ith of auxiliary contacts (1-pole, open) |
5 A
|
| Power consumption |
3 W
|
| Rated breaking capacity |
300000 Operations at AC-15, 250 V AC, 3 A (600 Ops./h)
200000 Operations at DC-13, 24 V DC, 1 A (500 Ops./h) |
| Rated insulation voltage (Ui) |
240 V
|
| Rated operational voltage |
24 V AC (-15 %/+10 % - power supply)
10.2 - 28.8 V DC 24 V DC (digital inputs) Max. 300 V DC 12 V DC (digital inputs) Max. 300 V AC 240 V AC 12/24 V DC (-15 %/+ 20 % - power supply) 20.4 - 26.4 V AC 24 V AC (digital inputs) |
| Supply frequency |
50/60 Hz (± 5%)
|
| Supply voltage at AC, 50 Hz - min |
85 VAC
|
| Supply voltage at AC, 50 Hz - max |
264 VAC
|
| Supply voltage at DC - min |
10.2 VDC
|
| Supply voltage at DC - max |
28.8 VDC
|
| Uninterrupted current |
1 A DC, at R 300 (UL/CSA)
10 A AC, at 240 V AC (UL/CSA) 8 A DC, at 24 V DC (UL/CSA) 5 A AC, max. thermal continuous current cos ϕ = 1 at B 300 (UL/CSA) |
| Short-circuit protection |
≥ 1A (T), Fuse, Power supply
|
| Connection type |
Screw terminal
|
| Cable length |
100 m, unscreened, Digital inputs 12 V DC
100 m, unscreened, Digital inputs 24 V AC 100 m, unscreened, Digital inputs 24 V DC 40 m (max. per input), Digital inputs 24 V DC |
| Delay time |
0.1 ms typ., Digital inputs 24 V DC (I1 - I8), Delay time from 0 to 1, Debounce OFF
20 ms, Digital Inputs 12 V DC, Delay time from 1 to 0, Debounce ON 0.2 ms typ., Digital inputs 24 V DC (I1 - I8), Delay time from 1 to 0, Debounce OFF 20 ms, Digital Inputs 12 V DC, Delay time from 0 to 1, Debounce ON 0.2 ms typ., Digital inputs 12 V DC (I1 - I8), Delay time from 1 to 0, Debounce OFF 0.15 ms typ., Digital inputs 12 V DC (I1 - I8), Delay time from 0 to 1, Debounce OFF |
| Input current |
3.3 mA (I5 - I8, at 24 V DC, at signal 1)
200 mA |
| Input voltage |
Condition 1: ≥ 15 V DC (I1 - I8, Digital inputs, 24 V DC)
Signal 0: ≤ 5 V DC (I1 - I4, Digital inputs, 12 V DC) At signal 0: ≤ 5 V (I1 - I8, sinusoidal, Digital inputs, 24 V DC) At signal 1: ≥ 15 V (I1 - I8, sinusoidal, Digital inputs, 24 V DC) Signal 0: ≤ 5 V DC (I1 - I8, Digital inputs, 24 V DC) Status 0: ≤ 15 V DC (I1 - I4, Digital inputs, 24 V DC) |
| Making/breaking capacity |
3600/360 VA (AC, at B 300)
28/28 VA (DC, at R 300) |
| Number of inputs (analog) |
0
|
| Number of inputs (digital) |
8
|
| Number of outputs (analog) |
0
|
| Number of outputs (digital) |
8
|
| Output |
8 Relay Outputs
Relay outputs in groups of 1 > 500 mA (Relay outputs, Recommended for load: 12 V AC/DC) Voltage Current |
| Parallel switching |
Not permitted
|
| Explosion safety category for gas |
None
|
| Potential isolation |
Between Digital inputs 24 V DC and base unit: yes
Between Digital inputs 24 V DC and Outputs: yes Between Digital inputs 24 V DC and expansion devices: yes Between Relay outputs and Inputs: yes Basic isolation: 600 V AC (Relay outputs) Safe isolation according to EN 50178: 300 V AC (Relay outputs) Between Digital inputs 24 V AC and base unit: yes Between Digital inputs 12 V DC and Outputs: yes Between Digital inputs 24 V AC and expansion devices: yes Between Digital inputs 12 V DC and expansion devices: yes Between Relay outputs and Power supply: yes Between Relay outputs and expansion devices: yes Between Digital inputs 12 V DC and base unit: yes Between Digital inputs 24 V AC and Outputs: yes Between Relay outputs: yes |
| Protection against polarity reversal |
Yes, for supply voltage (Siemens MPI optional)
|
| Explosion safety category for dust |
None
|
| Safe isolation |
300 V AC, Between two contacts, According to EN 50178
300 V AC, Between coil and contact, According to EN 50178 |
| Equipment heat dissipation, current-dependent Pvid |
2 W
|
| Heat dissipation capacity Pdiss |
0 W
|
| Heat dissipation per pole, current-dependent Pvid |
0 W
|
| Rated operational current for specified heat dissipation (In) |
0 A
|
| Static heat dissipation, non-current-dependent Pvs |
3 W
|
| 10.2.2 Corrosion resistance |
Meets the product standard's requirements.
|
| 10.2.3.1 Verification of thermal stability of enclosures |
Meets the product standard's requirements.
|
| 10.2.3.2 Verification of resistance of insulating materials to normal heat |
Meets the product standard's requirements.
|
| 10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects |
Meets the product standard's requirements.
|
| 10.2.4 Resistance to ultra-violet (UV) radiation |
Meets the product standard's requirements.
|
| 10.2.5 Lifting |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.2.6 Mechanical impact |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.2.7 Inscriptions |
Meets the product standard's requirements.
|
| 10.3 Degree of protection of assemblies |
Meets the product standard's requirements.
|
| 10.4 Clearances and creepage distances |
Meets the product standard's requirements.
|
| 10.5 Protection against electric shock |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.6 Incorporation of switching devices and components |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.7 Internal electrical circuits and connections |
Is the panel builder's responsibility.
|
| 10.8 Connections for external conductors |
Is the panel builder's responsibility.
|
| 10.9.2 Power-frequency electric strength |
Is the panel builder's responsibility.
|
| 10.9.3 Impulse withstand voltage |
Is the panel builder's responsibility.
|
| 10.9.4 Testing of enclosures made of insulating material |
Is the panel builder's responsibility.
|
| 10.10 Temperature rise |
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
|
| 10.11 Short-circuit rating |
Is the panel builder's responsibility.
|
| 10.12 Electromagnetic compatibility |
Is the panel builder's responsibility.
|
| 10.13 Mechanical function |
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
|