Download document () of 20

169147
Model code: DX-LM3-370

Eaton DX Motor choke, three-phase, 750 V + 0% (0 - 400 Hz), V AC, 370 A, 0.12 mH

General specifications

Product Name
Eaton DX Motor choke
Catalog Number
169147
EAN
4015081656257
Model Code
DX-LM3-370
Product Length/Depth
600 mm
Product Height
750 mm
Product Width
800 mm
Product Weight
61.7 kg
Certifications
UL
UL Category Control No.: XPTQ2, XPTQ8
UL File No.: E167225
CE
CSA-C22.2 No. 14
UL 508C
VDE 0570 Part 2-20/2001-04
UL report applies to both US and Canada
CSA
IEC/EN61800-5
IEC/EN 61558-2-20-2000
Certified by UL for use in Canada
IEC/EN61800-3

Features & Functions

Fitted with:
PE stud
Connection lugs
Number of phases
3
Number of poles
Three-pole

General

Bore diameter
14 mm
Degree of protection
IP00
NEMA Other
Duty factor
100 %
Insulation class
F
Product Category
Accessories
Suitable as
Output reactance coil
Suitable for
Branch circuits, (UL/CSA)
Switching frequency
3 kHz
Used with
DA1
DG1

Ambient conditions, mechanical

Mounting position
Free surrounding areas > 50 mm
Suspended horizontally
Standing vertically
Shock resistance
Shock duration: 11 ms
3 shocks
Vibration resistance
10 - 55 Hz, 0.35 mm
0 - 150 Hz, 1 g

Climatic environmental conditions

Altitude
Max. 5000 m with current reduction
Max. 1000 m
Ambient operating temperature - max
40 °C
Ambient operating temperature - min
-25 °C
Ambient storage temperature - max
85 °C
Ambient storage temperature - min
-25 °C
Operating temperature details
-25 - 40 °C (up to 70 °C with current derating)

Terminal capacities

Tightening torque
15.5 Nm, Screw terminals

Connection

Connection lug
Cu 40 x 5 mm²

Electrical rating

Permissible connection voltage
Max. 550 V AC (0 - 400 Hz)
Power loss
685 W (3 kHz)
Rated current (Ith) at rated voltage DC - max
0 A
Rated frequency - min
0 Hz
Rated frequency - max
400 Hz
Rated inductance
0.12 mH
Rated operational current (Ie) - min
370 A
Rated operational current (Ie) - max
370 A
Rated operational voltage (Ue) - max
750 V
Relative short-circuit voltage
20.2 %
Voltage rating - max
480 V

Design verification

Equipment heat dissipation, current-dependent Pvid
685 W
Heat dissipation capacity Pdiss
0 W
Heat dissipation per pole, current-dependent Pvid
0 W
Rated operational current for specified heat dissipation (In)
370 A
Static heat dissipation, non-current-dependent Pvs
0 W
10.2.2 Corrosion resistance
Meets the product standard's requirements.
10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard's requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard's requirements.
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects
Meets the product standard's requirements.
10.2.4 Resistance to ultra-violet (UV) radiation
Meets the product standard's requirements.
10.2.5 Lifting
Does not apply, since the entire switchgear needs to be evaluated.
10.2.6 Mechanical impact
Does not apply, since the entire switchgear needs to be evaluated.
10.2.7 Inscriptions
Meets the product standard's requirements.
10.3 Degree of protection of assemblies
Does not apply, since the entire switchgear needs to be evaluated.
10.4 Clearances and creepage distances
Meets the product standard's requirements.
10.5 Protection against electric shock
Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and components
Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections
Is the panel builder's responsibility.
10.8 Connections for external conductors
Is the panel builder's responsibility.
10.9.2 Power-frequency electric strength
Is the panel builder's responsibility.
10.9.3 Impulse withstand voltage
Is the panel builder's responsibility.
10.9.4 Testing of enclosures made of insulating material
Is the panel builder's responsibility.
10.10 Temperature rise
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.12 Electromagnetic compatibility
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.13 Mechanical function
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.

Export product specification