Eaton DC1 Variable frequency drive, 400 V AC, 3-phase, 5.8 A, 2.2 kW, IP66/NEMA 4X, Radio interference suppression filter, Brake chopper, 7-digital display assembly, Additional PCB protection, UV resistant, FS2
| Product Name |
Eaton DC1 Variable frequency drive
|
| Catalog Number |
199435
|
| EAN |
4015081978243
|
| Model Code |
DC1-345D8FB-A66OE1
|
| Product Length/Depth |
182 mm
|
| Product Height |
257 mm
|
| Product Width |
188 mm
|
| Product Weight |
3.5 kg
|
| Certifications |
RCM
IEC/EN 61800-5-1 UL Category Control No.: NMMS, NMMS7 UL File No.: E172143 UL report applies to both US and Canada UkrSEPRO EAC IEC/EN61800-5 IEC/EN 61800-3 RoHS, ISO 9001 CSA-C22.2 No. 14 UL CE CE marking IEC/EN 61800-2 UL Listed CUL UL 508C Certified by UL for use in Canada |
| Catalog Notes |
|
| Features |
Parameterization: drivesConnect
Parameterization: Keypad Parameterization: drivesConnect mobile (App) Parameterization: Fieldbus |
| Fitted with: |
Brake chopper
Internal DC link Breaking resistance Radio interference suppression filter PC connection UV resistance 7-digital display assembly Additional PCB protection IGBT inverter Control unit |
| Functions |
4-quadrant operation possible
|
| Cable length |
100 m, screened, maximum permissible cable length
300 m, unscreened, with motor choke, maximum permissible, Motor feeder C3 ≤ 25 m, maximum motor cable length 200 m, screened, with motor choke, maximum permissible cable length C2 ≤ 5 m, maximum motor cable length 150 m, unscreened, maximum permissible cable length |
| Communication interface |
SmartWire-DT, optional
Modbus RTU, built in OP-Bus (RS485), built in CANopen®, built in |
| Connection to SmartWire-DT |
No
|
| Degree of protection |
IP66
NEMA 4X |
| Electromagnetic compatibility |
1st and 2nd environments (according to EN 61800-3)
|
| Frame size |
FS2
|
| Mounting position |
Vertical
|
| Product category |
Variable frequency drives
|
| Protection |
Finger and back-of-hand proof, Protection against direct contact (BGV A3, VBG4)
|
| Protocol |
EtherNet/IP
CAN Other bus systems MODBUS |
| Radio interference class |
Optional external radio interference suppression filter for longer motor cable lengths and for use in different EMC environments
C2, C3: depending on the motor cable length, the connected load, and ambient conditions. External radio interference suppression filters (optional) may be necessary. |
| Suitable for |
Branch circuits, (UL/CSA)
|
| Altitude |
Max. 4000 m
Above 1000 m with 1 % derating per 100 m |
| Ambient operating temperature - min |
-20 °C
|
| Ambient operating temperature - max |
40 °C
|
| Ambient storage temperature - min |
-40 °C
|
| Ambient storage temperature - max |
60 °C
|
| Climatic proofing |
< 95 average relative humidity (RH), no condensation, no corrosion
|
| Efficiency |
97 % (η)
|
| Heat dissipation capacity Pdiss |
0 W
|
| Input current ILN at 150% overload |
7.5 A
|
| Leakage current at ground IPE - max |
12.6 mA
|
| Mains switch-on frequency |
Maximum of one time every 30 seconds
|
| Mains voltage - min |
380 V
|
| Mains voltage - max |
480 V
|
| Operating mode |
U/f control
Sensorless vector control (SLV) Synchronous reluctance motors PM motors Speed control with slip compensation BLDC motors |
| Output frequency - min |
0 Hz
|
| Output frequency - max |
500 Hz
|
| Output voltage (U2) |
400 V AC, 3-phase
480 V AC, 3-phase |
| Overload current IL at 150% overload |
8.7 A
|
| Rated control supply voltage |
10 V DC (Us, max. 10 mA)
|
| Rated frequency - min |
48 Hz
|
| Rated frequency - max |
62 Hz
|
| Rated operational current (Ie) |
5.8 A at 150% overload (at an operating frequency of 6 kHz and an ambient air temperature of +40 °C)
|
| Rated operational power at 380/400 V, 50 Hz, 3-phase |
1.5 kW
|
| Rated operational voltage |
400 V AC, 3-phase
480 V AC, 3-phase |
| Resolution |
0.1 Hz (Frequency resolution, setpoint value)
|
| Short-circuit protection rating |
10 A, UL (Class CC or J), Safety device (fuse or miniature circuit-breaker), Power Wiring
|
| Starting current - max |
175 % IH
|
| Supply frequency |
50/60 Hz
|
| Switching frequency |
8 kHz, 4 - 32 kHz adjustable (audible), fPWM, Power section, Main circuit
|
| System configuration type |
AC supply systems with earthed center point
|
| Voltage rating - max |
480 V
|
| Assigned motor current IM at 400 V, 50 Hz, 150% overload |
5 A
|
| Assigned motor current IM at 440 - 480 V, 60 Hz, 150% overload |
4.8 A
|
| Assigned motor power at 460/480 V, 60 Hz, 3-phase |
3 HP
|
| Apparent power at 400 V |
4.02 kVA
|
| Apparent power at 480 V |
4.82 kVA
|
| Braking resistance |
200 Ω
|
| Braking torque |
Max. 100 % of rated operational current Ie with external braking resistor - Main circuit
Max. 30 % MN, Standard - Main circuit Max. 100 % of rated operational current Ie, variable, DC - Main circuit |
| Switch-on threshold for the braking transistor |
780 VDC
|
| Number of inputs (analog) |
2 (parameterizable, 0 - 10 V DC, 0/4 - 20 mA)
|
| Number of inputs (digital) |
4 (parameterizable, 10 - 30 V DC)
|
| Number of outputs (analog) |
1
|
| Number of outputs (digital) |
1
|
| Number of relay outputs |
1 (parameterizable, N/O, 6 A (250 V, AC-1) / 5 A (30 V, DC-1))
|
| Heat dissipation capacity Pdiss |
0 W
|
| Heat dissipation per pole, current-dependent Pvid |
0 W
|
| 10.2.2 Corrosion resistance |
Meets the product standard's requirements.
|
| 10.2.3.1 Verification of thermal stability of enclosures |
Meets the product standard's requirements.
|
| 10.2.3.2 Verification of resistance of insulating materials to normal heat |
Meets the product standard's requirements.
|
| 10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects |
Meets the product standard's requirements.
|
| 10.2.4 Resistance to ultra-violet (UV) radiation |
Meets the product standard's requirements.
|
| 10.2.5 Lifting |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.2.6 Mechanical impact |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.2.7 Inscriptions |
Meets the product standard's requirements.
|
| 10.3 Degree of protection of assemblies |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.4 Clearances and creepage distances |
Meets the product standard's requirements.
|
| 10.5 Protection against electric shock |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.6 Incorporation of switching devices and components |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.7 Internal electrical circuits and connections |
Is the panel builder's responsibility.
|
| 10.8 Connections for external conductors |
Is the panel builder's responsibility.
|
| 10.9.2 Power-frequency electric strength |
Is the panel builder's responsibility.
|
| 10.9.3 Impulse withstand voltage |
Is the panel builder's responsibility.
|
| 10.9.4 Testing of enclosures made of insulating material |
Is the panel builder's responsibility.
|
| 10.10 Temperature rise |
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
|
| 10.11 Short-circuit rating |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
| 10.12 Electromagnetic compatibility |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
| 10.13 Mechanical function |
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
|