Eaton Moeller® series P3 Main switch, P3, 30 A, flush mounting, 3 pole, With red rotary handle and yellow locking ring, Lockable in the 0 (Off) position, UL/CSA
Product Name |
Eaton Moeller® series P3 Main switch
|
Catalog Number |
237892
|
EAN |
4015082378929
|
Model Code |
P3-30/EA/SVB-MCS
|
Product Length/Depth |
150 mm
|
Product Height |
114 mm
|
Product Width |
90 mm
|
Product Weight |
0.374 kg
|
Certifications |
UL
CSA UL File No.: E148671 UL489 CSA File No.: 1342868 (LR12528) UL 489 |
Features |
Version as main switch
Version as maintenance-/service switch Version as emergency stop installation |
Fitted with: |
Red rotary handle and yellow locking ring
|
Functions |
Interlockable
|
Locking facility |
Lockable in the 0 (Off) position
|
Number of poles |
3
|
Degree of protection |
NEMA 12
|
Degree of protection (front side) |
IP65
|
Lifespan, mechanical |
100,000 Operations
|
Mounting method |
Flush mounting
|
Mounting position |
As required
|
Operating frequency |
1200 Operations/h
|
Overvoltage category |
III
|
Pollution degree |
3
|
Product Category |
Main switch
|
Rated impulse withstand voltage (Uimp) |
6000 V AC
|
Safe isolation |
440 V AC, Between the contacts, According to EN 61140
|
Safety parameter (EN ISO 13849-1) |
B10d values as per EN ISO 13849-1, table C.1
|
Shock resistance |
15 g, Mechanical, According to IEC/EN 60068-2-27, Half-sinusoidal shock 20 ms
|
Suitable for |
Branch circuits, feeder circuits, (UL/CSA)
Front mounting 4-hole |
Ambient operating temperature - min |
-25 °C
|
Ambient operating temperature - max |
50 °C
|
Ambient operating temperature (enclosed) - min |
-25 °C
|
Ambient operating temperature (enclosed) - max |
40 °C
|
Climatic proofing |
Damp heat, cyclic, to IEC 60068-2-30
Damp heat, constant, to IEC 60068-2-78 |
Terminal capacity |
14 - 2 AWG, solid or flexible with ferrule
|
Screw size |
M5, Terminal screw
|
Tightening torque |
26.5 lb-in, Screw terminals
|
Rated operational power at AC-3, 380/400 V, 50 Hz |
0 kW
|
Rated operational power at AC-23A, 400 V, 50 Hz |
0 kW
|
Rated operational voltage (Ue) at AC - max |
690 V
|
Rated uninterrupted current (Iu) |
30 A
|
Uninterrupted current |
Rated uninterrupted current Iu is specified for max. cross-section.
|
Rated conditional short-circuit current (Iq) |
4 kA (Load side)
100 kA (Supply side) |
Rated short-time withstand current (Icw) |
0 kA
|
Short-circuit current rating (high fault) |
30 A, Class RK5, max. Fuse, SCCR (UL/CSA)
10 kA, SCCR (UL/CSA) |
Short-circuit protection rating |
100 A gG/gL, Fuse, Contacts
|
Load rating |
2 x Iₑ (with intermittent operation class 12, 25 % duty factor)
1.6 x Iₑ (with intermittent operation class 12, 40 % duty factor) 1.3 x Iₑ (with intermittent operation class 12, 60 % duty factor) |
Switching capacity (main contacts, general use) |
30 A, Rated uninterrupted current max. (UL/CSA)
|
Number of auxiliary contacts (change-over contacts) |
0
|
Number of auxiliary contacts (normally closed contacts) |
0
|
Number of auxiliary contacts (normally open contacts) |
0
|
Actuator color |
Red
|
Actuator type |
Door coupling rotary drive
|
Heat dissipation capacity Pdiss |
0 W
|
Rated operational current for specified heat dissipation (In) |
30 A
|
10.2.2 Corrosion resistance |
Meets the product standard's requirements.
|
10.2.3.1 Verification of thermal stability of enclosures |
Meets the product standard's requirements.
|
10.2.3.2 Verification of resistance of insulating materials to normal heat |
Meets the product standard's requirements.
|
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects |
Meets the product standard's requirements.
|
10.2.4 Resistance to ultra-violet (UV) radiation |
UV resistance only in connection with protective shield.
|
10.2.5 Lifting |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.2.6 Mechanical impact |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.2.7 Inscriptions |
Meets the product standard's requirements.
|
10.3 Degree of protection of assemblies |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.4 Clearances and creepage distances |
Meets the product standard's requirements.
|
10.5 Protection against electric shock |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.6 Incorporation of switching devices and components |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.7 Internal electrical circuits and connections |
Is the panel builder's responsibility.
|
10.8 Connections for external conductors |
Is the panel builder's responsibility.
|
10.9.2 Power-frequency electric strength |
Is the panel builder's responsibility.
|
10.9.3 Impulse withstand voltage |
Is the panel builder's responsibility.
|
10.9.4 Testing of enclosures made of insulating material |
Is the panel builder's responsibility.
|
10.10 Temperature rise |
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
|
10.11 Short-circuit rating |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
10.12 Electromagnetic compatibility |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
10.13 Mechanical function |
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
|