Eaton xComfort KLV LV systems Final Distribution Boards. Hollow wall compact distribution board, 2-rows, flush sheet steel door, 24HWS-F
| Product Name | 
                                                Eaton xComfort KLV energy distribution board
                                             | 
| Catalog Number | 
                                                178824
                                             | 
| EAN | 
                                                4015081741533
                                             | 
| Product Length/Depth | 
                                                100 mm
                                             | 
| Product Height | 
                                                465 mm
                                             | 
| Product Width | 
                                                360 mm
                                             | 
| Product Weight | 
                                                3.41 kg
                                             | 
| Compliances | 
                                                RoHS conform
                                             | 
| Certifications | 
                                                IEC/EN 62208  IEC/EN 60670-24 (PD) | 
| Model Code | 
                                                KLV-24HWS-F
                                             | 
| Type | 
 | 
| Application | 
                                                Indoor (installation site)
                                             | 
| Color | 
                                                White  Traffic white (RAL 9016) | 
| Frequency rating of contacts | 
                                                50 Hz
                                             | 
| Closure type | 
                                                Other
                                             | 
| Enclosure material | 
                                                Plastic
                                             | 
| Width in number of modular spacings | 
                                                12
                                             | 
| Mounting method | 
                                                DIN-rail  Hollow-wall mounting Hollow wall | 
| Material | 
                                                Sheet steel, powder-coated  Polystyren (plastic) | 
| Number of module space units per row | 
                                                12
                                             | 
| Number of rows | 
                                                2
                                             | 
| Terminal type | 
                                                Screw terminals
                                             | 
| PE and N terminal number and cross section | 
                                                N - Fi: 4x (0.75 mm² - 16 mm²)  PE: 13 x (0.75 mm² - 16 mm²) N: 16 x (0.75 mm² - 16 mm²) | 
| Built-in depth | 
                                                88 mm
                                             | 
| Internal depth | 
                                                75 mm
                                             | 
| Cover/door color | 
                                                White
                                             | 
| Cover/door model | 
                                                With notch
                                             | 
| Cover/door type | 
                                                Door  Single | 
| Module rack type | 
                                                Rail frame
                                             | 
| Protective shrouding material | 
                                                Plastic
                                             | 
| Heat diss. ambient 35°C delta T:20°C flush mount individ. encl. top(IEC 60890) | 
                                                16 W
                                             | 
| Ambient operating temperature details | 
                                                -5 °C - 40 °C
                                             | 
| 10.2.2 Corrosion resistance | 
                                                Meets the product standard's requirements.
                                             | 
| 10.2.3.1 Verification of thermal stability of enclosures | 
                                                Meets the product standard's requirements.
                                             | 
| 10.2.3.2 Verification of resistance of insulating materials to normal heat | 
                                                Meets the product standard's requirements.
                                             | 
| 10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects | 
                                                850 °C; meets the product standard's requirements.
                                             | 
| 10.2.4 Resistance to ultra-violet (UV) radiation | 
                                                Not relevant to indoor installations.
                                             | 
| 10.2.5 Lifting | 
                                                Does not apply to enclosures without lifting aids.
                                             | 
| 10.2.6 Mechanical impact | 
                                                IK05
                                             | 
| 10.2.7 Inscriptions | 
                                                Meets the product standard's requirements.
                                             | 
| 10.3 Degree of protection of assemblies | 
                                                IP30
                                             | 
| 10.4 Clearances and creepage distances | 
                                                Is the panel builder's responsibility.
                                             | 
| 10.5 Protection against electric shock | 
                                                Protection class 2, therefore not applicable.
                                             | 
| 10.6 Incorporation of switching devices and components | 
                                                Is the panel builder's responsibility.
                                             | 
| 10.7 Internal electrical circuits and connections | 
                                                Is the panel builder's responsibility.
                                             | 
| 10.8 Connections for external conductors | 
                                                Is the panel builder's responsibility.
                                             | 
| 10.9.2 Power-frequency electric strength | 
                                                Ui = 400 V AC
                                             | 
| 10.9.3 Impulse withstand voltage | 
                                                4 kV
                                             | 
| 10.9.4 Testing of enclosures made of insulating material | 
                                                Meets the product standard's requirements.
                                             | 
| 10.10 Temperature rise | 
                                                The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
                                             | 
| 10.11 Short-circuit rating | 
                                                Is the panel builder's responsibility.
                                             | 
| 10.12 Electromagnetic compatibility | 
                                                Is the panel builder's responsibility.
                                             | 
| 10.13 Mechanical function | 
                                                Meets the product standard's requirements.
                                             | 
| Features | 
                                                EMC-version
                                             | 
| Fitted with: | 
                                                Neutral and protective conductor terminals with SK screw terminal technology  Hollow-wall anchor Cable retainer Wall trough Device support rails Door/Frame Front cover Imprintable sheet 3D adjustment element for mounting designed to adjust the mounting depth by up to 18 mm Spirit level for leveling Installation instructions | 
| Functions | 
                                                Extension possible  Basic device Sealable | 
| Protection class | 
                                                II (totally insulated)
                                             | 
| RAL-number | 
                                                9016
                                             | 
| Special features | 
 | 
| Used with | 
                                                Basic device  Installation distribution board KLV energy |