Photo is representative
Download
Eaton Moeller series xPole - AFDD+ Arc Fault Detection Device, 2 poles, B32A, 30mA, type A
Product Name |
Eaton Moeller series xPole - AFDD+ Arc fault detection device
|
Catalog Number |
187231
|
EAN |
4015081822805
|
Product Length/Depth |
80 mm
|
Product Height |
73 mm
|
Product Width |
52.5 mm
|
Product Weight |
0.277 kg
|
Compliances |
CE Marked
RoHS conform |
Certifications |
CE
|
Model Code |
AFDD-32/2/B/003-A
|
Application |
Switchgear for residential and commercial applications
|
Product range |
AFDD
|
Basic function |
Arc fault circuit interrupter
|
Product application |
Switchgear for residential and commercial applications
|
Number of poles |
Two-pole
|
Number of poles (protected) |
2
|
Number of poles (total) |
2
|
Release characteristic |
B
|
Tripping characteristic |
B
|
Rated current |
32 A
|
Rated current of product range |
10-40 Ampere
|
Fault current rating |
0.03 A
|
Sensitivity type |
Pulse-current sensitive
Type A |
Type |
AFDD+
|
Voltage rating |
230 V
|
Rated impulse withstand voltage (Uimp) |
4
|
Current test marks |
As per inscription
|
Impulse withstand current |
Partly surge-proof, 250 A
|
Frequency |
50 Hz
|
Leakage current type |
A
|
Rated switching capacity (IEC/EN 61009) |
6 kA
|
Rated short-circuit breaking capacity |
6 Kilo Ampere
|
Rated short-circuit breaking capacity (EN 60947-2) |
0 kA
|
Rated short-circuit breaking capacity (EN 61009) |
6 kA
|
Rated short-circuit breaking capacity (EN 61009-1) |
6 kA
|
Test circuit AC |
170 - 264 Voltage AC
|
Tripping |
Non-delayed
|
Control voltage type auxiliary equipment |
AC
|
Rated voltage auxiliary device |
230 V
|
Rated switch current auxiliary device |
0 A
|
Overvoltage category |
III
|
Pollution degree |
2
|
Lifespan, electrical |
4000 operations
|
Frame |
45 mm
|
Width In Number Of Modular Spacings |
3
|
Built-in width |
54 mm
|
Device height |
80 mm
|
Built-in depth |
67 mm
|
Mounting style |
Tri-stable slide catch - enables removal from existing busbar combination
|
Degree of protection |
IP20
|
Degree of protection (built in) |
IP40
|
Terminals (top and bottom) |
Twin-purpose
|
Terminal protection |
Busbar tag shroud as per VBG4, ÖVE-EN 6
|
Permissible Storage and Trans Temp. Min |
-35 °C
|
Permissible Storage and Trans Temp. Max |
60 °C
|
Contact position indicator |
red / green
|
Thickness of busbar material |
0.8 - 2 Square Millimeter
|
Climatic proofing |
IEC/EN 61009
|
Lifespan, mechanical |
20000 operations
|
Rated operational current for specified heat dissipation (In) |
32 A
|
Equipment heat dissipation, current-dependent |
9 W
|
Ambient operating temperature - min |
-25 °C
|
Ambient operating temperature - max |
40 °C
|
10.2.2 Corrosion resistance |
Meets the product standard's requirements.
|
10.2.3.1 Verification of thermal stability of enclosures |
Meets the product standard's requirements.
|
10.2.3.2 Verification of resistance of insulating materials to normal heat |
Meets the product standard's requirements.
|
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects |
Meets the product standard's requirements.
|
10.2.4 Resistance to ultra-violet (UV) radiation |
Meets the product standard's requirements.
|
10.2.5 Lifting |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.2.6 Mechanical impact |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.2.7 Inscriptions |
Meets the product standard's requirements.
|
10.3 Degree of protection of assemblies |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.4 Clearances and creepage distances |
Meets the product standard's requirements.
|
10.5 Protection against electric shock |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.6 Incorporation of switching devices and components |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.7 Internal electrical circuits and connections |
Is the panel builder's responsibility.
|
10.8 Connections for external conductors |
Is the panel builder's responsibility.
|
10.9.2 Power-frequency electric strength |
Is the panel builder's responsibility.
|
10.9.3 Impulse withstand voltage |
Is the panel builder's responsibility.
|
10.9.4 Testing of enclosures made of insulating material |
Is the panel builder's responsibility.
|
10.10 Temperature rise |
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
|
10.11 Short-circuit rating |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
10.12 Electromagnetic compatibility |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
10.13 Mechanical function |
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
|
Current limiting class |
3
|
Additional equipment attached at delivery |
Fire protection switch
|
Types conform to |
IEC/EN 61009
IEC/EN 62606 |