Eaton Moeller® series DILEM Contactor, 230 V 50 Hz, 240 V 60 Hz, 4 pole, 380 V 400 V, 4 kW, Screw terminals, AC operation
| Product Name |
Eaton Moeller® series DILEM Mini contactor
|
| Catalog Number |
051804
|
| EAN |
4015080518044
|
| Product Length/Depth |
52 mm
|
| Product Height |
58 mm
|
| Product Width |
45 mm
|
| Product Weight |
0.17 kg
|
| Certifications |
UL Category Control No.: NLDX
IEC/EN 60947 UL CSA File No.: 012528 CSA Class No.: 3211-04 IEC/EN 60947-4-1 UL File No.: E29096 VDE 0660 CE UL 508 CSA-C22.2 No. 14-05 CSA |
| Catalog Notes |
Also tested according to AC-3e.
|
| Model Code |
DILEM4(230V50HZ,240V60HZ)
|
| Features |
Positive operating contacts to EN 60947-5-1 appendix L, including auxiliary contact module
|
| Number of poles |
Four-pole
|
| Application |
Mini Contactors for Motors and Resistive Loads
|
| Degree of protection |
IP20
|
| Lifespan, mechanical |
150,000 Operations (at 240 V, DC, L/R = 50 ms: 2 contacts in series 0.5 A)
7,000,000 Operations (Coil 50/60 Hz) 20,000,000 Operations 200,000 Operations (at 240 V, AC-15) |
| Operating frequency |
9000 mechanical Operations/h
|
| Overvoltage category |
III
|
| Pollution degree |
3
|
| Product category |
Contactors
|
| Rated impulse withstand voltage (Uimp) |
6000 V AC
|
| Utilization category |
AC-1: Non-inductive or slightly inductive loads, resistance furnaces
AC-4: Normal AC induction motors: starting, plugging, reversing, inching AC-3: Normal AC induction motors: starting, switch off during running |
| Utilization category |
AC-1: Non-inductive or slightly inductive loads, resistance furnaces
AC-4: Normal AC induction motors: starting, plugging, reversing, inching AC-3: Normal AC induction motors: starting, switch off during running |
| Ambient operating temperature - min |
-25 °C
|
| Ambient operating temperature - max |
50 °C
|
| Climatic proofing |
Damp heat, cyclic, to IEC 60068-2-30
Damp heat, constant, to IEC 60068-2-78 |
| Number of auxiliary contacts (normally closed contacts) |
0
|
| Number of auxiliary contacts (normally open contacts) |
0
|
| Rated operational current (Ie) |
2.5 A at 60 V, DC L/R ≤ 15 ms (with 2 contacts in series)
2.5 A at 24 V, DC L/R ≤ 15 ms (with 1 contact in series) 0.5 A at 220 V, DC L/R ≤ 15 ms (with 3 contacts in series) 1.5 A at 100 V, DC L/R ≤ 15 ms (with 3 contacts in series) |
| Rated operational current (Ie) at AC-3, 380 V, 400 V, 415 V |
9 A
|
| Rated operational power at AC-3, 380/400 V, 50 Hz |
4 kW
|
| Rated operational voltage (Ue) at AC - max |
690 V
|