Zoeken in de Kennisbank
Document downloaden () van 20

239158
Model Code: FAZ6-B16/3N

FAZ6-B16/3N. Miniature circuit breaker (MCB), 16 A, 3p+N, characteristic: B, 6 kA

General specifications

Product Name
Eaton Moeller series xEffect - FAZ6 MCB
Catalog Number
239158
EAN
4015082391584
Product Length/Depth
85 mm
Product Height
73 mm
Product Width
70.8 mm
Product Weight
0.456 kg
Compliances
RoHS conform
Model Code
FAZ6-B16/3N

Delivery program

Number of poles (total)
4
Number of poles (protected)
3
Release characteristic
B
Amperage Rating
16 A

Technical Data - Electrical

Voltage type
AC
Voltage rating (IEC/EN 60898-1)
415 V
Voltage rating (IEC/EN 60947-2)
400
Rated operational voltage (Ue) - max
400 V
Operational voltage (IEC/EN 60947-2) - max
400 V
Operational voltage at DC (EC/EN 60947-2) - max
60 V
Rated insulation voltage (Ui)
440 V
Rated impulse withstand voltage (Uimp)
4 kV
Frequency rating - min
50 Hz
Frequency rating - max
60 Hz
Rated switching capacity (IEC/EN 60947-2)
7.5 kA
Overvoltage category
III
Pollution degree
2

Technical Data - Mechanical

Width in number of modular spacings
4
Built-in depth
70.5 mm
Connectable conductor cross section (solid-core) - min
1 mm²
Connectable conductor cross section (solid-core) - max
25 mm²
Connectable conductor cross section (multi-wired) - min
1 mm²
Connectable conductor cross section (multi-wired) - max
25 mm²

Design verification as per IEC/EN 61439 - technical data

Rated operational current for specified heat dissipation (In)
16 A
Equipment heat dissipation, current-dependent
7.2 W
Ambient operating temperature - min
-25 °C
Ambient operating temperature - max
75 °C

Design verification as per IEC/EN 61439

10.2.2 Corrosion resistance
Meets the product standard's requirements.
10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard's requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard's requirements.
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects
Meets the product standard's requirements.
10.2.4 Resistance to ultra-violet (UV) radiation
Meets the product standard's requirements.
10.2.5 Lifting
Does not apply, since the entire switchgear needs to be evaluated.
10.2.6 Mechanical impact
Does not apply, since the entire switchgear needs to be evaluated.
10.2.7 Inscriptions
Meets the product standard's requirements.
10.3 Degree of protection of assemblies
Does not apply, since the entire switchgear needs to be evaluated.
10.4 Clearances and creepage distances
Meets the product standard's requirements.
10.5 Protection against electric shock
Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and components
Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections
Is the panel builder's responsibility.
10.8 Connections for external conductors
Is the panel builder's responsibility.
10.9.2 Power-frequency electric strength
Is the panel builder's responsibility.
10.9.3 Impulse withstand voltage
Is the panel builder's responsibility.
10.9.4 Testing of enclosures made of insulating material
Is the panel builder's responsibility.
10.10 Temperature rise
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.12 Electromagnetic compatibility
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.13 Mechanical function
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.

Additional information

Current limiting class
3
Features
Concurrently switching N-neutral
Additional equipment possible

Productspecificatie exporteren

Serial Number Verified :
Authenticated:
The product is verified as being authentic; however, this does not guarantee the condition or fit for purpose of the product.

Product authenticeren

Voer uw 16- of 17-cijferige serienummer in
Het serienummer dat u invoert, mag geen speciale tekens bevatten. Het serienummer dat u heet ingevoerd is niet correct; het moet een getal van 16 of 17 cijfers zijn. Het door u ingevoerde serienummer is niet gevonden. Probeer opnieuw of Dit probleem melden voor verdere hulp. Het door u ingevoerde serienummer komt niet overeen met het product. Controleer het serienummer van uw product en probeer het opnieuw. Klik hier om naar de productpagina te navigeren voor het serienummer dat u heeft ingevoerd Het serienummer is bij Eaton bekend als verdacht, probeer het opnieuw of Dit probleem melden voor verdere hulp.
Serienummer
Reset Het serienummer is bij Eaton bekend als verdacht, probeer het opnieuw of Dit probleem melden voor verdere hulp. Het serienummer wordt niet door Eaton herkend en is ongeldig. Gebruik dit formulier Dit probleem melden voor verdere hulp.
Voer de 6-cijferige authenticatiecode in
Het product dat u heeft ingevoerd is verdacht! Probeer opnieuw of Dit probleem melden voor verdere hulp. De authenticatiecode die u invoert, komt niet overeen met onze gegevens voor dit serienummer. Probeer opnieuw, of Dit probleem melden voor verdere hulp. Ongeldige authenticatiecode. De lengte moet 6 tekens zijn Dit probleem melden voor verdere hulp. Authenticatiecode is vereist Dit probleem melden voor verdere hulp.
Voltooi de CAPTCHA-uitdaging voordat u zich kunt aanmelden.