Eaton xEnergy Basic LV systems Low voltage switchgear. Surface-mount service distribution board, 3-point turn-lock, DIN rails, front plate with 45-mm cutout, W = 800 mm, H = 1560
Product Name |
Eaton xEnergy Basic small distribution board
|
Catalog Number |
293314
|
EAN |
4015082933142
|
Product Length/Depth |
262 mm
|
Product Height |
1560 mm
|
Product Width |
800 mm
|
Product Weight |
47.5 kg
|
Compliances |
RoHS conform
|
Model Code |
BP-O-800/15-C
|
Type |
Basic device
|
Application |
Indoor (installation site)
|
Color |
Gray
Light gray (RAL 7035) |
Closure type |
Other
|
Surface finishing |
With powder coating
|
Enclosure material |
Steel
|
Width in number of modular spacings |
35
|
Mounting method |
DIN-rail
Surface mounting Surface mounted (plaster) |
Material |
Sheet steel
|
Number of rows |
9
|
Built-in depth |
280 mm
|
Built-in height |
1575 mm
|
Built-in width |
815 mm
|
Cover/door model |
Closed
|
Cover/door type |
Three-point turn-lock
Door Single |
Heat diss. ambient 35°C delta T: 20°C wall mount middle encl. top (IEC 60890) |
128 W
|
Heat diss. ambient 35°C delta T: 35°C wall mount middle encl. top (IEC 60890) |
256 W
|
Heat diss. ambient 35°C delta T:20°C wall mount individ. encl. top (IEC 60890) |
139 W
|
Heat diss. ambient 35°C delta T:20°C wall mount starting encl. top (IEC 60890) |
132 W
|
Heat diss. ambient 35°C delta T:35°C wall mount individ. encl. top (IEC 60890) |
278 W
|
Heat diss. ambient 35°C delta T:35°C wall mount starting encl. top (IEC 60890) |
265 W
|
10.2.2 Corrosion resistance |
Meets the product standard's requirements.
|
10.2.3.1 Verification of thermal stability of enclosures |
Meets the product standard's requirements.
|
10.2.3.2 Verification of resistance of insulating materials to normal heat |
Meets the product standard's requirements.
|
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects |
Meets the product standard's requirements.
|
10.2.4 Resistance to ultra-violet (UV) radiation |
Not relevant to indoor installations.
|
10.2.5 Lifting |
Does not apply to enclosures without lifting aids.
|
10.2.6 Mechanical impact |
IK07
|
10.2.7 Inscriptions |
Meets the product standard's requirements.
|
10.3 Degree of protection of assemblies |
IP30
|
10.4 Clearances and creepage distances |
Is the panel builder's responsibility.
|
10.5 Protection against electric shock |
< 0.1 Ω; meets the product standard's requirements.
|
10.6 Incorporation of switching devices and components |
Is the panel builder's responsibility.
|
10.7 Internal electrical circuits and connections |
Is the panel builder's responsibility.
|
10.8 Connections for external conductors |
Is the panel builder's responsibility.
|
10.9.2 Power-frequency electric strength |
Ui = 440 V AC
|
10.9.3 Impulse withstand voltage |
4 kV
|
10.9.4 Testing of enclosures made of insulating material |
Does not apply to metal enclosures.
|
10.10 Temperature rise |
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
|
10.11 Short-circuit rating |
Is the panel builder's responsibility.
|
10.12 Electromagnetic compatibility |
Is the panel builder's responsibility.
|
10.13 Mechanical function |
Meets the product standard's requirements.
|
Features |
EMC-version
|
Functions |
Basic device
Extension possible Sealable |
RAL-number |
7035
|
Special features |
With DIN-rail
Frontplate with 45mm cut-out
|