Eaton 93PM UPS, 60 kW (60 kW Frame), Input switch included, Battery breaker included, 5 strings of 9 Ah long life batteries, Network card included
| Product Name |
Eaton 93PM UPS
|
| Catalog Number |
AA06AG206A03002000
|
| EAN |
6430070720623
|
| Product Length/Depth |
91.4 cm
|
| Product Height |
187.6 cm
|
| Product Width |
56 cm
|
| Product Weight |
773 kg
|
| Compliances |
CE Marked
RoHS Compliant CB |
| Certifications |
IEC/EN 62040-2
IEC/EN 62040-1 EN 62040-3 Manufactured in a plant certified to ISO 9001 and ISO 14001 management system standards |
| Model Code |
93PM-60(60)-IS-BB-5x9Ah-LL-6
|
| Audible alarms |
Yes
|
| Auto shutdown function |
Yes
|
| Battery charger type |
ABM technology
|
| External battery connection |
Hardwired
|
| Color |
Black
|
| Construction type |
Free standing model
|
| Efficiency (eco-mode) |
99 %
|
| Improved efficiency mode |
ESS with VMMS
|
| Feed type |
AC
|
| Form factor |
Modular
|
| Hot-swappable power modules |
No
|
| Input connection |
Fixed connection
|
| Input nominal voltage |
400V default (380/400/415V)
|
| Number of output connections fixed connection |
1
|
| Output frequency |
50 Hz (50/60 Hz programmable)
|
| Output power factor |
0.9
|
| Overall efficiency |
97 %
|
| Package contents |
|
| Parallelable |
Parallel for capacity and redundancy
|
| Phase (input) |
3
|
| Phase (output) |
3
|
| Potential free switch contact |
Yes
|
| Snmp |
Yes
|
| Topology |
Online
|
| Type Of Interface |
Other
|
| Internal maintenance bypass |
No
|
| kVA rating |
60 kVA
|
| Wattage |
54000 W
|
| Application |
Data center/ facility/IT
|
| Output effective power |
54 kW
|
| Transition time for full load |
0 s
|
| Efficiency (improved efficiency mode) |
99 %
|
| Voltage distortion output (linear load) - max |
1.5 %
|
| Integrated functionality |
Network Mangement
Modular |
| Input frequency - min |
50 Hz
|
| Input frequency - max |
60 Hz
|
| Input voltage - min |
380 V
|
| Input voltage - max |
415 V
|
| Output voltage - min |
380 V
|
| Output voltage - max |
415 V
|
| Secondary Frequency Min |
50 Hz
|
| Secondary Frequency Max |
60 Hz
|
| Output apparent power |
60000 VA
|
| Primary frequency - max |
60 Hz
|
| Primary frequency - min |
50 Hz
|
| Runtime at half load |
18 min
|
| Runtime at full load |
7 min
|
| Mounting Method |
Tower
|
| Degree of Protection |
IP20
|