Eaton EC4P Compact PLC, 24 V DC, 12DI(of 4AI), 6DO(R), 1AO, ethernet, CAN
Product Name |
Eaton EC4P Compact PLC
|
Catalog Number |
106406
|
EAN |
4015081061761
|
Product Length/Depth |
72 mm
|
Product Height |
90 mm
|
Product Width |
107.5 mm
|
Product Weight |
0.358 kg
|
Certifications |
UL508
UL CSA-C22.2 No. 142-M CSA CSA File No.: 012528 CSA-C22.2 No. 0-M UL File No.: E135462 CSA Class No.: 2252-01 IEC/EN 61000-4-2, Level 3 UL Category Control No.: NRAQ CE |
Catalog Notes |
Expandable: Inputs/outputs and bus systems
|
Features |
190 received bytes in a block (PRG interface RS232, Master mode)
Overload and short-circuit protection Asynchronous, cyclic, acyclic PDO types (operating modes of the slave) |
Air discharge |
8 kV
|
10.10 Temperature rise |
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
|
10.11 Short-circuit rating |
Is the panel builder's responsibility.
|
10.12 Electromagnetic compatibility |
Is the panel builder's responsibility.
|
10.13 Mechanical function |
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
|
10.2.2 Corrosion resistance |
Meets the product standard's requirements.
|
10.2.3.1 Verification of thermal stability of enclosures |
Meets the product standard's requirements.
|
10.2.3.2 Verification of resistance of insulating materials to normal heat |
Meets the product standard's requirements.
|
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects |
Meets the product standard's requirements.
|
10.2.4 Resistance to ultra-violet (UV) radiation |
Meets the product standard's requirements.
|
10.2.5 Lifting |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.2.6 Mechanical impact |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.2.7 Inscriptions |
Meets the product standard's requirements.
|
10.3 Degree of protection of assemblies |
Meets the product standard's requirements.
|
10.4 Clearances and creepage distances |
Meets the product standard's requirements.
|
10.5 Protection against electric shock |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.6 Incorporation of switching devices and components |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.7 Internal electrical circuits and connections |
Is the panel builder's responsibility.
|
10.8 Connections for external conductors |
Is the panel builder's responsibility.
|
10.9.2 Power-frequency electric strength |
Is the panel builder's responsibility.
|
10.9.3 Impulse withstand voltage |
Is the panel builder's responsibility.
|
10.9.4 Testing of enclosures made of insulating material |
Is the panel builder's responsibility.
|
Fitted with: |
Power supply
Function module Other components Ethernet on board easyNet/CANopen® on board Digital input module Engineering software Memory unit Analog input module Analog output module Digital output module Documentation Basic device Communication module Libraries |
Pollution degree |
2
|
Accuracy |
± 3 %, of actual value, two devices (Analog Inputs)
± 5 s/day (± 0.5 h⁄year), Real-time clock, normally ± 2, (I7, I8, I11, I12) ± 0.12 V, of actual value, within a single device (Analog Inputs) 2 %, Analog outputs at-25 °C - 55 °C 1 %, Analog outputs at 25 °C |
Burst impulse |
2 kV, Supply cable
According to IEC/EN 61000-4-4, level 3 2 kV, Signal cable |
Rated impulse withstand voltage (Uimp) |
6 kV (contact-coil)
|
Utilization category |
R 300 Light Pilot Duty, UL/CSA Control Circuit Rating Codes DC
B 300 Light Pilot Duty, UL/CSA Control Circuit Rating Codes AC |
Air pressure |
1080 hPa (operation)
|
Bus termination |
EASY-NT-R plug (incl. bus terminating resistor 120 Ω),first and last station, CANopen®
|
Environmental conditions |
Clearance in air and creepage distances according to EN 50178, UL 508, CSA C22.2, No. 142
Condensation: prevent with appropriate measures |
Indication |
LCD-display used as status indication of Digital inputs 24 V DC
|
Input |
Voltage (DC)
|
Cable length |
100 m, unshielded, Digital inputs 24 V DC
30 m, screened, Analog inputs |
Mounting method |
Screw fixing using fixing brackets ZB4-101-GF1 (accessories)
Top-hat rail fixing (according to IEC/EN 60715, 35 mm) |
Number of outputs |
Relay outputs in groups of 1
8 Transistor Outputs 6 (relay outputs) |
Character formats |
8E1, 8O1, 8N1, 8N2, 7E2, 7O2, 7N2, 7E1, PRG interface RS232, Master mode
|
Screwdriver size |
3.5 x 0.8 mm, Terminal screw
|
Mounting position |
Vertical
Horizontal |
Output |
Voltage (DC)
|
Contact discharge |
6 kV, Electrostatic discharge (ESD)
|
Overvoltage category |
II
|
Connection type |
RJ45, Ethernet
2 x RJ45, 8 pole, CANopen® RJ45, PRG Interface RS232 |
Constant acceleration |
2 g, 57 - 150 Hz, according to IEC/EN 60068-2-6, Vibrations
|
Constant amplitude |
0,15 mm, 10 - 57 Hz, according to IEC/EN 60068-2-6, Vibrations
|
Surge rating |
2 kV, Supply cables, symmetrical, EASY...AC, power pulses (Surge), EMC
0.5 kV, Supply cables, symmetrical, EASY…DC, power pulses (Surge), EMC According to IEC/EN 61000-4-5, power pulses (Surge), EMC |
Terminal capacity (flexible with ferrule AWG) |
22 - 12
|
Conversions |
Each CPU cycle, Analog outputs
Each CPU cycle, Analog inputs |
Electromagnetic fields |
10 V/m (according to IEC EN 61000-4-3)
|
Terminal capacity (solid AWG) |
22 - 12
|
Number of inputs (analog) |
4 (I7, I8, I11, I12)
|
Load resistance |
1 kΩ
|
Cycle time |
< 0.3 ms, for 1 k of instructions (Bit, Byte), CPU
|
Number of modules |
Max. 126 (slaves)
|
Drop and topple |
50 mm Drop height, Drop to IEC/EN 60068-2-31
|
Immunity to line-conducted interference |
10 V (according to IEC/EN 61000-4-6)
|
Radio interference class |
Class B (EN 55022)
Class B (EN 55011) |
Data transfer rate |
0.6 kBit/s, PRG interface RS232, Master mode
500 kBit/s at 25 m, CANopen® 0.3 kBit/s, PRG interface RS232, Master mode 250 kBit/s at 60 m, CANopen® 125 kBit/s at 125 m, CANopen® 2.4 kBit/s, PRG interface RS232, Master mode 10 kBit/s at 1000 m , CANopen® 10 MBit/s, 100 m, Ethernet 19.2 kBit/s, PRG interface RS232, Master mode 38.4 kBit/s, PRG interface RS232, Master mode 57.6 kBit/s, PRG interface RS232, Master mode 4.8 kBit/s, PRG interface RS232, Master mode 20 kBit/s at 700 m, CANopen® 1.2 kBit/s, PRG interface RS232, Master mode 50 kBit/s at 300 m, CANopen® 9.6 kBit/s, PRG interface RS232, Master mode |
Relative humidity |
5 - 95 % (non-condensing)
|
Degree of protection |
IP20
|
Safe isolation |
300 V AC, Between two contacts, According to EN 50178
300 V AC, Between coil and contact, According to EN 50178 |
Delay time |
0.25 ms typ., Digital inputs 24 DC (I5 - I12), Delay time from 0 to 1
0.02 ms typ., Digital inputs 24 DC (I1 - I4), Delay time from 0 to 1 |
Residual ripple |
≤ 5 %
|
Rapid counter inputs |
2 (I1, I2) at 16 Bit or 1 (I1) at 32 Bit
50 kHz, Counter frequency 16/32 Bit (value range) ≤ 20 m (cable length, screened) Square (pulse shape) |
Recovery time |
100 µs
|
Insulation resistance |
According to EN 50178
|
Functions |
Building blocks
|
Heat dissipation |
3.4 W
|
Supply voltage at DC - max |
24 VDC
|
Resolution |
|
Incremental counter |
Pulse shape: Square
Signal offset: 90° Counter inputs: I1, I2 Value range: 32 Bit Number of counter inputs: 1 (I1, I2, I3, I4) Counter frequency: ≤ 40 kHz Input for reference switch: I4 Reference input: I3 |
Station |
To DS 301 V4, Control contact rated current, Mode slave, Interfaces
|
Input current |
3.3 mA (I9 - I10, at 24 V DC, at signal 1)
140 mA 3.3 mA (I1 - I6, at 24 V DC, at signal 1) 2.2 mA (I11 - I12, at 24 V DC, at signal 1) 2.2 mA (I7 - I8, at 24 V DC, at signal 1) 1 mA (Analog inputs) |
Input impedance |
11.2 kΩ
|
Input voltage |
Signal 0: < 8 V DC (I7 - I8, I11 - I12, Digital inputs, 24 V DC)
Signal 0: < 5 V DC (I1 - I6, I9 - I10, Digital inputs, 24 V DC) Signal 1: > 8 V DC (I7 - I8, I11 - I12, Digital inputs, 24 V DC) Signal 1: > 15 V DC (I1 - I6, I9 - I10, Digital inputs, 24 V DC) |
Processor |
Infineon XC161
|
Shock resistance |
15 g, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 11 ms, 18 Impacts
|
Inscription |
Individual inscription possible with EC4-COMBINATION-*
|
Rated breaking capacity |
300000 Operations at AC-15, 250 V AC, 3 A (600 Ops./h)
200000 Operations at DC-13, 24 V DC, 1 A (500 Ops./h) |
Lifespan, electrical |
25,000 Operations (Filament bulb load at 1000 W, 230/240 V AC)
25,000 Operations (Fluorescent lamp load 1 x 58 W at 230/240 V AC, conventional, compensated) 25,000 Operations (Filament bulb load at 500 W, 115/120 V AC) 25,000 Operations (Fluorescent lamp load 10 x 58 W at 230/240 V AC, with upstream electrical device) 25,000 Operations (Fluorescent lamp load 10 x 58 W at 230/240 V AC, uncompensated) |
Signal range |
0 - 10 V DC, Analog inputs
|
Lifespan, mechanical |
10,000,000 Operations
10,000,000 Operations (Relay outputs) |
Making/breaking capacity |
3600/360 VA (AC, at B 300)
28/28 VA (DC, at R 300) |
Memory |
256 kByte Program memory code
8 kByte Retain Memory 14 segments of 16 kByte Program memory data 4 kByte Output Memory 16 kByte Marker Memory 4 kByte Input Memory |
Number of bytes |
190 transmission bytes (in a block)
|
Number of inputs (digital) |
4 (I7, I8, I11, I12, can also be used as analog inputs)
12 (24 V DC) 12 4 (can also be used as analog inputs) |
Parallel switching |
Not permitted
|
Voltage dips |
According to EN 61131-2
≤ 10 ms |
Uninterrupted current |
5 A AC, max. thermal continuous current cos ϕ = 1 at B 300 (UL/CSA)
10 A AC, at 240 V AC (UL/CSA) 8 A DC, at 24 V DC (UL/CSA) 1 A DC, at R 300 (UL/CSA) |
Potential isolation |
Between Relay outputs and Power supply: yes
Basic isolation: 600 V AC (Relay outputs) Between Relay outputs and Inputs: yes Between Analog inputs and Interface/memory card: no Safe isolation according to EN 50178: 300 V AC (Relay outputs) Between Digital inputs 24 V DC and Outputs: yes In groups (Relay outputs) Between Digital inputs 24 V DC and network easyNet, easyLink Between Analog inputs and Outputs: yes |
Protection of an output relay |
Miniature circuit-breaker B16 or fuse 8 A (slow)
|
Rated operational voltage |
24 V DC (-15 %/+ 20 % - power supply)
20.4 - 28.8 V DC |
Relay output |
> 500 mA (Recommended for load: 12 V AC/DC)
|
Short-circuit protection |
16 A, Short-circuit-proof cos ϕ = 0.5 to 0.7, characteristic B16 at 900 A, Contacts, Relay outputs
16 A, Short-circuit-proof cos ϕ = 1, characteristic B16 at 600 A, Contacts, Relay outputs |
Terminal capacity (flexible with ferrule) |
0.2/2.5 mm²
|
Switching frequency |
0.5 Hz, Inductive load, Relay outputs
10 Hz, Relay outputs 2 Hz, Resistive load/lamp load, Relay outputs |
Terminal capacity (solid) |
0.2/4 mm²
|
Tightening torque |
0.6 Nm
|
Write cycles of the retentive memory |
10,000,000,000 read-write cycles
|
Ambient operating temperature - max |
55 °C
|
Ambient operating temperature - min |
-25 °C
|
Ambient storage temperature - max |
70 °C
|
Ambient storage temperature - min |
-40 °C
|
Conventional thermal current Ith of auxiliary contacts (1-pole, open) |
8 A
|
Display temperature - max |
55 °C
|
Display temperature - min |
0 °C
|
Equipment heat dissipation, current-dependent Pvid |
0 W
|
Heat dissipation capacity Pdiss |
0 W
|
Heat dissipation per pole, current-dependent Pvid |
0 W
|
Height of fall (IEC/EN 60068-2-32) - max |
1 m
|
Number of outputs (analog) |
1
|
Output current (mA) - max |
100 mA
|
Rated insulation voltage (Ui) |
250 V
|
Rated operational current for specified heat dissipation (In) |
0 A
|
Rated operational voltage (Ue) at AC - max |
300 V
|
Rated operational voltage (Ue) at DC - max |
300 V
|
Static heat dissipation, non-current-dependent Pvs |
3.4 W
|