Descargar documento () de 20

110313
Código del modelo: N2-250-BT

Eaton Moeller series NZM - Molded Case Circuit Breaker. Switch-disconnector 3p 250A terminals

Especificaciones generales

Product Name
Eaton Moeller series NZM switch-disconnector
Catalog Number
110313
EAN
4015081098613
Product Length/Depth
149 mm
Product Height
184 mm
Product Width
105 mm
Product Weight
2.081 kg
Compliances
RoHS conform
Certifications
IEC/EN 60947
IEC
Model Code
N2-250-BT

Delivery program

Application
Use in unearthed supply systems at 690 V
Type
Switch-disconnector
Circuit breaker frame type
N2
Number of poles
Three-pole
Amperage Rating
250 A
Features
Version as emergency stop installation
Motor drive optional
Version as main switch
Version as maintenance-/service switch
Special features
  • Main switch characteristics including positive drive to IEC/EN 60204 and VDE 0113.
  • Isolating characteristics to IEC/EN 60947-3 and VDE 0660.
  • Busbar tag shroud to VDE 0160 Part 100.
  • Rated current = rated uninterrupted current: 250 A
  • The rated short-time withstand current for PN2/N2 in conjunction with earth-fault release NZM2-4-XFI...Icw = 1.5 kA

Technical Data - Electrical

Voltage rating
690 V - 690 V
Rated operating voltage (Ue) at AC - max
690 V
Rated insulation voltage (Ui)
690 V
Rated impulse withstand voltage (Uimp) at auxiliary contacts
6000 V
Rated impulse withstand voltage (Uimp) at main contacts
8000 V
Rated operational current
250 A (415 V AC-22/23A, making and breaking capacity)
250 A (690 V AC-22/23A, making and breaking capacity)
Rated conditional short-circuit current with back-up fuse
PN2(N2)-160…250: 250 AgGgL
80 kA at 690 V
100 kA at 400/415 V
Rated conditional short-circuit current with downstream fuse
100 kA at 400/415 V
80 kA at 690 V
PN2(N2)-160…250: 250 AgGgL
Rated short-time withstand current (t = 0.3 s)
3.5 kA
Rated short-time withstand current (t = 1 s)
3.5 kA
Amperage Rating
250 A
Rated operating frequency
50 Hz
Rated short-circuit making capacity Icm at 690 V, 50/60 Hz
5.5 kA
Rated operating power at AC-23, 400 V
132 kW
Short-circuit protective device fuses - max
250 A gL
Electrical connection type of main circuit
Frame clamp
Isolation
500 V AC (between auxiliary contacts and main contacts)
300 V AC (between the auxiliary contacts)
Number of operations per hour - max
120
Handle type
Rocker lever
Overvoltage category
III
Pollution degree
3
Lifespan, electrical
10000 operations at 415 V AC-1
7500 operations at 415 V AC-3
10000 operations at 400 V AC-1
7500 operations at 690 V AC-1
5000 operations at 690 V AC-3
7500 operations at 400 V AC-3
Direction of incoming supply
As required

Technical Data - Mechanical

Mounting Method
Intermediate mounting
Built-in device fixed built-in technique
Distribution board installation
Ground mounting
Fixed
Mounting Method
Intermediate mounting
Built-in device fixed built-in technique
Distribution board installation
Ground mounting
Fixed
Degree of protection
IP20 (basic protection type, in the area of the HMI devices)
Other
Degree of protection (IP), front side
IP66 (with door coupling rotary handle)
IP40 (with insulating surround)
IP20
Degree of protection (terminations)
IP10 (tunnel terminal)
IP00 (terminations, phase isolator and band terminal)
Protection against direct contact
Finger and back-of-hand proof to DIN EN 50274/VDE 0106 part 110
Shock resistance
20 g (half-sinusoidal shock 20 ms)
Number of auxiliary contacts (change-over contacts)
0
Number of auxiliary contacts (normally closed contacts)
0
Number of auxiliary contacts (normally open contacts)
0
Number of switches
1
Handle color
Black
Switch positions
I, +, 0
Climatic proofing
Damp heat, constant, to IEC 60068-2-78
Damp heat, cyclic, to IEC 60068-2-30
Special features
  • Main switch characteristics including positive drive to IEC/EN 60204 and VDE 0113.
  • Isolating characteristics to IEC/EN 60947-3 and VDE 0660.
  • Busbar tag shroud to VDE 0160 Part 100.
  • Rated current = rated uninterrupted current: 250 A
  • The rated short-time withstand current for PN2/N2 in conjunction with earth-fault release NZM2-4-XFI...Icw = 1.5 kA
Lifespan, mechanical
20000 operations

Technical Data - Mechanical - Terminals

Standard terminals
Box terminal
Optional terminals
Connection on rear. Screw terminal. Tunnel terminal
Terminal capacity (aluminum solid conductor/cable)
10 mm² - 16 mm² (1x) direct at switch rear-side connection
16 mm² (1x) at tunnel terminal
10 mm² - 16 mm² (2x) direct at switch rear-side connection
Terminal capacity (aluminum stranded conductor/cable)
25 mm² - 185 mm² (1x) at 1-hole tunnel terminal
Terminal capacity (copper busbar)
Min. 16 mm x 5 mm direct at switch rear-side connection
M8 at rear-side screw connection
Max. 24 mm x 8 mm direct at switch rear-side connection
Terminal capacity (copper solid conductor/cable)
6 mm² - 16 mm² (2x) at box terminal
6 mm² - 16 mm² (2x) direct at switch rear-side connection
10 mm² - 16 mm² (1x) at box terminal
16 mm² (1x) at tunnel terminal
10 mm² - 16 mm² (1x) direct at switch rear-side connection
Terminal capacity (copper stranded conductor/cable)
25 mm² - 185 mm² (1x) at 1-hole tunnel terminal
25 mm² - 185 mm² (1x) direct at switch rear-side connection
25 mm² - 185 mm² (1x) at box terminal
25 mm² - 70 mm² (2x) at box terminal
25 mm² - 70 mm² (2x) direct at switch rear-side connection
Terminal capacity (copper strip)
Max. 10 segments of 24 mm x 0.8 mm at rear-side connection (punched)
Max. 10 segments of 16 mm x 0.8 mm at box terminal
Min. 2 segments of 9 mm x 0.8 mm at box terminal
Min. 2 segements of 16 mm x 0.8 mm at rear-side connection (punched)
Max. 8 segments of 15.5 mm x 0.8 mm (2x) at box terminal

Design verification as per IEC/EN 61439 - technical data

Rated operational current for specified heat dissipation (In)
250 A
Equipment heat dissipation, current-dependent
48 W
Ambient operating temperature - min
-25 °C
Ambient operating temperature - max
70 °C
Ambient storage temperature - min
40 °C
Ambient storage temperature - max
70 °C

Design verification as per IEC/EN 61439

10.2.2 Corrosion resistance
Meets the product standard's requirements.
10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard's requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard's requirements.
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects
Meets the product standard's requirements.
10.2.4 Resistance to ultra-violet (UV) radiation
Meets the product standard's requirements.
10.2.5 Lifting
Does not apply, since the entire switchgear needs to be evaluated.
10.2.6 Mechanical impact
Does not apply, since the entire switchgear needs to be evaluated.
10.2.7 Inscriptions
Meets the product standard's requirements.
10.3 Degree of protection of assemblies
Does not apply, since the entire switchgear needs to be evaluated.
10.4 Clearances and creepage distances
Meets the product standard's requirements.
10.5 Protection against electric shock
Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and components
Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections
Is the panel builder's responsibility.
10.8 Connections for external conductors
Is the panel builder's responsibility.
10.9.2 Power-frequency electric strength
Is the panel builder's responsibility.
10.9.3 Impulse withstand voltage
Is the panel builder's responsibility.
10.9.4 Testing of enclosures made of insulating material
Is the panel builder's responsibility.
10.10 Temperature rise
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.12 Electromagnetic compatibility
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.13 Mechanical function
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.

Additional information

Functions
Disconnectors/main switches
Voltage release optional
Interlockable

Exportar especificaciones del producto

Serial Number Verified :
Authenticated:
The product is verified as being authentic; however, this does not guarantee the condition or fit for purpose of the product.

Autenticar producto

Introduzca su número de serie de 16-17 dígitos
El número de serie que ha introducido no debe contener caracteres especiales. El número de serie que ha introducido no es correcto, debe ser de 16 o 17 dígitos. No se ha encontrado el número de serie que ha introducido. Vuelva a intentarlo o informar de este problema para obtener más ayuda. El número de serie que ha introducido no coincide con el producto. Compruebe el número de serie de su producto e inténtelo de nuevo. Cliquear aquí. para navegar a la página del producto para el número de serie que ha introducido Eaton sabe que el número de serie es SOSPECHADO, inténtelo de nuevo o informar de este problema para obtener más ayuda.
Número de serie
Reiniciar Eaton sabe que el número de serie es SOSPECHADO, inténtelo de nuevo o informar de este problema para obtener más ayuda. Eaton no reconoce el número de serie y no es válido. Utilice este formulario para informar de este problema para obtener más ayuda.
Introduzca el código de autenticación de 6 dígitos
El producto que ha introducido es sospechado. Vuelva a intentarlo o informar de este problema para obtener más ayuda. El código de autenticación que introduzca no coincide con nuestros registros para este número de serie. Vuelva a intentarlo o informar de este problema para obtener más ayuda. Código de autenticación no válido. La longitud debe ser de 6 caracteres informar de este problema para obtener más ayuda. El código de autenticación es obligatorio informar de este problema para obtener más ayuda.
Complete el desafío Captcha antes de autenticar.
Contáctenos para informar de un problema
x
Informar de un problema
Por favor, introduzca sus apellidos.
x
Gracias, su problema ha sido enviado, nuestro equipo de productos se pondrá en contacto con usted pronto.
Nota: Si faltan archivo(s) en la descarga .zip, el ejecución de archivo no es compatible con la descarga masiva.