Eaton Moeller® series DILMT Power contactor, 3 pole, 380 V 400 V: 15 kW, 24 V 50/60 Hz, AC operation, Screw terminals
| Product Name |
Eaton Moeller® series DILMT Contactor
|
| Catalog Number |
197618
|
| EAN |
4015081944972
|
| Product Length/Depth |
97.5 mm
|
| Product Height |
82 mm
|
| Product Width |
36 mm
|
| Product Weight |
0.36 kg
|
| Certifications |
EN 60335-1
GB14048 IEC/EN 60947 |
| Catalog Notes |
Also tested according to AC-3e.
|
| Model Code |
DILMT32(24V50/60HZ)
|
| Number of poles |
Three-pole
|
| Application |
Contactors for Motors
|
| Connection |
Screw terminals
|
| Connection to SmartWire-DT |
No
|
| Degree of protection |
IP20
|
| Frame size |
FS2
|
| Lifespan, electrical |
1,000,000 Operations (at 400V, AC-3)
|
| Lifespan, mechanical |
10,000,000 Operations (AC operated)
|
| Operating frequency |
3600 mechanical Operations/h (AC operated)
|
| Overvoltage category |
III
|
| Pollution degree |
3
|
| Product category |
Contactors
|
| Rated impulse withstand voltage (Uimp) |
6000 V AC
|
| Suitable for |
Also motors with efficiency class IE3
|
| Used with |
DILT-XHI01(10)
|
| Utilization category |
AC-1: Non-inductive or slightly inductive loads, resistance furnaces
AC-3: Normal AC induction motors: starting, switch off during running AC-4: Normal AC induction motors: starting, plugging, reversing, inching |
| Voltage type |
AC
|
| Ambient operating temperature - min |
-25 °C
|
| Ambient operating temperature - max |
55 °C
|
| Ambient storage temperature - min |
-40 °C
|
| Ambient storage temperature - max |
80 °C
|
| Climatic proofing |
Damp heat, cyclic, to IEC 60068-2-30
Damp heat, constant, to IEC 60068-2-78 |
| Terminal capacity (solid) |
1 x (1 - 10) mm², Main cables
1 x (0.75 - 2.5) mm² 2 x (0.75 - 2.5) mm² |
| Terminal capacity (stranded) |
2 x (1 - 10) mm²
1 x (1 - 10) mm² |
| Stripping length (main cable) |
14 mm
|
| Screw size |
M3.5, Terminal screw
M5, Terminal screw |
| Screwdriver size |
2, Terminal screw, Pozidriv screwdriver
2, Terminal screw, Control circuit cables, Pozidriv screwdriver |
| Tightening torque |
2 Nm, Threaded ring
0.8 Nm, Screw terminals |
| Rated breaking capacity at 380/400 V |
256 A
|
| Rated insulation voltage (Ui) |
690 V
|
| Rated operational current (Ie) at AC-1, 380 V, 400 V, 415 V |
40 A
|
| Rated operational current (Ie) at AC-3, 220 V, 230 V, 240 V |
32 A
|
| Rated operational current (Ie) at AC-3, 380 V, 400 V, 415 V |
32 A
|
| Rated operational power at AC-3, 380/400 V, 50 Hz |
15 kW
|
| Rated operational voltage (Ue) at AC - max |
660 V
|
| Pick-up voltage |
0.85 - 1.1 V AC x Uc
|
| Power consumption, pick-up, 50 Hz |
0 VA, Dual-frequency coil in a cold state and 1.0 x Us
85 VA, Dual-frequency coil in a cold state and 1.0 x Us |
| Power consumption, pick-up, 60 Hz |
85 VA, Dual-frequency coil in a cold state and 1.0 x Us
0 VA, Dual-frequency coil in a cold state and 1.0 x Us |
| Power consumption, sealing, 50 Hz |
2.5 W, Dual-frequency coil in a cold state and 1.0 x Us
2.6 VA, Coil in a cold state and 1.0 x Us 0 W, Dual-frequency coil in a cold state and 1.0 x Us |
| Power consumption, sealing, 60 Hz |
0 W, Dual-frequency coil in a cold state and 1.0 x Us
0 VA, Dual-frequency coil in a cold state and 1.0 x Us, at 60 Hz 8.1 VA, Dual-frequency coil in a cold state and 1.0 x Us, at 60 Hz 2.5 W, Dual-frequency coil in a cold state and 1.0 x Us |
| Rated control supply voltage (Us) at AC, 50 Hz - min |
24 V
|
| Rated control supply voltage (Us) at AC, 50 Hz - max |
24 V
|
| Rated control supply voltage (Us) at AC, 60 Hz - min |
24 V
|
| Rated control supply voltage (Us) at AC, 60 Hz - max |
24 V
|
| Rated control supply voltage (Us) at DC - min |
0 V
|
| Rated control supply voltage (Us) at DC - max |
0 V
|
| Number of auxiliary contacts (normally closed contacts) |
0
|
| Number of auxiliary contacts (normally open contacts) |
0
|