Eaton DMM Switch-disconnector, DMM, 40 A, 4 pole, With black rotary handle and drive shaft, Vertical connection
| Product Name | 
                                                Eaton DMM Switch-disconnector
                                             | 
| Catalog Number | 
                                                1314057
                                             | 
| Model Code | 
                                                DMM-40/4
                                             | 
| EAN | 
                                                8711426325708
                                             | 
| Product Length/Depth | 
                                                146 mm
                                             | 
| Product Height | 
                                                74 mm
                                             | 
| Product Width | 
                                                84 mm
                                             | 
| Product Weight | 
                                                0.63 kg
                                             | 
| Certifications | 
                                                CE  IEC/EN 60947-3 EAC Lloyds RoHS IEC/EN 60947 VDE 0660 KEMA IEC/EN 60204 | 
| Features | 
                                                Version as main switch  Version as maintenance-/service switch | 
| Fitted with: | 
                                                Black rotary handle and drive shaft
                                             | 
| Locking facility | 
                                                Lockable in the 0 (Off) position
                                             | 
| Number of poles | 
                                                Four-pole
                                             | 
| Accessories | 
                                                Auxiliary contact fitted by user.
                                             | 
| Actuator color | 
                                                Black
                                             | 
| Actuator type | 
                                                Short thumb-grip
                                             | 
| Connection type | 
                                                Vertical
                                             | 
| Degree of protection | 
                                                NEMA Other
                                             | 
| Degree of protection (front side) | 
                                                IP20
                                             | 
| Lifespan, mechanical | 
                                                8,500 Operations
                                             | 
| Mounting method | 
                                                Surface mounting
                                             | 
| Mounting position | 
                                                As required
                                             | 
| Overvoltage category | 
                                                III
                                             | 
| Pollution degree | 
                                                3
                                             | 
| Product Category | 
 | 
| Rated impulse withstand voltage (Uimp) | 
                                                6000 V
                                             | 
| Safety parameter (EN ISO 13849-1) | 
                                                B10d values as per EN ISO 13849-1, table C.1
                                             | 
| Suitable for | 
                                                Distribution board installation  Ground mounting | 
| Ambient operating temperature - min | 
                                                -25 °C
                                             | 
| Ambient operating temperature - max | 
                                                55 °C
                                             | 
| Ambient storage temperature - min | 
                                                -30 °C
                                             | 
| Ambient storage temperature - max | 
                                                80 °C
                                             | 
| Stripping length (main cable) | 
                                                14 mm
                                             | 
| Rated breaking capacity at 400/415 V (cos phi to IEC 60947-3) | 
                                                320 A
                                             | 
| Rated breaking capacity at 500 V (cos phi to IEC 60947-3) | 
                                                264 A
                                             | 
| Rated breaking capacity at 660/690 V (cos phi to IEC 60947-3) | 
                                                200 A
                                             | 
| Rated insulation voltage (Ui) | 
                                                1000 V
                                             | 
| Rated operational current (Ie) at AC-21, 400 V, 415 V | 
                                                40 A
                                             | 
| Rated operational current (Ie) at AC-21, 500 V | 
                                                40 A
                                             | 
| Rated operational current (Ie) at AC-21, 690 V | 
                                                40 A
                                             | 
| Rated operational current (Ie) at AC-22, 380 V, 400 V, 415 V | 
                                                40 A
                                             | 
| Rated operational current (Ie) at AC-22, 500 V | 
                                                40 A
                                             | 
| Rated operational current (Ie) at AC-22, 690 V | 
                                                40 A
                                             | 
| Rated operational current (Ie) at AC-23A, 400 V, 415 V | 
                                                40 A
                                             | 
| Rated operational current (Ie) at AC-23A, 500 V | 
                                                33 A
                                             | 
| Rated operational current (Ie) at AC-23A, 690 V | 
                                                25 A
                                             | 
| Rated operational power at AC-23A, 400 V, 50 Hz | 
                                                22 kW
                                             | 
| Rated operational power at AC-23A, 500 V, 50 Hz | 
                                                22 kW
                                             | 
| Rated operational power at AC-23A, 690 V, 50 Hz | 
                                                22 kW
                                             | 
| Rated operational power at AC-3, 380/400 V, 50 Hz | 
                                                0 kW
                                             | 
| Rated operational voltage (Ue) at AC - max | 
                                                690 V
                                             | 
| Rated uninterrupted current (Iu) | 
                                                40 A
                                             | 
| Uninterrupted current | 
                                                Rated uninterrupted current Iu is specified for max. cross-section.
                                             | 
| Breaking current | 
                                                9.6 kA (at In = 50)  9.7 kA (at In = 80) | 
| Let-through energy | 
                                                Max. 10 kA²s (at In = 50)  Max. 44 kA²s (at In = 80) | 
| Rated conditional short-circuit current (Iq) | 
                                                100 kA  50 kA at In = 80 | 
| Rated short-time withstand current (Icw) | 
                                                1 kA  1 kA, Contacts, 1 second | 
| Short-circuit protection rating | 
                                                80/50, Fuse, Contacts
                                             | 
| Number of auxiliary contacts (change-over contacts) | 
                                                0
                                             | 
| Number of auxiliary contacts (normally closed contacts) | 
                                                0
                                             | 
| Number of auxiliary contacts (normally open contacts) | 
                                                0
                                             | 
| Equipment heat dissipation, current-dependent Pvid | 
                                                0.5 W
                                             | 
| Heat dissipation capacity Pdiss | 
                                                0 W
                                             | 
| Heat dissipation per pole, current-dependent Pvid | 
                                                4 W
                                             | 
| Rated operational current for specified heat dissipation (In) | 
                                                40 A
                                             | 
| Static heat dissipation, non-current-dependent Pvs | 
                                                0 W
                                             | 
| 10.2.2 Corrosion resistance | 
                                                Meets the product standard's requirements.
                                             | 
| 10.2.3.1 Verification of thermal stability of enclosures | 
                                                Meets the product standard's requirements.
                                             | 
| 10.2.3.2 Verification of resistance of insulating materials to normal heat | 
                                                Meets the product standard's requirements.
                                             | 
| 10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects | 
                                                Meets the product standard's requirements.
                                             | 
| 10.2.4 Resistance to ultra-violet (UV) radiation | 
                                                Meets the product standard's requirements.
                                             | 
| 10.2.5 Lifting | 
                                                Does not apply, since the entire switchgear needs to be evaluated.
                                             | 
| 10.2.6 Mechanical impact | 
                                                Does not apply, since the entire switchgear needs to be evaluated.
                                             | 
| 10.2.7 Inscriptions | 
                                                Meets the product standard's requirements.
                                             | 
| 10.3 Degree of protection of assemblies | 
                                                Does not apply, since the entire switchgear needs to be evaluated.
                                             | 
| 10.4 Clearances and creepage distances | 
                                                Meets the product standard's requirements.
                                             | 
| 10.5 Protection against electric shock | 
                                                Does not apply, since the entire switchgear needs to be evaluated.
                                             | 
| 10.6 Incorporation of switching devices and components | 
                                                Does not apply, since the entire switchgear needs to be evaluated.
                                             | 
| 10.7 Internal electrical circuits and connections | 
                                                Is the panel builder's responsibility.
                                             | 
| 10.8 Connections for external conductors | 
                                                Is the panel builder's responsibility.
                                             | 
| 10.9.2 Power-frequency electric strength | 
                                                Is the panel builder's responsibility.
                                             | 
| 10.9.3 Impulse withstand voltage | 
                                                Is the panel builder's responsibility.
                                             | 
| 10.9.4 Testing of enclosures made of insulating material | 
                                                Is the panel builder's responsibility.
                                             | 
| 10.10 Temperature rise | 
                                                The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
                                             | 
| 10.11 Short-circuit rating | 
                                                Is the panel builder's responsibility. The specifications for the switchgear must be observed.
                                             | 
| 10.12 Electromagnetic compatibility | 
                                                Is the panel builder's responsibility. The specifications for the switchgear must be observed.
                                             | 
| 10.13 Mechanical function | 
                                                The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
                                             | 
Assistance de la part d’Eaton
Des questions sur ce produit ?
0 800 336 858