Eaton xEnergy Basic LV systems Low voltage switchgear. Floor-standing distribution board without door, IP55, HxWxD=1760x600x320mm
| Product Name |
Eaton xEnergy Basic empty enclosure
|
| Catalog Number |
174362
|
| Model Code |
BPM-F-600/17-F
|
| EAN |
4015081708246
|
| Product Length/Depth |
320 mm
|
| Product Height |
1760 mm
|
| Product Width |
600 mm
|
| Product Weight |
46.8 kg
|
| Compliances |
RoHS conform
|
| Type |
Basic device
|
| Application |
Moisture-proof (installation site)
|
| Color |
Gray
Light gray (RAL 7035) |
| Surface finishing |
Powder coating
With powder coating |
| Mounting method |
Floor standing distribution board
Detached |
| Material |
Sheet steel
Steel |
| Degree of protection |
IP55
IK10 Other |
| Number of connector holes |
0
|
| Number of covers/doors |
0
|
| Number of locks |
0
|
| Permissible load of the door(s) according to IEC 62208 - max |
0 N
|
| Permissible load of the enclosure according to IEC 62208 - max |
0 N
|
| Permissible load of the mounting plate according to IEC 62208 - max |
0 N
|
| Grade material |
Sheet steel
|
| Installation type |
Floor installation possible
|
| Heat diss. ambient 35°C delta T: 20°C free stand middle encl. top (IEC 60890) |
130 W
|
| Heat diss. ambient 35°C delta T: 20°C wall mount middle encl. top (IEC 60890) |
115 W
|
| Heat diss. ambient 35°C delta T: 35°C free stand middle encl. top (IEC 60890) |
261 W
|
| Heat diss. ambient 35°C delta T: 35°C wall mount middle encl. top (IEC 60890) |
231 W
|
| Heat diss. ambient 35°C delta T:20°C free stand individ. encl. top (IEC 60890) |
156 W
|
| Heat diss. ambient 35°C delta T:20°C free stand starting encl. top (IEC 60890) |
142 W
|
| Heat diss. ambient 35°C delta T:20°C wall mount individ. encl. top (IEC 60890) |
132 W
|
| Heat diss. ambient 35°C delta T:20°C wall mount starting encl. top (IEC 60890) |
122 W
|
| Heat diss. ambient 35°C delta T:35°C free stand individ. encl. top (IEC 60890) |
312 W
|
| Heat diss. ambient 35°C delta T:35°C free stand starting encl. top (IEC 60890) |
284 W
|
| Heat diss. ambient 35°C delta T:35°C wall mount individ. encl. top (IEC 60890) |
264 W
|
| Heat diss. ambient 35°C delta T:35°C wall mount starting encl. top (IEC 60890) |
246 W
|
| Thermal dissipation (Delta T = 20 K) according to IEC/TR 60890 |
0 W
|
| 10.2.2 Corrosion resistance |
Meets the product standard's requirements.
|
| 10.2.3.1 Verification of thermal stability of enclosures |
Meets the product standard's requirements.
|
| 10.2.3.2 Verification of resistance of insulating materials to normal heat |
Meets the product standard's requirements.
|
| 10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects |
Meets the product standard's requirements.
|
| 10.2.4 Resistance to ultra-violet (UV) radiation |
Not relevant to indoor installations.
|
| 10.2.5 Lifting |
Met; assembled and secured as per the latest applicable instruction leaflet.
|
| 10.2.6 Mechanical impact |
IK10
|
| 10.2.7 Inscriptions |
Meets the product standard's requirements.
|
| 10.3 Degree of protection of assemblies |
IP55
|
| 10.4 Clearances and creepage distances |
Is the panel builder's responsibility.
|
| 10.5 Protection against electric shock |
< 0.1 Ω; meets the product standard's requirements.
|
| 10.6 Incorporation of switching devices and components |
Is the panel builder's responsibility.
|
| 10.7 Internal electrical circuits and connections |
Is the panel builder's responsibility.
|
| 10.8 Connections for external conductors |
Is the panel builder's responsibility.
|
| 10.9.2 Power-frequency electric strength |
Ui = 440 V AC
|
| 10.9.3 Impulse withstand voltage |
4 kV
|
| 10.9.4 Testing of enclosures made of insulating material |
Does not apply to metal enclosures.
|
| 10.10 Temperature rise |
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
|
| 10.11 Short-circuit rating |
Is the panel builder's responsibility.
|
| 10.12 Electromagnetic compatibility |
Is the panel builder's responsibility.
|
| 10.13 Mechanical function |
Meets the product standard's requirements.
|
| Functions |
Basic device
|
| RAL-number |
7035
|
| Suitable for |
Metrical mounting
|