Télécharger le document () de 20

199977
Model Code: XC-204-C20-002

Eaton Modular PLC XC204, Micro PLC, programmable CODESYS 3, USB, 2xEthernet, RS485, 2DIO, XN300 IO expandable

Spécifications générales

Product Name
Eaton XC200 modular PLC
Catalog Number
199977
Model Code
XC-204-C20-002
EAN
4015081997640
Product Length/Depth
104.2 mm
Product Height
29.3 mm
Product Width
80.3 mm
Product Weight
0.11 kg
Certifications
UL listed
EN 61131
EAC
UL File No.: E205091
CE
cULus Listed

Features & Functions

Features
Short-circuit protection (power supply)
Fitted with:
XSOFT-CODESYS 3
Functions
Additional program memory possible
Redundancy

General information

Connection type
Push-in spring-cage terminal, Connection design in TOP direction
Degree of protection
IP20
Model
Modular
Mounting method
Rail mounting possible
Overvoltage category
II
Pollution degree
2
Potential isolation
Between Digital inputs: no
Between Digital outputs: no
Voltage type
DC

Ambient conditions, mechanical

Mounting position
Vertical (on horizontal top-hat rail)
Shock resistance
15 g, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 11 ms, 9 Impacts
Vibration resistance
5 - 8.4 / 8.4 -150 Hz, 3,5 mm / 1 g

Climatic environmental conditions

Air pressure
795 - 1080 hPa (operation)
Ambient operating temperature - min
-20 °C
Ambient operating temperature - max
60 °C
Ambient storage temperature - min
-25 °C
Ambient storage temperature - max
70 °C
Relative humidity
< 95 % (non-condensing)

Electro magnetic compatibility

Emitted interference
40 dB (at 30 - 230 MHz, Class A, radiated, high frequency)
47 dB (at 230 - 1000 MHz, Class A, radiated, high frequency)

Terminal capacities

Terminal capacity
0.25 - 0.75 mm², with ferrules with plastic collar according to DIN 46228-1 (ferrules crimped gas-tight)
Terminal capacity (AWG)
24 - 16
Terminal capacity (flexible with ferrule)
0.25 - 1.5 mm², with ferrules without plastic collar according to DIN 46228-1 (ferrules crimped gas-tight)
0.25 - 1.5 mm², with ferrules with plastic collar according to DIN 46228-1 (ferrules crimped gas-tight)
Terminal capacity (flexible)
0.2 - 1.5 mm², H 07V-K
Terminal capacity (solid)
0.2 - 1.5 mm², H07V-U

Power supply

Input voltage
0 - 5 V (Digital inputs, low level)
24 V DC (Digital inputs)
15 - 30 V (Digital inputs, high level)
Output current
0.5 A
Supply voltage at AC, 50 Hz - min
0 VAC
Supply voltage at AC, 50 Hz - max
0 VAC
Supply voltage at DC - min
19.2 VDC
Voltage dips
20 ms
10 ms
Supply voltage at DC - max
30 VDC

Communication

Interfaces
2 x ETH
RS485
DIO
XN300
Protocol
EtherNet/IP
MODBUS
Other bus systems
TCP/IP

Input/Output

Delay time
200 µs, Digital outputs, Delay on signal change and resistive load, from High to Low signal
200 µs, Digital outputs, Delay on signal change and resistive load, from Low to High signal
Input current
≤ 1.1 mA (Digital inputs, low level)
≥ 2.0 mA (Digital inputs, high level)
Number of channels
2
Number of inputs (analog)
0
Number of inputs (digital)
2
Number of outputs (analog)
0
Number of outputs (digital)
2
Number of relay outputs
0
Rated operational current (Ie)
2.4 A (supply input)
Utilization factor
100 % (Ʃ IAmax = 2A)

Safety

Explosion safety category for gas
None
Explosion safety category for dust
None

System

Memory capacity
512,000 kByte

Design verification

Static heat dissipation, non-current-dependent Pvs
6.3 W
Heat dissipation details
The max. heat dissipation is specified as the maximum power produced inside the device's housing.
10.2.2 Corrosion resistance
Meets the product standard's requirements.
10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard's requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard's requirements.
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects
Meets the product standard's requirements.
10.2.4 Resistance to ultra-violet (UV) radiation
Meets the product standard's requirements.
10.2.5 Lifting
Does not apply, since the entire switchgear needs to be evaluated.
10.2.6 Mechanical impact
Does not apply, since the entire switchgear needs to be evaluated.
10.2.7 Inscriptions
Meets the product standard's requirements.
10.3 Degree of protection of assemblies
Meets the product standard's requirements.
10.4 Clearances and creepage distances
Meets the product standard's requirements.
10.5 Protection against electric shock
Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and components
Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections
Is the panel builder's responsibility.
10.8 Connections for external conductors
Is the panel builder's responsibility.
10.9.2 Power-frequency electric strength
Is the panel builder's responsibility.
10.9.3 Impulse withstand voltage
Is the panel builder's responsibility.
10.9.4 Testing of enclosures made of insulating material
Is the panel builder's responsibility.
10.10 Temperature rise
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating
Is the panel builder's responsibility.
10.12 Electromagnetic compatibility
Is the panel builder's responsibility.
10.13 Mechanical function
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.

Exporter les spécifications du produit

Remarque : L’absence d’un ou plusieurs fichiers dans un ficher .zip téléchargé peut être causée par l’absence de prise en charge du type de fichier pour un téléchargement groupé.