Pow-R-Line 3e distribution panelboards

Eaton's Pow-R-Line 3e distribution panelboards provide higher interrupting ratings for selective coordination purposes and electric power distribution with integrated breakers, metering and surge protection. Additionally, they’re designed to meet UL 67 and NEMA PB1 standards for use in data center, industrial, commercial and healthcare facilities for up to 480 Vac, 250 Vdc and 600 A applications.

Maximum voltage class
480 Vac and 250 Vdc
Interrupting rating
Fully-rated to 100 kAIC Series-rated to 200 kAIC
Continuous current rating
100-600 A

핵심 기능

  • Includes bolt-on breakers up to 125 A
  • Provides flush or surface mounted, and fully or series rated options
  • Offers aluminum or copper bus options
  • Includes NEMA 1, 2, 3R and 12 enclosures
  • Offers sub-feed or through-feed lugs, single sub-feed breaker options, and a handle lock off device
  • Includes surge protection, service entrance and integrated metering capabilities
  • Panelboards are seismically tested, qualified and exceed requirements of the IBC/CBC/OSHPD

Selective coordination breaker application

Determine selective coordination by short circuit current ratings in panelboards

Customized solutions, customized service

Regional satellite locations provide manufacturing of local, custom, and quick-ship panelboards and switchboards

    EZ Trim and EZ Box capabilities

    Install tool-less of standard door-in-door construction with no exposed hardware or sharp edges

    You may also be interested in

    사양

    Ratings

    RATED MAXIMUM VOLTAGE 480 Vac and 250 Vdc
    CONTINUOUS CURRENT 100-600 A
    INTERRUPTING RATING

    240 Vac: 25-100 kA fully rated

    240 Vac: 100-200 kA series rated

    480Y/277 Vac: 18-65 kA fully rated

    480Y/277 Vac: 65-100 kA series rated

    250 Vdc: 10-22 kA fully rated

    Standards

    NEMA PB-1
    THIRD-PARTY APPROVAL/RECOGNITION UL 67 / CSA
    SEISMIC QUALIFICATION Lighting and appliance panelboards certificate

    Devices

    PROTECTION DEVICES

    Molded Case Circuit Breakers

     and 

    Miniature Circuit Breakers

    METERS

    IQ 35

    SURGE PROTECTION DEVICES

    SPD

    DEVICE MOUNTING

    Bolt-on

    Enclosure

    ACCESS Top and bottom access
    ENCLOSURE TYPE NEMA Type 1, 2, 3R and 12
    STANDARD INDOOR WIDTH DIMENSIONS 20 and optional 28 inches
    STANDARD INDOOR DEPTH DIMENSIONS 5.75 inches
    STANDARD INDOOR HEIGHT DIMENSIONS 36, 42, 48, 60, 72 or 90 inches
    CUSTOM DIMENSIONS AVAILABLE Contact satellite manufacturing facility