문서 다운로드 () / 20
당신의 필요한 일, 이튼이 합니다*
중단됨

090900
모델 코드: MCS11-U

Eaton Moeller® series MCS Pressure switch, 1W, 15bar MCS11-U

일반 규범

Product Name
Eaton Moeller® series MCS Pressure switch
Catalog Number
090900
Model Code
MCS11-U
EAN
4015080909002
Product Length/Depth
96 mm
Product Height
111 mm
Product Width
60 mm
Product Weight
0.28 kg
Certifications
IEC/EN 60947-5-1
Catalog Notes
Note on use: This product complies with Low-Voltage Directive 2014/35/EC and EMC Directive 2014/30/EC and meets the requirements in EN 60947-5-1. This product does not meet the rail industry's standard requirements. Accordingly, the user must review it separately for the specific application at hand.

특징 및 기능

Electric connection type
Screw connection
Features
Variable switching differential

일반

Actuator diameter
0 mm
Bursting pressure
90 bar
Connection
Inner thread gas cylindrical (BSPP)
Connection type
Tunnel terminal
Degree of protection
IP65
NEMA Other
Operating pressure - max
15000 hPa
Overvoltage category
III
Pollution degree
3
Product category
Pressure switches
Rated impulse withstand voltage (Uimp)
4000 V AC
Suitable as
2-point controller
Guard
Test pressure
32 bar

주변 조건, 기계적 조건

Mounting position
As required
Shock resistance
10 g, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 20 ms
Vibration resistance
36 Hz, Amplitude 1 mm, (IEC/EN 60068-2-6)

기후 환경 조건

Ambient operating temperature - min
25 °C
Ambient operating temperature - max
70 °C
Climatic proofing
Damp heat, constant, to IEC 60068-2-78
Damp heat, cyclic, to IEC 60068-2-30

단자 용량

Terminal capacity (flexible with ferrule)
1 x (0.5 - 1.5) mm², ferrules to DIN 46228
Terminal capacity (solid)
1 x (0.75 - 2.5) mm²
Screw size
M3, Terminal screw
Tightening torque
0.5 Nm, Screw terminals

전기 정격

Rated frequency - max
50 Hz
Rated insulation voltage (Ui)
400 V
Rated operational current (Ie)
0.25 A at DC-13, 110 V
2 A at DC-13, 24 V
Rated operational current (Ie) at AC-1, 380 V, 400 V, 415 V
0 A
Rated operational current (Ie) at AC-3, 380 V, 400 V, 415 V
0 A
Rated operational power at AC-3, 380/400 V, 50 Hz
0 kW
Rated operational voltage (Ue) at AC - min
0 V
Rated operational voltage (Ue) at AC - max
230 V
Rated operational voltage (Ue) at DC - min
0 V
Rated operational voltage (Ue) at DC - max
110 V

단락 정격

Short-circuit protection rating
Max. 10 A gG/gL, Fuse, Contacts

접점

Number of auxiliary contacts (change-over contacts)
1
Number of auxiliary contacts (normally closed contacts)
0
Number of auxiliary contacts (normally open contacts)
0

제품 사양 내보내기

참고: ZIP 다운로드에 파일이 없는 경우 해당 파일 형식은 대량 다운로드에서 지원되지 않습니다.