Reset
Eaton Moeller series NZM - Molded Case Circuit Breaker. Switch-disconnector 4p 200A 1000VDC
Product Name |
Eaton Moeller series NZM switch-disconnector
|
Catalog Number |
127733
|
Model Code |
N2-4-200-S1-DC
|
EAN |
4015081251438
|
Product Length/Depth |
149 mm
|
Product Height |
184 mm
|
Product Width |
140 mm
|
Product Weight |
2.878 kg
|
Compliances |
RoHS conform
|
Certifications |
IEC
|
Voltage rating |
1000 V - 1000 V
|
Rated operating voltage (Ue) at AC - max |
0 V
|
Rated insulation voltage (Ui) |
1250 V
|
Current rating (Iu) at 40°C with terminal jumpers |
200 A
|
Current rating (Iu) at 65°C with terminal jumpers |
200 A
|
Rated operational current |
200 A (DC 22-A)
|
Rated permanent current at AC-21, 400 V |
0 A
|
Rated permanent current at AC-23, 400 V |
0 A
|
Rated conditional short-circuit current with back-up fuse |
200 AgR
15 kA at 1000 V |
Rated conditional short-circuit current (Iq) |
0 kA
|
Rated short-time withstand current (Icw) |
3.6 kA
|
Rated short-time withstand current (t = 1 s) |
3.6 kA
|
Amperage Rating |
200 A
|
Rated operating power at AC-3, 400 V |
0 kW
|
Rated operating power at AC-23, 400 V |
0 kW
|
Switching power at 400 V |
0 kW
|
Short-circuit protective device fuses - max |
200 A gR
|
Electrical connection type of main circuit |
Screw connection
|
Number of operations per hour - max |
120
|
Handle type |
Rocker lever
|
Utilization category |
DC-22 A
|
Overvoltage category |
III
|
Pollution degree |
3
|
Current rating (Iu) at 40°C with terminal jumpers |
200 A
|
Current rating (Iu) at 65°C with terminal jumpers |
200 A
|
Rated operational current |
200 A (DC 22-A)
|
Rated permanent current at AC-21, 400 V |
0 A
|
Rated permanent current at AC-23, 400 V |
0 A
|
Rated conditional short-circuit current with back-up fuse |
200 AgR
15 kA at 1000 V |
Rated conditional short-circuit current (Iq) |
0 kA
|
Rated short-time withstand current (Icw) |
3.6 kA
|
Rated short-time withstand current (t = 1 s) |
3.6 kA
|
Amperage Rating |
200 A
|
Rated operating power at AC-3, 400 V |
0 kW
|
Rated operating power at AC-23, 400 V |
0 kW
|
Switching power at 400 V |
0 kW
|
Short-circuit protective device fuses - max |
200 A gR
|
Electrical connection type of main circuit |
Screw connection
|
Number of operations per hour - max |
120
|
Handle type |
Rocker lever
|
Utilization category |
DC-22 A
|
Overvoltage category |
III
|
Pollution degree |
3
|
Mounting Method |
Ground mounting
Built-in device fixed built-in technique Distribution board installation Fixed Intermediate mounting |
Degree of protection |
IP20
|
Degree of protection (IP), front side |
IP20
|
Number of auxiliary contacts (change-over contacts) |
0
|
Number of auxiliary contacts (normally closed contacts) |
0
|
Number of auxiliary contacts (normally open contacts) |
0
|
Number of switches |
1
|
Handle color |
Black
|
Switch positions |
I, +, 0
|
Lifespan, mechanical |
20000 operations
|