문서 다운로드 () / 20
당신의 필요한 일, 이튼이 합니다*

1319904
모델 코드: QM63/6N2

Eaton QM Switch-disconnector, QM, 50 A, 6 pole + 2 N (switched), without rotary handle, With drive shaft, 6 mm square

일반 규범

Product Name
Eaton QM Switch-disconnector
Catalog Number
1319904
Model Code
QM63/6N2
EAN
8711426181670
Product Length/Depth
125 mm
Product Height
90 mm
Product Width
125 mm
Product Weight
0.94 kg
Certifications
IEC/EN 60947-3
IEC/EN 60947
VDE 0660
RoHS
CE
IEC/EN 60204

특징 및 기능

Fitted with:
Drive shaft
Functions
Optional Stop Function
Number of poles
Eight-pole

일반

Accessories
Auxiliary contact fitted by user.
Actuator type
Other
Degree of protection
NEMA Other
Degree of protection (front side)
IP20
Mounting method
Top-hat rail mounting
Rear mounting
Mounting position
As required
Overvoltage category
III
Pollution degree
3
Product Category
  • Main switch
  • Switch-disconnector
Rated impulse withstand voltage (Uimp)
6000 V
Safety parameter (EN ISO 13849-1)
B10d values as per EN ISO 13849-1, table C.1

기후 환경 조건

Ambient operating temperature - min
-25 °C
Ambient operating temperature - max
55 °C
Ambient storage temperature - min
-30 °C
Ambient storage temperature - max
80 °C

단자 용량

Terminal capacity
2.5 - 16 mm², solid
1 x (2.5 - 10) mm², flexible
Stripping length (main cable)
10 mm
Stripping length (main cable)
10 mm
Tightening torque
1.8 Nm, Screw terminals, Main cables

전기 정격

Rated conditional short-circuit current (Iq)
15 kA
Rated insulation voltage (Ui)
690 V
Rated operational power at AC-23A, 400 V, 50 Hz
22 kW
Rated operational power at AC-3, 380/400 V, 50 Hz
18.5 kW
Rated operational voltage (Ue) at AC - max
690 V
Rated uninterrupted current (Iu)
50 A
Uninterrupted current
Rated uninterrupted current Iu is specified for max. cross-section.

연락처

Number of auxiliary contacts (normally closed contacts)
0
Number of auxiliary contacts (normally open contacts)
0

설계 검증

Equipment heat dissipation, current-dependent Pvid
0 W
Heat dissipation capacity Pdiss
0 W
Heat dissipation per pole, current-dependent Pvid
6 W
Rated operational current for specified heat dissipation (In)
50 A
Static heat dissipation, non-current-dependent Pvs
0 W
10.2.2 Corrosion resistance
Meets the product standard's requirements.
10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard's requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard's requirements.
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects
Meets the product standard's requirements.
10.2.4 Resistance to ultra-violet (UV) radiation
Meets the product standard's requirements.
10.2.5 Lifting
Does not apply, since the entire switchgear needs to be evaluated.
10.2.6 Mechanical impact
Does not apply, since the entire switchgear needs to be evaluated.
10.2.7 Inscriptions
Meets the product standard's requirements.
10.3 Degree of protection of assemblies
Does not apply, since the entire switchgear needs to be evaluated.
10.4 Clearances and creepage distances
Meets the product standard's requirements.
10.5 Protection against electric shock
Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and components
Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections
Is the panel builder's responsibility.
10.8 Connections for external conductors
Is the panel builder's responsibility.
10.9.2 Power-frequency electric strength
Is the panel builder's responsibility.
10.9.3 Impulse withstand voltage
Is the panel builder's responsibility.
10.9.4 Testing of enclosures made of insulating material
Is the panel builder's responsibility.
10.10 Temperature rise
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.12 Electromagnetic compatibility
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.13 Mechanical function
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.

제품 사양 내보내기

참고: ZIP 다운로드에 파일이 없는 경우 해당 파일 형식은 대량 다운로드에서 지원되지 않습니다.