문서 다운로드 () / 20
당신의 필요한 일, 이튼이 합니다*

206929
모델 코드: UTI1,0-115

Eaton Moeller® series UTI Control transformer, 1 kVA, Rated input voltage 208 – 600 V, Rated output voltage 2 x 115 V

일반 규범

Product Name
Eaton Moeller® series UTI Control transformer
Catalog Number
206929
Model Code
UTI1,0-115
EAN
4015082069292
Product Length/Depth
150 mm
Product Height
150 mm
Product Width
151 mm
Product Weight
13.4 kg
Certifications
UL Recognized
CSA-C22.2 No. 66.1-06
CSA-C22.2 No. 66.2-06
VDE 0570 Part 2-2/2-6 (safety transformer)
UL report applies to both US and Canada
UL 506
IEC/EN 61558-2-2/2-4/2-6
VDE 0113, VDE 0100 Part 410
IEC/EN 61558-2-2
UL 5085-2
VDE 0550
UL5085-1
CSA-C22.2 No. 66
Certified by UL for use in Canada
VDE 0570 Part 2-4 (isolating transformer)
IEC/EN 60204-1, ÖVE-EN 13
UL File No.: E167225
CE
UL Category Control No.: XPTQ2, XPTQ8
Catalog Notes
Electrical characteristics: all details for no-load loss, short-circuit loss (copper losses), short-circuit voltage and efficiency values relate to a temperature of 20 °C

특징 및 기능

Features
Reinforced insulation
Fully Vacuum-impregnated
Separate windings

일반

Ambient operating temperature - min
-25 °C
Ambient operating temperature - max
40 °C
Connection type
Terminations
Duty factor
100 %
Insulation class
B
Primary tapping
± 20 %
Product category
Single-phase UTI multi-winding transformers
Suitable for
Branch circuits, (UL/CSA)

전기 정격

Efficiency
92.9 %
No-load losses
46 W
Rated frequency - min
50 Hz
Rated frequency - max
60 Hz
Rated power
1 VA
Relative short-circuit voltage
2.1 %
Short-circuit losses
30 W
Voltage rating - max
600 V

설계 검증

Equipment heat dissipation, current-dependent Pvid
0 W
Heat dissipation capacity Pdiss
0 W
Heat dissipation per pole, current-dependent Pvid
0 W
Rated operational current for specified heat dissipation (In)
0 A
Static heat dissipation, non-current-dependent Pvs
76 W
10.2.2 Corrosion resistance
Meets the product standard's requirements.
10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard's requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard's requirements.
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects
Meets the product standard's requirements.
10.2.4 Resistance to ultra-violet (UV) radiation
Meets the product standard's requirements.
10.2.5 Lifting
Does not apply, since the entire switchgear needs to be evaluated.
10.2.6 Mechanical impact
Does not apply, since the entire switchgear needs to be evaluated.
10.2.7 Inscriptions
Meets the product standard's requirements.
10.3 Degree of protection of assemblies
Does not apply, since the entire switchgear needs to be evaluated.
10.4 Clearances and creepage distances
Meets the product standard's requirements.
10.5 Protection against electric shock
Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and components
Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections
Is the panel builder's responsibility.
10.8 Connections for external conductors
Is the panel builder's responsibility.
10.9.2 Power-frequency electric strength
Is the panel builder's responsibility.
10.9.3 Impulse withstand voltage
Is the panel builder's responsibility.
10.9.4 Testing of enclosures made of insulating material
Is the panel builder's responsibility.
10.10 Temperature rise
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.12 Electromagnetic compatibility
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.13 Mechanical function
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.

제품 사양 내보내기

참고: ZIP 다운로드에 파일이 없는 경우 해당 파일 형식은 대량 다운로드에서 지원되지 않습니다.