문서 다운로드 () / 20
당신의 필요한 일, 이튼이 합니다*

278428
모델 코드: DILM1000-XHIC11-SI

Eaton Moeller® series DILM Auxiliary contact module, 2 pole, Ith= 10 A, 1 N/O, 1 NC, Side mounted, Spring-loaded terminals, DILM40 - DILM225A

일반 규범

Product Name
Eaton Moeller® series DILM auxiliary contact module
Catalog Number
278428
Model Code
DILM1000-XHIC11-SI
EAN
4015082784287
Product Length/Depth
77 mm
Product Height
77 mm
Product Width
15 mm
Product Weight
0.037 kg
Certifications
CSA
VDE 0660
CSA-C22.2 No. 14-05
IEC/EN 60947-4-1
CE
UL
CSA Class No.: 3211-04
CSA File No.: 012528
UL 508
UL Category Control No.: NKCR
UL File No.: E29184
IEC/EN 60947

정격 작동 전류

Features
Interlocked opposing contacts within an auxiliary contact module (according to IEC 60947-5-1 Annex L)
Functions
For standard applications
Fitted with:
Interlocked opposing contacts
Number of poles
Two-pole
Electric connection type
Spring clamp connection

정격 작동 전력

Lifespan, electrical
1,300,000 Operations (at 230 V, AC-15, 3 A)
Model
Top mounting
Mounting method
Side mounting
Overvoltage category
III
Pollution degree
3
Protection
Finger and back-of-hand proof, Protection against direct contact when actuated from front (EN 50274)
Rated impulse withstand voltage (Uimp)
6000 V
6000 V AC
Type
Side-mounting auxiliary contacts

정격 작동 전압

Ambient operating temperature - min
-25 °C
Ambient operating temperature - max
60 °C
Ambient operating temperature (enclosed) - min
-25 °C
Ambient operating temperature (enclosed) - max
40 °C
Ambient storage temperature - min
-40 °C
Ambient storage temperature - max
80 °C
Climatic proofing
Damp heat, constant, to IEC 60068-2-78
Damp heat, cyclic, to IEC 60068-2-30

도체 세부 정보

Terminal capacity (flexible with ferrule)
1 x (1 - 2.5) mm²
2 x (1 - 2.5) mm²
Terminal capacity (solid)
2 x (1 - 2.5) mm²
1 x (1 - 2.5) mm²
Terminal capacity (solid/stranded AWG)
16 - 14
Screwdriver size
0.6 x 3.5 mm, Spring-loaded terminals

전자기 호환성(EMC)

Rated operational current (Ie)
1 A at 220 V, DC L/R ≤ 15 ms (with 1 contact in series)
10 A at 24 V, DC L/R ≤ 15 ms (with 1 contact in series)
6 A at 60 V, DC L/R ≤ 15 ms (with 1 contact in series)
3 A at 110 V, DC L/R ≤ 15 ms (with 1 contact in series)
Rated operational current (Ie) at AC-15, 220 V, 230 V, 240 V
6 A
Rated operational current (Ie) at AC-15, 380 V, 400 V, 415 V
4 A
Rated operational current (Ie) at AC-15, 500 V
1.5 A

제품 사양 내보내기