Eaton DG1 Variable frequency drive, 400 V AC, 3-phase, 385 A, 200 kW, IP00, DC link choke
| Product Name |
Eaton DG1 variable frequency drive
|
| Catalog Number |
3-4917-103A
|
| EAN |
4015081941735
|
| Product Length/Depth |
561 mm
|
| Product Height |
980 mm
|
| Product Width |
506 mm
|
| Product Weight |
205 kg
|
| Certifications |
UkrSEPRO
CUL Safety requirements: IEC/EN 61800-5 CE C-Tick EAC IEC/EN 61800-3 RoHS, ISO 9001 Specification for general requirements: IEC/EN 61800-2 UL |
| Model Code |
DG1-34385FN-C00C
|
| Features |
Temperature-controlled fan
Externally accessible fan Parameterization: Fieldbus Parameterization: Keypad Parameterization: Power Xpert inControl |
| Air volume capacity |
1400 m³/h
|
| Cable length |
50 m, screened, maximum permissible, Motor feeder
C2 ≤ 10 m, Radio interference level, maximum motor cable length C3 ≤ 50 m, Radio interference level, maximum motor cable length |
| Degree of protection |
IP00
NEMA Other |
| Electromagnetic compatibility |
1st and 2nd environments (according to EN 61800-3)
|
| Environmental class |
3C2, 3S2 (Air quality)
|
| Fitted with: |
DC link choke
Internal DC link Multi-line graphic display Additional PCB protection IGBT inverter Radio interference suppression filter Control unit PC connection |
| Frame size |
FS7
|
| Mounting position |
Vertical
|
| Number of slots |
2 (expansion)
|
| Overvoltage category |
III
|
| Pollution degree |
2
|
| Product Category |
Variable frequency drives
|
| Protection |
Finger and back-of-hand proof, Protection against direct contact (BGV A3, VBG4)
|
| Radio interference class |
C1: with external filter, for conducted emissions only
Optional external radio interference suppression filter for longer motor cable lengths and for use in different EMC environments C2, C3: depending on the motor cable length, the connected load, and ambient conditions. External radio interference suppression filters (optional) may be necessary. |
| Safety function/level |
STO (Safe Torque Off, SIL1, PLc Cat 1)
|
| Shock resistance |
UPS drop test (for weights inside the UPS frame)
Mechanical, According to EN 61800-5-1, IEC/EN 60068-2-27 Storage and transportation: maximum 15 g, 11 ms (inside the packaging) |
| Suitable for |
Branch circuits, (UL/CSA)
|
| Vibration |
Resistance: 5 - 15.8 Hz, Amplitude 1 mm (peak)
Resistance: 5 - 150 Hz, According to EN 61800-5-1, IEC/EN 60068-2-6 Resistance: 15.8 – 150 Hz, 1 g, Maximum acceleration amplitude |
| Altitude |
Max. 2000 m for Corner Grounded TN Systems
Max. 1000 m Max. 3000 m Above 1000 m with 1 % derating per 100 m |
| Ambient operating temperature - min |
-10 °C
|
| Ambient operating temperature - max |
40 °C
|
| Ambient operating temperature at 150% overload - min |
-10 °C
|
| Ambient operating temperature at 150% overload - max |
40 °C
|
| Ambient storage temperature - min |
-40 °C
|
| Ambient storage temperature - max |
70 °C
|
| Climatic proofing |
< 95 average relative humidity (RH), no condensation, no corrosion
|
| Current limitation |
0.1 - 2 x IH (CT), motor, main circuit
|
| Efficiency |
97.9 % (η)
|
| Input current ILN at 110% overload |
460 A
|
| Input current ILN at 150% overload |
391 A
|
| Mains current distortion |
28 %
|
| Mains switch-on frequency |
Maximum of one time every 60 seconds
|
| Mains voltage - min |
380 V
|
| Mains voltage - max |
500 V
|
| Operating mode |
U/f control
Sensorless vector control (SLV) Speed control with slip compensation Torque regulation |
| Output frequency - min |
0 Hz
|
| Output frequency - max |
400 Hz
|
| Output voltage (U2) |
480 V AC, 3-phase
400 V AC, 3-phase 500 V AC, 3-phase |
| Overload current IL at 110% overload |
506 A
|
| Overload current IL at 150% overload |
577.5 A
|
| Rated conditional short-circuit current (Iq) |
65 kA
|
| Rated control supply voltage |
10 V DC (Us, max. 10 mA)
|
| Rated frequency - min |
45 Hz
|
| Rated frequency - max |
66 Hz
|
| Rated operational current (Ie) at 110% overload |
460 A
|
| Rated operational current (Ie) at 150% overload |
385 A
|
| Rated operational power at 380/400 V, 50 Hz |
200 kW
|
| Rated operational power at 380/400 V, 50 Hz, 110% overload |
250 kW
|
| Rated operational power at 500 V, 50 Hz |
250 kW
|
| Rated operational power at 500 V, 50 Hz, 110% overload |
315 kW
|
| Rated operational voltage |
400 V AC, 3-phase
500 V AC, 3-phase 480 V AC, 3-phase |
| Resolution |
0.01 Hz (Frequency resolution, setpoint value)
|
| Short-circuit protection rating |
600 A, UL (Class CC or J), Safety device (fuse or miniature circuit-breaker), Power Wiring
|
| Starting current - max |
200 %, IH, max. starting current (High Overload), For 2 seconds every 20 seconds, Power section
|
| Supply frequency |
50/60 Hz
|
| Switching frequency |
2 kHz, 1.5 - 6 kHz adjustable, fPWM, Power section, Main circuit
|
| System configuration type |
TN-S, TN-C, TN-C-S, TT, IT
|
| Voltage rating - max |
500 VAC
|
| Assigned motor current IM at 400 V, 50 Hz, 110% overload |
437 A
|
| Assigned motor current IM at 400 V, 50 Hz, 150% overload |
353 A
|
| Assigned motor current IM at 440 - 480 V, 60 Hz, 150% overload |
361 A
|
| Assigned motor current IM at 440/480 V, 60 Hz, 110% overload |
414 A
|
| Assigned motor current IM at 500 V, 50 Hz, 110% overload |
436 A
|
| Assigned motor current IM at 500 V, 50 Hz, 150% overload |
349 A
|
| Assigned motor power at 460/480 V, 60 Hz |
300 HP
|
| Assigned motor power at 460/480 V, 60 Hz, 110% overload |
350 HP
|
| Apparent power at 400 V |
318.7 kVA
|
| Apparent power at 480 V |
398.4 kVA
|
| Braking resistance |
1.4 Ω
|
| Braking torque |
Adjustable to 150 % (I/Ie), DC - Main circuit
Max. 30 % MN, Standard - Main circuit Adjustable to 150 %, DC - Main circuit Max. 100 % of rated operational current Ie with external braking resistor - Main circuit |
| Switch-on threshold for the braking transistor |
850 VDC
|
| Number of inputs (analog) |
2
|
| Number of inputs (digital) |
8
|
| Number of outputs (analog) |
2
|
| Number of outputs (digital) |
1
|
| Number of relay outputs |
3 (parameterizable, 2 changeover contacts and 1 N/O, 6 A (240 V AC) / 6 A (24 V DC))
|
| Rated control voltage (Uc) |
24 V DC (external, max. 250 mA options incl.)
|
| Communication interface |
Modbus TCP, built in
CANopen®, optional PROFIBUS, optional Ethernet IP, built in BACnet MS/TP, built in DeviceNet, optional Modbus RTU, built in SmartWire-DT, optional |
| Connection to SmartWire-DT |
In conjunction with DXG-NET-SWD SmartWire DT module
Yes |
| Protocol |
BACnet
CAN DeviceNet EtherNet/IP MODBUS Other bus systems PROFIBUS PROFINET IO TCP/IP |
| Equipment heat dissipation, current-dependent Pvid |
5465 W
|
| Rated operational current for specified heat dissipation (In) |
385 A
|
| Static heat dissipation, non-current-dependent Pvs |
108 W
|
| 10.2.2 Corrosion resistance |
Meets the product standard's requirements.
|
| 10.2.3.1 Verification of thermal stability of enclosures |
Meets the product standard's requirements.
|
| 10.2.3.2 Verification of resistance of insulating materials to normal heat |
Meets the product standard's requirements.
|
| 10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects |
Meets the product standard's requirements.
|
| 10.2.4 Resistance to ultra-violet (UV) radiation |
Meets the product standard's requirements.
|
| 10.2.5 Lifting |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.2.6 Mechanical impact |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.2.7 Inscriptions |
Meets the product standard's requirements.
|
| 10.3 Degree of protection of assemblies |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.4 Clearances and creepage distances |
Meets the product standard's requirements.
|
| 10.6 Incorporation of switching devices and components |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.7 Internal electrical circuits and connections |
Is the panel builder's responsibility.
|
| 10.8 Connections for external conductors |
Is the panel builder's responsibility.
|
| 10.9.2 Power-frequency electric strength |
Is the panel builder's responsibility.
|
| 10.9.3 Impulse withstand voltage |
Is the panel builder's responsibility.
|
| 10.9.4 Testing of enclosures made of insulating material |
Is the panel builder's responsibility.
|
| 10.10 Temperature rise |
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
|
| 10.11 Short-circuit rating |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
| 10.12 Electromagnetic compatibility |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
| 10.13 Mechanical function |
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
|