Download documento () de 20

189727
Model code: NZM2/3-XU2A208-240AC

Eaton Moeller series NZM Undervoltage release for NZM2/3, configurable relays, 2NO, 208-240AC, Push-in terminals

General specifications

Product Name
Eaton Moeller series NZM Undervoltage release
Catalog Number
189727
EAN
4015081877225
Product Length/Depth
115 mm
Product Height
65 mm
Product Width
75 mm
Product Weight
0.08 kg
Compliances
UL/CSA
IEC
RoHS conform
Certifications
CSA (Class No. 1437-01)
IEC60947
UL489
UL (File No. E140305)
CSA (File No. 22086)
UL listed
UL (Category Control Number DIHS)
CSA certified
CE marking
CSA-C22.2 No. 5-09
Model Code
NZM2/3-XU2A208-240AC

Dados técnicos - elétricos

Voltage type
AC
Rated insulation voltage (Ui)
250 V
Rated impulse withstand voltage (Uimp)
4 kV AC
Rated control voltage (relay contacts)
240 V AC
24 V AC
24 V DC
208 V AC
Rated control supply voltage (Us) at AC, 50 Hz - min
208 V
Rated control supply voltage (Us) at AC, 50 Hz - max
240 V
Rated control supply voltage (Us) at AC, 60 Hz - min
208 V
Rated control supply voltage (Us) at AC, 60 Hz - max
240 V
Voltage tolerance - min
0.85
Voltage tolerance - max
1.1
Drop-out voltage of undervoltage release AC/DC - min
0.35 x Us
Drop-out voltage of undervoltage release AC/DC - max
0.7 x Us
Rated operational current
1 A (110 V AC-1, relay contacts)
1 A (230 V AC-1, relay contacts)
1 A (24 V AC-1, relay contacts)
1 A (24 V DC-1, relay contacts)
Power consumption
0.8 W (sealing DC)
1.5 VA (sealing AC)
Pick-up power consumption at AC (undervoltage release)
1.5 VA
Pick-up power consumption at DC (undervoltage release)
0.8 W
Switching capacity (reference value) - min
0.1 mA / 0.1 VDC
Reaction time
19 ms
Minimum command time - min
10 ms
Minimum command time - max
15 ms
Electric connection type
Spring clamp connection
Overvoltage category
II
Pollution degree
2

Dados técnicos - comunicação

Rated impulse withstand voltage (Uimp)
4 kV AC
Rated control voltage (relay contacts)
240 V AC
24 V AC
24 V DC
208 V AC
Rated control supply voltage (Us) at AC, 50 Hz - min
208 V
Rated control supply voltage (Us) at AC, 50 Hz - max
240 V
Rated control supply voltage (Us) at AC, 60 Hz - min
208 V
Rated control supply voltage (Us) at AC, 60 Hz - max
240 V
Voltage tolerance - min
0.85
Voltage tolerance - max
1.1
Drop-out voltage of undervoltage release AC/DC - min
0.35 x Us
Drop-out voltage of undervoltage release AC/DC - max
0.7 x Us
Rated operational current
1 A (110 V AC-1, relay contacts)
1 A (230 V AC-1, relay contacts)
1 A (24 V AC-1, relay contacts)
1 A (24 V DC-1, relay contacts)
Power consumption
0.8 W (sealing DC)
1.5 VA (sealing AC)
Pick-up power consumption at AC (undervoltage release)
1.5 VA
Pick-up power consumption at DC (undervoltage release)
0.8 W
Switching capacity (reference value) - min
0.1 mA / 0.1 VDC
Reaction time
19 ms
Minimum command time - min
10 ms
Minimum command time - max
15 ms
Electric connection type
Spring clamp connection
Overvoltage category
II
Pollution degree
2

Dados técnicos - mecânicos

Number of contacts (change-over contacts)
0
Number of contacts (normally closed contacts)
0
Number of contacts (normally open contacts)
2
Number of relays
2
Connection type
With push in terminal
Strip length
8 mm (relay contact connection)

Exportar as especificações do produto

Nota: Se existirem ficheiro(s) em falta na pasta .zip transferida, significa que o tipo de ficheiro não é compatível com a transferência de vários ficheiros em simultâneo.