192523
Model code: NZMN2-MX90-NA

NZMN2-MX90-NA. NZM2 PXR20 circuit breaker, 90A, 3p, Screw terminal, UL/CSA

General specifications

Product Name
Eaton Moeller series NZM molded case circuit breaker electronic
Catalog Number
192523
EAN
4015081932511
Product Length/Depth
149 mm
Product Height
195 mm
Product Width
105 mm
Product Weight
2.509 kg
Compliances
RoHS conform
Certifications
CE marking
CSA-C22.2 No. 5-09
UL 489
UL listed
UL508
Specially designed for North America
CSA (Class No. 1432-01)
UL (File No. E31593)
CSA certified
IEC 60947-2
CSA (File No. 22086)
UL/CSA
UL (Category Control Number DIVQ)
IEC
Model Code
NZMN2-MX90-NA

Additional information

Functions
Phase failure sensitive
Current limiting circuit breaker
Motor protection

Delivery program

Amperage Rating
90 A
Application
Branch circuits, feeder circuits
Circuit breaker frame type
NZM2
Fitted with:
Thermal protection
Number of poles
Three-pole
Release system
Electronic release
Special features
  • Rated current = rated uninterrupted current: 90 A
  • Switches conform to UL/CSA as well as the IEC regulations. IEC switching performance values are contained on the rating plate.
Type
Circuit breaker

Design verification as per IEC/EN 61439

10.10 Temperature rise
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.12 Electromagnetic compatibility
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.13 Mechanical function
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
10.2.2 Corrosion resistance
Meets the product standard's requirements.
10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard's requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard's requirements.
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects
Meets the product standard's requirements.
10.2.4 Resistance to ultra-violet (UV) radiation
Meets the product standard's requirements.
10.2.5 Lifting
Does not apply, since the entire switchgear needs to be evaluated.
10.2.6 Mechanical impact
Does not apply, since the entire switchgear needs to be evaluated.
10.2.7 Inscriptions
Meets the product standard's requirements.
10.3 Degree of protection of assemblies
Does not apply, since the entire switchgear needs to be evaluated.
10.4 Clearances and creepage distances
Meets the product standard's requirements.
10.5 Protection against electric shock
Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and components
Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections
Is the panel builder's responsibility.
10.8 Connections for external conductors
Is the panel builder's responsibility.
10.9.2 Power-frequency electric strength
Is the panel builder's responsibility.
10.9.3 Impulse withstand voltage
Is the panel builder's responsibility.
10.9.4 Testing of enclosures made of insulating material
Is the panel builder's responsibility.

Design verification as per IEC/EN 61439 - technical data

Ambient operating temperature - max
70 °C
Ambient storage temperature - max
70 °C
Ambient operating temperature - min
-25 °C
Ambient storage temperature - min
40 °C
Equipment heat dissipation, current-dependent
6.68 W
Rated operational current for specified heat dissipation (In)
90 A

Technical Data - Electrical

Amperage Rating
90 A
Direction of incoming supply
As required
Electrical connection type of main circuit
Screw connection
Handle type
Rocker lever
Instantaneous current setting (Ii) - max
1620 A
Instantaneous current setting (Ii) - min
180 A
Overload current setting (Ir) - max
90 A
Overload current setting (Ir) - min
36 A
Rated insulation voltage (Ui)
690 V
Rated operating power at AC-3, 230 V
22 kW
Rated operating power at AC-3, 400 V
45 kW
Rated operating voltage Ue (UL) - max
480 V
Rated short-circuit breaking capacity Ics (IEC/EN 60947) at 400/415 V, 50/60 Hz
150 kA
Rated short-circuit breaking capacity Ics (IEC/EN 60947) at 440 V, 50/60 Hz
150 kA
Short-circuit release non-delayed setting - max
1260 A
Short-circuit release non-delayed setting - min
180 A
Voltage rating
690 V - 690 V

Technical Data - Mechanical

Degree of protection
IP20
Mounting Method
Fixed
Built-in device fixed built-in technique
Special features
  • Rated current = rated uninterrupted current: 90 A
  • Switches conform to UL/CSA as well as the IEC regulations. IEC switching performance values are contained on the rating plate.
Switch off technique
Electronic

Exportar as especificações do produto

Serial Number Verified :
Authenticated:
The product is verified as being authentic; however, this does not guarantee the condition or fit for purpose of the product.

Autenticar produto

Introduza o seu número de série de 16–17 dígitos
O número de série que introduziu não deve conter caracteres especiais. O número de série que introduziu está incorreto; deve ter 16 ou 17 dígitos. O número de série que introduziu não foi encontrado. Tente novamente ou comunicar este problema para obter assistência adicional. O número de série que introduziu não corresponde ao produto. Verifique o número de série do seu produto e tente novamente. Clique aqui para navegar até à página do produto correspondente ao número de série que introduziu O número de série é considerado SUSPEITO pela Eaton, tente novamente ou comunicar este problema para obter assistência adicional.
Número de série
Reset O número de série é considerado SUSPEITO pela Eaton, tente novamente ou comunicar este problema para obter assistência adicional. O número de série não é reconhecido pela Eaton e é inválido. Utilize este formulário para comunicar este problema para obter assistência adicional.
Introduza o código de autenticação de 6 dígitos
O produto que introduziu é suspeito! Tente novamente ou comunicar este problema para obter assistência adicional. O código de autenticação que introduziu não corresponde aos nossos registos para este número de série. Tente novamente ou comunicar este problema para obter assistência adicional. Código de autenticação inválido. O comprimento deve ser de 6 caracteres comunicar este problema para obter assistência adicional. O código de autenticação é obrigatório comunicar este problema para obter assistência adicional.
Conclua o desafio Captcha antes de autenticar.
Contacte-nos para comunicar problema
x
Comunicar um problema
Introduza o seu nome completo.
x
Obrigado, o seu problema foi submetido. A nossa equipa de produto entrará em contacto consigo em breve.
Nota: Se existirem ficheiro(s) em falta na pasta .zip transferida, significa que o tipo de ficheiro não é compatível com a transferência de vários ficheiros em simultâneo.