Reset

Eaton Moeller® series EASY Control relays easyE4 with display (expandable, Ethernet), 12/24 V DC, 24 V AC, Inputs Digital: 8, of which can be used as analog: 4, screw terminal
Product Name |
Eaton Moeller® series EASY Control relay
|
Catalog Number |
197211
|
EAN |
4015081939480
|
Model Code |
EASY-E4-UC-12RC1
|
Product Length/Depth |
58 mm
|
Product Height |
90 mm
|
Product Width |
72 mm
|
Product Weight |
0.25 kg
|
Compliances |
Eaton supports the product until its end of life
|
Certifications |
IEC 60068-2-30
IEC 60068-2-6 IEC/EN 61000-4-2 CSA-C22.2 No. 61010 CULus per UL 61010 EN 61010 IEC/EN 61000-6-3 IEC/EN 61131-2 IEC/EN 61000-6-2 EN 50178 IEC 60068-2-27 UL Listed UL Category Control No.: NRAQ, NRAQ7 UL File No.: E205091 DNV GL CE UL hazardous location class I UL hazardous location division 2 UL hazardous location group A (acetylene) UL hazardous location group B (hydrogen) UL hazardous location group C (ethylene) UL hazardous location group D (propane) UL hazardous location class I UL hazardous location division 2 UL hazardous location group A (acetylene) UL hazardous location group B (hydrogen) UL hazardous location group C (ethylene) UL hazardous location group D (propane) |
Catalog Notes |
Accuracy of the real-time clock depending on ambient air temperature - fluctuations of up to ± 5 s/day (± 0.5 h⁄year) are possible
|
Features |
Expandable
Display indication of 6 lines x 16 characters Networkable (Ethernet) |
Fitted with: |
Display
Real time clock Relay output Keypad Timer |
Indication |
LCD-display used as status indication of Digital inputs 24 V DC
LCD-display used as status indication of Digital inputs 12 V DC |
Degree of protection |
IP20
|
Display temperature - min |
0 °C
|
Display temperature - max |
55 °C
|
Display type |
Monochrome
|
Frequency counter |
Pulse shape: Square (digital inputs 24 V DC)
Cable length: ≤ 20 m (screened, Digital inputs 24 V DC) Number: 4 (I1, I2, I3, I4 - Digital inputs 24 V DC) Pulse pause ratio: 1:1 (Digital inputs 24 V DC) Counter frequency: 5 kHz (Digital inputs 24 V DC) |
Input frequency |
50/60 Hz (Digital inputs, at 24 V DC)
|
Insulation resistance |
According to EN 50178, EN 61010-2-201, UL61010-2-201, CSA-C22.2 NO. 61010-2-201
|
Lifespan, electrical |
25,000 Operations (Filament bulb load at 1000 W, 230/240 V AC)
25,000 Operations (Fluorescent lamp load 10 x 58 W at 230/240 V AC, uncompensated) 25,000 Operations (Fluorescent lamp load 10 x 58 W at 230/240 V AC, with upstream electrical device) 25,000 Operations (Filament bulb load at 500 W, 115/120 V AC) 25,000 Operations (Fluorescent lamp load 1 x 58 W at 230/240 V AC, conventional, compensated) |
Lifespan, mechanical |
10,000,000 Operations
|
Mounting method |
Screw fixing using fixing brackets ZB4-101-GF1 (accessories)
Front build in possible Rail mounting possible Top-hat rail fixing (according to IEC/EN 60715, 35 mm) Wall mounting/direct mounting |
Overvoltage category |
III
|
Pollution degree |
2
|
Product category |
Control relays easyE4
|
Protection |
Miniature circuit-breaker B16 or slow-blow 8 A fuse, Protection of an output relay
|
Protocol |
TCP/IP
MODBUS |
Rated impulse withstand voltage (Uimp) |
6 kV (contact-coil)
|
Residual ripple |
≤ 5 %
|
Resolution |
|
Software |
EASYSOFT-SWLIC/easySoft
|
Switching frequency |
10 Hz, Relay outputs
2 Hz, Resistive load/lamp load, Relay outputs 0.5 Hz, Inductive load, Relay outputs |
Type |
easyE4 base device
|
Used with |
easyE4
|
Utilization category |
B 300 Light Pilot Duty, UL/CSA Control Circuit Rating Codes AC
R 300 Light Pilot Duty, UL/CSA Control Circuit Rating Codes DC |
Voltage type |
AC/DC
|
Drop and topple |
50 mm Drop height, Drop to IEC/EN 60068-2-31
|
Height of fall (IEC/EN 60068-2-32) - max |
0.3 m
|
Mounting position |
Vertical
Horizontal |
Shock resistance |
15 g, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 11 ms, 18 Impacts
|
Vibration resistance |
10 - 57 Hz, 0.15 mm constant amplitude
According to IEC/EN 60068-2-6 57 - 150 Hz, 2 g constant acceleration |
Air pressure |
795 - 1080 hPa (operation)
|
Ambient operating temperature - min |
-25 °C
|
Ambient operating temperature - max |
55 °C
|
Ambient storage temperature - min |
-40 °C
|
Ambient storage temperature - max |
70 °C
|
Environmental conditions |
Clearance in air and creepage distances according to EN 50178, EN 61010-2-201, UL61010-2-201, CSA-C22.2 NO. 61010-2-201
Condensation: prevent with appropriate measures |
Relative humidity |
5 - 95 % (IEC 60068-2-30, IEC 60068-2-78)
|
Air discharge |
8 kV
|
Burst impulse |
2 kV, Supply cable
2 kV, Signal cable According to IEC/EN 61000-4-4 |
Contact discharge |
6 kV
|
Electromagnetic fields |
10 V/m at 0.8 - 1.0 GHz (according to IEC EN 61000-4-3)
1 V/m at 2.0 - 2.7 GHz (according to IEC EN 61000-4-3) 3 V/m at 1.4 - 2 GHz (according to IEC EN 61000-4-3) |
Immunity to line-conducted interference |
10 V (according to IEC/EN 61000-4-6)
|
Radio interference class |
Class B (EN 61000-6-3)
|
Surge rating |
1 kV, Supply cables, symmetrical, power pulses (Surge), EMC
According to IEC/EN 61000-4-5, power pulses (Surge), EMC 2 kV, Supply cables, asymmetrical, power pulses (Surge), EMC |
Voltage dips |
≤ 1 ms from rated voltage (12 V DC)
10 ms |
Terminal capacity |
0.2 - 4 mm² (AWG 22 - 12), solid
0.2 - 2.5 mm² (22 - 12 AWG), flexible with ferrule |
Screwdriver size |
3.5 x 0.8 mm, Terminal screw
|
Tightening torque |
0.6 Nm, Screw terminals
|
Conventional thermal current Ith of auxiliary contacts (1-pole, open) |
8 A
|
Power consumption |
3 W
|
Rated breaking capacity |
300000 Operations at AC-15, 250 V AC, 3 A (600 Ops./h)
200000 Operations at DC-13, 24 V DC, 1 A (500 Ops./h) |
Rated insulation voltage (Ui) |
240 V
|
Rated operational voltage |
Max. 300 V DC
12 V DC (digital inputs) Max. 300 V AC 240 V AC 24 V AC (-15 %/+10 % - power supply) 24 V DC (digital inputs) 12/24 V DC (-15 %/+ 20 % - power supply) 10.2 - 28.8 V DC 24 V AC (digital inputs) 20.4 - 26.4 V AC |
Supply frequency |
50/60 Hz (± 5%)
|
Supply voltage at AC, 50 Hz - min |
20.4 VAC
|
Supply voltage at AC, 50 Hz - max |
26.4 VAC
|
Supply voltage at DC - min |
10.2 VDC
|
Supply voltage at DC - max |
28.8 VDC
|
Uninterrupted current |
1 A DC, at R 300 (UL/CSA)
8 A DC, at 24 V DC (UL/CSA) 5 A AC, max. thermal continuous current cos ϕ = 1 at B 300 (UL/CSA) 10 A AC, at 240 V AC (UL/CSA) |
Short-circuit protection |
≥ 1A (T), Fuse, Power supply
|
Connection type |
Screw terminal
Ethernet: RJ45 plug, 8-pole |
Data transfer rate |
10/100 MBit/s
|
Cable length |
100 m, unscreened, Digital inputs 24 V DC
100 m, unscreened, Digital inputs 24 V AC ≤ 30 m, screened, Analog inputs 100 m, unscreened, Digital inputs 12 V DC 40 m (max. per input), Digital inputs 24 V DC |
Cable type |
CAT5
|
Accuracy |
± 2 s/day, Real-time clock to inputs (± 0.2 h⁄Year)
± 2 %, (I7, I8) ± 0.12 V, of actual value, within a single device (Analog Inputs) ± 1 %, Repetition accuracy of timing relays (of values) ± 3 %, of actual value, two easy devices (Analog Inputs) |
Conversions |
Each CPU cycle, Analog inputs
|
Delay time |
0.015 ms typ., Digital inputs 12 V DC (I1 - I8), Delay time from 1 to 0, Debounce OFF
0.015 ms typ., Digital inputs 24 V DC (I1 - I8), Delay time from 1 to 0, Debounce OFF 0.015 ms typ., Digital inputs 24 V DC (I1 - I8), Delay time from 0 to 1, Debounce OFF 20 ms typ., Digital inputs 12 V DC (I1 - I8), Delay time from 1 to 0, Debounce ON 20 ms typ., Digital inputs 12 V DC (I1 - I8), Delay time from 0 to 1, Debounce ON 20 ms typ., Digital inputs 24 V DC (I1 - I8), Delay time from 0 to 1, Debounce ON 20 ms typ., Digital inputs 24 V DC (I1 - I8), Delay time from 1 to 0, Debounce ON 0.015 ms typ., Digital inputs 12 V DC (I1 - I8), Delay time from 0 to 1, Debounce OFF |
Incremental counter |
Number of counter inputs: 2 (I1 + I2, I3 + I4)
Value range: -2147483648 to +2147483647 Pulse shape: Square Pulse pause ratio: 1:1 Signal offset: 90° Counter frequency: ≤ 5 kHz |
Incremental encoder |
Cable length: ≤ 20 m (screened)
|
Input |
Voltage (DC)
|
Input current |
3.3 mA (I1 - I4, at 24 V DC, at signal 1)
2.2 mA (I5 - I8, at 24 V DC, at signal 1) 1 mA (Analog inputs) 200 mA |
Input impedance |
13.3 kΩ
|
Input voltage |
At signal 1: ≥ 15 V (I1 - I8, sinusoidal, Digital inputs, 24 V DC)
Status 0: ≤ 8 V DC (I5 - I8, Digital inputs, 24 V DC) Status 1: ≥ 8 V DC (I5 - I8, Digital inputs, 24 V DC) Signal 0: ≤ 5 V DC (I1 - I4, Digital inputs, 12 V DC) Status 0: ≤ 15 V DC (I1 - I4, Digital inputs, 24 V DC) At signal 0: ≤ 5 V (I1 - I8, sinusoidal, Digital inputs, 24 V DC) Status 1: ≥ 15 V DC (I1 - I4, Digital inputs, 24 V DC) |
Making/breaking capacity |
28/28 VA (DC, at R 300)
3600/360 VA (AC, at B 300) |
Number of inputs (analog) |
0
4 |
Number of inputs (digital) |
4
8 |
Number of outputs (analog) |
0
|
Number of outputs (digital) |
4
|
Output |
4 Relay Outputs
> 500 mA (Relay outputs, Recommended for load: 12 V AC/DC) Relay outputs in groups of 1 Voltage Current |
Parallel switching |
Not permitted
|
Rapid counter inputs |
10 kHz, Counter frequency
-2147483648 - 2147483647 (value range) ≤ 20 m (cable length, screened) 1:1 (Pulse pause ratio) Square (pulse shape) Number: 4 (I1, I2, I3, I4 - Digital inputs 24 V DC) |
Signal range |
0 - 10 V DC, Analog inputs
|
Explosion safety category for gas |
None
|
Potential isolation |
Between Digital inputs 12 V DC and Outputs: yes
Between Analog inputs and Outputs: yes Between Digital inputs 12 V DC and expansion devices: yes Between Digital inputs 24 V DC and Outputs: yes Between Relay outputs and expansion devices: yes Between Digital inputs 24 V AC and Outputs: yes Between Relay outputs and Power supply: yes Between Digital inputs 24 V DC and expansion devices: yes Between Digital inputs 24 V DC and Ethernet: yes Basic isolation: 600 V AC (Relay outputs) Between Analog inputs and expansion devices: yes Between Relay outputs: yes Between Relay outputs and Inputs: yes Between Digital inputs 12 V DC and Ethernet: yes Between Relay outputs and Ethernet: yes Safe isolation according to EN 50178: 300 V AC (Relay outputs) Between Digital inputs 24 V AC and expansion devices: yes Between Digital inputs 24 V AC and Ethernet: yes |
Protection against polarity reversal |
Yes, for supply voltage (Siemens MPI optional)
|
Explosion safety category for dust |
None
|
Safe isolation |
300 V AC, Between coil and contact, According to EN 50178
300 V AC, Between two contacts, According to EN 50178 |
Equipment heat dissipation, current-dependent Pvid |
4 W
|
Heat dissipation capacity Pdiss |
0 W
|
Heat dissipation per pole, current-dependent Pvid |
0 W
|
Rated operational current for specified heat dissipation (In) |
0 A
|
Static heat dissipation, non-current-dependent Pvs |
3 W
|
10.2.2 Corrosion resistance |
Meets the product standard's requirements.
|
10.2.3.1 Verification of thermal stability of enclosures |
Meets the product standard's requirements.
|
10.2.3.2 Verification of resistance of insulating materials to normal heat |
Meets the product standard's requirements.
|
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects |
Meets the product standard's requirements.
|
10.2.4 Resistance to ultra-violet (UV) radiation |
Meets the product standard's requirements.
|
10.2.5 Lifting |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.2.6 Mechanical impact |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.2.7 Inscriptions |
Meets the product standard's requirements.
|
10.3 Degree of protection of assemblies |
Meets the product standard's requirements.
|
10.4 Clearances and creepage distances |
Meets the product standard's requirements.
|
10.5 Protection against electric shock |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.6 Incorporation of switching devices and components |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.7 Internal electrical circuits and connections |
Is the panel builder's responsibility.
|
10.8 Connections for external conductors |
Is the panel builder's responsibility.
|
10.9.2 Power-frequency electric strength |
Is the panel builder's responsibility.
|
10.9.3 Impulse withstand voltage |
Is the panel builder's responsibility.
|
10.9.4 Testing of enclosures made of insulating material |
Is the panel builder's responsibility.
|
10.10 Temperature rise |
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
|
10.11 Short-circuit rating |
Is the panel builder's responsibility.
|
10.12 Electromagnetic compatibility |
Is the panel builder's responsibility.
|
10.13 Mechanical function |
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
|