Eaton DC1 Variable frequency drive, 230 V AC, 1-phase, 4.3 A, 0.37 kW, IP20/NEMA 0, FS1 DC1-S24D3NN-A20CE1
Product Name |
Eaton DC1 Variable frequency drive
|
Catalog Number |
186079
|
EAN |
4015081815807
|
Product Length/Depth |
124 mm
|
Product Height |
184 mm
|
Product Width |
81 mm
|
Product Weight |
1.2 kg
|
Certifications |
CSA-C22.2 No. 14
IEC/EN 61800-3 UL 508C Specification for general requirements: IEC/EN 61800-2 EAC IEC/EN61800-3 UL Category Control No.: NMMS, NMMS7 IEC/EN61800-5 Safety requirements: IEC/EN 61800-5-1 UkrSEPRO CE RCM RoHS, ISO 9001 UL File No.: E172143 Certified by UL for use in Canada UL UL report applies to both US and Canada CUL |
Catalog Notes |
Environmental class: 3C2, 3S2
|
Model Code |
DC1-S24D3NN-A20CE1
|
Features |
Parameterization: drivesConnect
Parameterization: drivesConnect mobile (App) Parameterization: Fieldbus Parameterization: Keypad |
Fitted with: |
7-digital display assembly
Internal DC link PC connection IGBT inverter Control unit Additional PCB protection |
Cable length |
100 m, screened, with motor choke, maximum permissible, Motor feeder
75 m, unscreened, maximum permissible, Motor feeder 50 m, screened, maximum permissible, Motor feeder 150 m, unscreened, with motor choke, maximum permissible, Motor feeder |
Communication interface |
SmartWire-DT, optional
Modbus RTU, built in CANopen®, built in OP-Bus (RS485), built in |
Connection to SmartWire-DT |
In conjunction with DX-NET-SWD3 SmartWire DT module
Yes |
Degree of protection |
IP20
NEMA 0 |
Frame size |
FS1
|
Mounting position |
Vertical
|
Product category |
Variable frequency drives
|
Protection |
Finger and back-of-hand proof, Protection against direct contact (BGV A3, VBG4)
|
Protocol |
MODBUS
Other bus systems EtherNet/IP CAN |
Radio interference class |
Optional external radio interference suppression filter for longer motor cable lengths and for use in different EMC environments
|
Suitable for |
Branch circuits, (UL/CSA)
|
Altitude |
Max. 4000 m
Above 1000 m with 1 % derating per 100 m |
Ambient operating temperature - min |
-10 °C
|
Ambient operating temperature - max |
50 °C
|
Ambient operating temperature at 150% overload - min |
-10 °C
|
Ambient operating temperature at 150% overload - max |
50 °C
|
Ambient storage temperature - min |
-40 °C
|
Ambient storage temperature - max |
60 °C
|
Climatic proofing |
< 95 average relative humidity (RH), no condensation, no corrosion
|
Efficiency |
95 % (η)
|
Input current ILN at 150% overload |
7.5 A
|
Leakage current at ground IPE - max |
< 1 mA
|
Mains switch-on frequency |
Maximum of one time every 30 seconds
|
Mains voltage - min |
200 V
|
Mains voltage - max |
240 V
|
Operating mode |
Speed control with slip compensation
U/f control BLDC motors PM motors Sensorless vector control (SLV) Synchronous reluctance motors |
Output frequency - min |
0 Hz
|
Output frequency - max |
500 Hz
|
Output voltage (U2) |
240 V AC, single-phase
230 V AC, single-phase |
Overload current IL at 150% overload |
6.45 A
|
Rated control supply voltage |
10 V DC (Us, max. 10 mA)
|
Rated frequency - min |
48 Hz
|
Rated frequency - max |
62 Hz
|
Rated operational current (Ie) |
4.3 A at 150% overload (at an operating frequency of 16 kHz and an ambient air temperature of +50 °C)
|
Rated operational voltage |
230 V AC, 1-phase
240 V AC, 1-phase |
Resolution |
0.1 Hz (Frequency resolution, setpoint value)
|
Short-circuit protection rating |
10 A, UL (Class CC or J), Safety device (fuse or miniature circuit-breaker), Power Wiring
|
Starting current - max |
175 %, IH, max. starting current (High Overload), For 2.5 seconds every 600 seconds, Power section
|
Supply frequency |
50/60 Hz
|
Switching frequency |
8 kHz, 4 - 32 kHz adjustable (audible), fPWM, Power section, Main circuit
|
System configuration type |
AC supply systems with earthed center point
|
Voltage rating - max |
240 V
|
Assigned motor current IM at 220 - 240 V, 60 Hz, 150% overload |
4.3 A
|
Assigned motor current IM at 230 V, 50 Hz, 150% overload |
4.3 A
|
Assigned motor power at 230/240 V, 60 Hz, 1-phase |
0.5 HP
|
Apparent power at 230 V |
0.99 kVA
|
Apparent power at 240 V |
1.03 kVA
|
Braking torque |
Max. 100 % of rated operational current Ie, variable, DC - Main circuit
|
Number of inputs (analog) |
2
|
Number of inputs (digital) |
4
|
Number of outputs (analog) |
1
|
Number of outputs (digital) |
1
|
Number of relay outputs |
1 (parameterizable, N/O, 6 A (250 V, AC-1) / 5 A (30 V, DC-1))
|
Equipment heat dissipation, current-dependent Pvid |
18.5 W
|
Heat dissipation capacity Pdiss |
0 W
|
Heat dissipation per pole, current-dependent Pvid |
0 W
|
Rated operational current for specified heat dissipation (In) |
2.3 A
|
Static heat dissipation, non-current-dependent Pvs |
0 W
|
10.2.2 Corrosion resistance |
Meets the product standard's requirements.
|
10.2.3.1 Verification of thermal stability of enclosures |
Meets the product standard's requirements.
|
10.2.3.2 Verification of resistance of insulating materials to normal heat |
Meets the product standard's requirements.
|
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects |
Meets the product standard's requirements.
|
10.2.4 Resistance to ultra-violet (UV) radiation |
Meets the product standard's requirements.
|
10.2.5 Lifting |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.2.6 Mechanical impact |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.2.7 Inscriptions |
Meets the product standard's requirements.
|
10.3 Degree of protection of assemblies |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.4 Clearances and creepage distances |
Meets the product standard's requirements.
|
10.5 Protection against electric shock |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.6 Incorporation of switching devices and components |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.7 Internal electrical circuits and connections |
Is the panel builder's responsibility.
|
10.8 Connections for external conductors |
Is the panel builder's responsibility.
|
10.9.2 Power-frequency electric strength |
Is the panel builder's responsibility.
|
10.9.3 Impulse withstand voltage |
Is the panel builder's responsibility.
|
10.9.4 Testing of enclosures made of insulating material |
Is the panel builder's responsibility.
|
10.10 Temperature rise |
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
|
10.11 Short-circuit rating |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
10.12 Electromagnetic compatibility |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
10.13 Mechanical function |
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
|