Eaton XN Analog output module XI/ON, 24 V DC, 1AO (0/4 to 20mA)
| Product Name |
Eaton XN Output module
|
| Catalog Number |
140065
|
| EAN |
7640130120051
|
| Product Length/Depth |
55.4 mm
|
| Product Height |
74.1 mm
|
| Product Width |
12.6 mm
|
| Product Weight |
0.032 kg
|
| Certifications |
UL Category Control No.: NRAQ, NRAQ7
UL report applies to both US and Canada CE CSA Class No.: 2252-01, 2252-81 cULus IEC/EN 61131-2 UL File No.: E205091 IEC/EN 61000-6-4 Certified by UL for use in Canada UL 508 CSA-C22.2 No. 142 IEC/EN 61000-6-2 IEC/EN 6113-2 UL Recognized |
| Model Code |
XN-1AO-I(0/4...20MA)
|
| Electric connection type |
Screw-/spring clamp connection
|
| Features |
Fieldbus connection over separate bus coupler possible
Analog outputs configurable Output, current |
| Current consumption |
50 mA, from supply terminal
39 mA, from module bus, Analog input modules |
| Degree of protection |
IP20
NEMA 1 |
| Mounting method |
Rail mounting possible
|
| Number of channels |
1
|
| Product category |
XN Slice module
|
| Repetition accuracy |
0.09 % (deviation)
|
| Residual ripple |
0.02 %
|
| Type |
XI/ON I/O module
|
| Used with |
XN-S3T-SBB
XN-S3S-SBB |
| Voltage type |
DC
|
| Drop and topple |
According to IEC 60068-2-31, free fall according to IEC 60068-2-32
|
| Shock resistance |
Mechanical, According to IEC/EN 60068-2-27
Continuous according to IEC/EN 60068-2-29 |
| Vibration resistance |
According to IEC/EN 60068-2-6
|
| Ambient operating temperature - min |
0 °C
|
| Ambient operating temperature - max |
55 °C
|
| Ambient storage temperature - min |
-25 °C
|
| Ambient storage temperature - max |
85 °C
|
| Environmental conditions |
Harmful gasses - SO2: 10 ppm (relative humidity < 75%, no condensation)
Harmful gasses - H2S: 1 ppm (relative humidity < 75%, no condensation) |
| Relative humidity |
5 - 95 % (indoor, Level RH-2, non-condensing for storage at 45°C)
|
| Air discharge |
According to EN 61100-4-2
|
| Burst impulse |
According to IEC/EN 61000-4-4
|
| Contact discharge |
According to EN 61100-4-2
|
| Electromagnetic fields |
According to IEC EN 61100-4-2
|
| Emitted interference |
30 - 230 MHz (radiated, high frequency, according to EN 55016-2-3)
230 - 1000 MHz (radiated, high frequency, according to EN 55016-2-3) |
| Radiated RFI |
IEC/EN 61100-4-6
|
| Surge rating |
According to IEC/EN 61000-4-5 Level 4
|
| Voltage dips |
According to EN 61131-2 (Voltage fluctuations/voltage dips)
|
| Power loss |
1 W
|
| Rated operational voltage |
24 V DC (supply terminal)
|
| Supply voltage at AC, 50 Hz - min |
0 VAC
|
| Supply voltage at AC, 50 Hz - max |
0 VAC
|
| Supply voltage at DC - min |
20.4 VDC
|
| Supply voltage at DC - max |
28.8 VDC
|
| Number of bytes |
3 parameter bytes
|
| Protocol |
Other bus systems
|
| Frequency |
200 Hz (Transfer)
|
| Linearity |
0.02 %
|
| Load resistance |
< 0.001 h (inductive load)
< 450 Ω |
| Measured value representation |
12-bit full range left-justified
16-bit signed integer |
| Measured variables |
Current
|
| Number of inputs (analog) |
0
|
| Number of outputs (analog) |
1
|
| Output |
1 Analog Output
|
| Output current |
0/4 - 20 mA
|
| Settling time |
0.5 ms, Capacitive load, Analog output modules
0.1 ms, Resistive load, Analog output modules 0.5 ms, Inductive load, Analog output modules |
| Timing cycle |
0.1 % Offset error
|
| Explosion safety category for dust |
None
|
| Explosion safety category for gas |
None
|
| Potential isolation |
Through optocoupler: yes
|
| Equipment heat dissipation, current-dependent Pvid |
1 W
|
| Heat dissipation capacity Pdiss |
0 W
|
| Heat dissipation per pole, current-dependent Pvid |
0 W
|
| Rated operational current for specified heat dissipation (In) |
0 A
|
| Static heat dissipation, non-current-dependent Pvs |
1 W
|
| 10.2.2 Corrosion resistance |
Meets the product standard's requirements.
|
| 10.2.3.1 Verification of thermal stability of enclosures |
Meets the product standard's requirements.
|
| 10.2.3.2 Verification of resistance of insulating materials to normal heat |
Meets the product standard's requirements.
|
| 10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects |
Meets the product standard's requirements.
|
| 10.2.4 Resistance to ultra-violet (UV) radiation |
Meets the product standard's requirements.
|
| 10.2.5 Lifting |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.2.6 Mechanical impact |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.2.7 Inscriptions |
Meets the product standard's requirements.
|
| 10.3 Degree of protection of assemblies |
Meets the product standard's requirements.
|
| 10.4 Clearances and creepage distances |
Meets the product standard's requirements.
|
| 10.5 Protection against electric shock |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.6 Incorporation of switching devices and components |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.7 Internal electrical circuits and connections |
Is the panel builder's responsibility.
|
| 10.8 Connections for external conductors |
Is the panel builder's responsibility.
|
| 10.9.2 Power-frequency electric strength |
Is the panel builder's responsibility.
|
| 10.9.3 Impulse withstand voltage |
Is the panel builder's responsibility.
|
| 10.9.4 Testing of enclosures made of insulating material |
Is the panel builder's responsibility.
|
| 10.10 Temperature rise |
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
|
| 10.11 Short-circuit rating |
Is the panel builder's responsibility.
|
| 10.12 Electromagnetic compatibility |
Is the panel builder's responsibility.
|
| 10.13 Mechanical function |
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
|