Foto is representatief
Download
Eaton DM1 Variable frequency drive, 400 V AC, 3-phase, 23 A, 11 kW, IP20/NEMA0, 7-digital display assembly, Setpoint potentiometer, Brake chopper, FS3
Product Name |
Eaton DM1 Variable frequency drive
|
Catalog Number |
3-5014-002A
|
EAN |
4015081980956
|
Product Length/Depth |
180 mm
|
Product Height |
260 mm
|
Product Width |
130 mm
|
Product Weight |
3.7 kg
|
Certifications |
C-Tick
IEC/EN 61800-5-1 CSA-C22.2 No. 274-17 UL report applies to both US and Canada CUL CE RoHS, ISO 9001 CE marking IEC/EN 61800-2 Certified by UL for use in Canada CSA-C22.2 No. 274-13 UL File No.: E134360 UL Listed UkrSEPRO IEC/EN61800-3 IEC/EN61800-5 EAC UL Category Control No.: NMMS, NMMS7 IEC/EN 61800-3 UL 508C UL |
Model Code |
DM1-34023NB-S20S-EM
|
Air volume capacity |
100 m³/h
|
Communication interface |
BACnet TCP
PROFIBUS, optional BACnet MS/TP, built in Ethernet IP, built in CANopen®, optional Modbus RTU, built in SmartWire-DT, optional Modbus TCP, built in DeviceNet, optional |
Connection to SmartWire-DT |
Yes
In conjunction with DXG-NET-SWD SmartWire DT module |
Degree of protection |
IP20
NEMA Other |
Electromagnetic compatibility |
1st and 2nd environments (according to EN 61800-3)
|
Environmental class |
3C2, 3S2 (Air quality)
|
Features |
Temperature-controlled fan
Parameterization: Fieldbus Parameterization: Keypad Parameterization: Power Xpert inControl |
Fitted with: |
Setpoint potentiometer
7-digital display assembly Brake chopper Internal DC link IGBT inverter Control unit PC connection |
Frame size |
FS3
|
Mounting position |
Vertical
|
Number of slots |
1 (expansion)
|
Overvoltage category |
III
|
Pollution degree |
2
|
Product Category |
Variable frequency drives
|
Protection |
Finger and back-of-hand proof, Protection against direct contact (BGV A3, VBG4)
|
Radio interference class |
C2, C3: depending on the motor cable length, the connected load, and ambient conditions. External radio interference suppression filters (optional) may be necessary.
Optional external radio interference suppression filter for longer motor cable lengths and for use in different EMC environments C1: with external filter |
Safety function/level |
STO (Safe Torque Off, SIL2, PLc Cat 2)
|
Shock resistance |
0.75 mm (peak) at 10 - 57 Hz, max. 1 g at 57 - 150 Hz, according to EN 61800-5-1, EN 60068-2-6: 10 - 150 Hz
|
Suitable for |
Branch circuits, (UL/CSA)
|
Altitude |
Max. 3000 m
Max. 2000 m for Corner Grounded TN Systems Max. 1000 m Above 1000 m with 1 % derating per 100 m |
Ambient operating temperature - min |
-10 °C
|
Ambient operating temperature - max |
50 °C
|
Ambient storage temperature - min |
-40 °C
|
Climatic proofing |
< 95 average relative humidity (RH), no condensation, no corrosion
|
Current limitation |
0.1 - 2 x IH (CT), motor, main circuit
|
Input current ILN at 110% overload |
35.7 A
|
Input current ILN at 150% overload |
26.5 A
|
Mains current distortion |
40 %
|
Mains switch-on frequency |
Maximum of one time every 60 seconds
|
Mains voltage - min |
380 V
|
Mains voltage - max |
500 V
|
Operating mode |
Sensorless vector control (SLV)
Torque regulation U/f control Speed control with slip compensation PM motors |
Output frequency - min |
0 Hz
|
Output frequency - max |
400 Hz
|
Output voltage (U2) |
500 V AC, 3-phase
400 V AC, 3-phase 480 V AC, 3-phase |
Overload current IL at 110% overload |
34.1 A
|
Overload current IL at 150% overload |
34.5 A
|
Rated conditional short-circuit current (Iq) |
100 kA
|
Rated control supply voltage |
10 V DC (Us, max. 10 mA)
|
Rated frequency - min |
45 Hz
|
Rated frequency - max |
66 Hz
|
Rated operational current (Ie) at 110% overload |
31 A
|
Rated operational current (Ie) at 150% overload |
23 A
|
Rated operational power at 380/400 V, 50 Hz, 110% overload |
15 kW
|
Rated operational power at 380/400 V, 50 Hz, 3-phase |
11 kW
|
Rated operational power at 500 V, 50 Hz, 3-phase |
11 kW
|
Rated operational power at 500 V, 50 Hz, 3-phase, 110% overload |
18.5 kW
|
Rated operational voltage |
500 V AC, 3-phase
400 V AC, 3-phase 480 V AC, 3-phase |
Resolution |
0.01 Hz (Frequency resolution, setpoint value)
|
Short-circuit protection rating |
40 A, UL (Class CC or J), Safety device (fuse or miniature circuit-breaker), Power Wiring
|
Starting current - max |
200 %, IH, max. starting current (High Overload), For 2 seconds every 20 seconds, Power section
|
Supply frequency |
50/60 Hz
|
Switching frequency |
4 kHz, 1 - 16 kHz adjustable, fPWM, Power section, Main circuit
|
System configuration type |
TN-S, TN-C, TN-C-S, TT, IT
|
Voltage rating - max |
500 V
|
Assigned motor current IM at 400 V, 50 Hz, 110% overload |
29.3 A
|
Assigned motor current IM at 400 V, 50 Hz, 150% overload |
21.7 A
|
Assigned motor current IM at 440 - 480 V, 60 Hz, 150% overload |
21 A
|
Assigned motor current IM at 440/480 V, 60 Hz, 110% overload |
27 A
|
Assigned motor current IM at 500 V, 50 Hz, 110% overload |
28.9 A
|
Assigned motor current IM at 500 V, 50 Hz, 150% overload |
17.4 A
|
Assigned motor power at 460/480 V, 60 Hz |
15 HP
|
Assigned motor power at 460/480 V, 60 Hz, 110% overload |
20 HP
|
Braking resistance |
26 Ω
|
Braking torque |
Max. 100 % of rated operational current Ie with external braking resistor - Main circuit
Adjustable to 150 %, DC - Main circuit Max. 30 % MN, Standard - Main circuit |
Switch-on threshold for the braking transistor |
800 VDC
|
Number of inputs (analog) |
1
|
Number of inputs (digital) |
4
|
Number of outputs (analog) |
1
|
Number of relay outputs |
2 (parameterizable, 1 changeover contact and 1 N/O, 3 A (240 V AC) / 3 A (24 V DC))
|
Rated control voltage (Uc) |
24 V DC (external, max. 100 mA options incl.)
|
Equipment heat dissipation, current-dependent Pvid |
407.4 W
|
Rated operational current for specified heat dissipation (In) |
31 A
|
10.2.2 Corrosion resistance |
Meets the product standard's requirements.
|
10.2.3.1 Verification of thermal stability of enclosures |
Meets the product standard's requirements.
|
10.2.3.2 Verification of resistance of insulating materials to normal heat |
Meets the product standard's requirements.
|
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects |
Meets the product standard's requirements.
|
10.2.4 Resistance to ultra-violet (UV) radiation |
Meets the product standard's requirements.
|
10.2.5 Lifting |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.2.6 Mechanical impact |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.2.7 Inscriptions |
Meets the product standard's requirements.
|
10.3 Degree of protection of assemblies |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.4 Clearances and creepage distances |
Meets the product standard's requirements.
|
10.5 Protection against electric shock |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.6 Incorporation of switching devices and components |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.7 Internal electrical circuits and connections |
Is the panel builder's responsibility.
|
10.8 Connections for external conductors |
Is the panel builder's responsibility.
|
10.9.2 Power-frequency electric strength |
Is the panel builder's responsibility.
|
10.9.3 Impulse withstand voltage |
Is the panel builder's responsibility.
|
10.9.4 Testing of enclosures made of insulating material |
Is the panel builder's responsibility.
|
10.10 Temperature rise |
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
|
10.11 Short-circuit rating |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
10.12 Electromagnetic compatibility |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
10.13 Mechanical function |
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
|