Foto is representatief
Download
Eaton DM1 Variable frequency drive, 115 V AC, single-phase, 3 A, 0.37 kW, IP20/NEMA0, 7-digital display assembly, Setpoint potentiometer, Brake chopper, FS1
| Product Name |
Eaton DM1 Variable frequency drive
|
| Catalog Number |
3-5042-004A
|
| EAN |
4015081980512
|
| Product Length/Depth |
180 mm
|
| Product Height |
152 mm
|
| Product Width |
72 mm
|
| Product Weight |
1.2 kg
|
| Certifications |
EAC
CSA-C22.2 No. 274-13 CUL UL Listed IEC/EN 61800-3 IEC/EN 61800-2 UL 508C Certified by UL for use in Canada UL Category Control No.: NMMS, NMMS7 UL File No.: E134360 UL CSA-C22.2 No. 274-17 RoHS, ISO 9001 IEC/EN61800-3 IEC/EN61800-5 UkrSEPRO CE marking C-Tick CE UL report applies to both US and Canada IEC/EN 61800-5-1 |
| Model Code |
DM1-113D0NB-S20S-EM
|
| Air volume capacity |
26 m³/h
|
| Communication interface |
PROFIBUS, optional
BACnet MS/TP, built in Modbus TCP, built in DeviceNet, optional Ethernet IP, built in SmartWire-DT, optional Modbus RTU, built in BACnet TCP CANopen®, optional |
| Connection to SmartWire-DT |
In conjunction with DXG-NET-SWD SmartWire DT module
Yes |
| Degree of protection |
IP20
NEMA Other |
| Electromagnetic compatibility |
1st and 2nd environments (according to EN 61800-3)
|
| Environmental class |
3C2, 3S2 (Air quality)
|
| Features |
Parameterization: Keypad
Temperature-controlled fan Parameterization: Fieldbus Parameterization: Power Xpert inControl |
| Fitted with: |
7-digital display assembly
Internal DC link Setpoint potentiometer IGBT inverter Brake chopper Control unit PC connection |
| Frame size |
FS1
|
| Mounting position |
Vertical
|
| Number of slots |
1 (expansion)
|
| Overvoltage category |
III
|
| Pollution degree |
2
|
| Product Category |
Variable frequency drives
|
| Protection |
Finger and back-of-hand proof, Protection against direct contact (BGV A3, VBG4)
|
| Radio interference class |
Optional external radio interference suppression filter for longer motor cable lengths and for use in different EMC environments
C2, C3: depending on the motor cable length, the connected load, and ambient conditions. External radio interference suppression filters (optional) may be necessary. C1: with external filter |
| Safety function/level |
STO (Safe Torque Off, SIL2, PLc Cat 2)
|
| Shock resistance |
0.75 mm (peak) at 10 - 57 Hz, max. 1 g at 57 - 150 Hz, according to EN 61800-5-1, EN 60068-2-6: 10 - 150 Hz
|
| Suitable for |
Branch circuits, (UL/CSA)
|
| Altitude |
Max. 1000 m
Max. 2000 m for Corner Grounded TN Systems Above 1000 m with 1 % derating per 100 m Max. 3000 m |
| Ambient operating temperature - min |
-10 °C
|
| Ambient operating temperature - max |
50 °C
|
| Ambient storage temperature - min |
-40 °C
|
| Ambient storage temperature - max |
70 °C
|
| Climatic proofing |
< 95 average relative humidity (RH), no condensation, no corrosion
|
| Current limitation |
0.1 - 2 x IH (CT), motor, main circuit
|
| Heat dissipation at current/speed |
23.44 W at 25% current and 50% speed
25 W at 25% current and 0% speed 29.65 W at 100% current and 50% speed 35.39 W at 50% current and 50% speed 40.72 W at 100% current and 0% speed 41.16 W at 50% current and 90% speed 58.49 W at 50% current and 0% speed 82.71 W at 100% current and 90% speed |
| Input current ILN at 110% overload |
20 A
|
| Input current ILN at 150% overload |
12 A
|
| Mains current distortion |
40 %
|
| Mains switch-on frequency |
Maximum of one time every 60 seconds
|
| Mains voltage - min |
100 V
|
| Mains voltage - max |
120 V
|
| Operating mode |
Speed control with slip compensation
Sensorless vector control (SLV) U/f control PM motors Torque regulation |
| Output frequency - min |
0 Hz
|
| Output frequency - max |
400 Hz
|
| Output voltage (U2) |
230 V AC, 3-phase
|
| Overload current IL at 110% overload |
5.28 A
|
| Overload current IL at 150% overload |
4.5 A
|
| Rated conditional short-circuit current (Iq) |
100 kA
|
| Rated control supply voltage |
10 V DC (Us, max. 10 mA)
|
| Rated frequency - min |
45 Hz
|
| Rated frequency - max |
66 Hz
|
| Rated operational current (Ie) at 110% overload |
4.8 A
|
| Rated operational current (Ie) at 150% overload |
3 A
|
| Rated operational power at 115 V, 50 Hz, 110% overload |
0.55 kW
|
| Rated operational power at 115 V, 50 Hz, 1-phase |
0.37 kW
|
| Rated operational voltage |
115 V AC, 1-phase
|
| Resolution |
0.01 Hz (Frequency resolution, setpoint value)
|
| Short-circuit protection rating |
25 A, UL (Class CC or J), Safety device (fuse or miniature circuit-breaker), Power Wiring
|
| Starting current - max |
200 %, IH, max. starting current (High Overload), For 2 seconds every 20 seconds, Power section
|
| Supply frequency |
50/60 Hz
|
| Switching frequency |
8 kHz, 4 - 32 kHz adjustable (audible), fPWM, Power section, Main circuit
|
| System configuration type |
TN-S, TN-C, TN-C-S, TT, IT
|
| Voltage rating - max |
120 VAC
|
| Assigned motor current IM at 230 V, 50 Hz, 150% overload |
2.7 A
|
| Assigned motor current IM at 690 V, 50 Hz, 110% overload |
3.8 A
|
| Assigned motor power at 115/120 V, 60 Hz, 1-phase |
0.5 HP
|
| Assigned motor power at 115/120 V, 60 Hz, 110% overload |
1 HP
|
| Braking torque |
Adjustable to 150 %, DC - Main circuit
Max. 100 % of rated operational current Ie with external braking resistor - Main circuit Max. 30 % MN, Standard - Main circuit |
| Number of inputs (analog) |
1
|
| Number of inputs (digital) |
4
|
| Number of outputs (analog) |
1
|
| Number of relay outputs |
2 (parameterizable, 1 changeover contact and 1 N/O, 3 A (240 V AC) / 3 A (24 V DC))
|
| Rated control voltage (Uc) |
24 V DC (external, max. 100 mA options incl.)
|
| Equipment heat dissipation, current-dependent Pvid |
81.1 W
|
| Rated operational current for specified heat dissipation (In) |
4.8 A
|
| 10.2.2 Corrosion resistance |
Meets the product standard's requirements.
|
| 10.2.3.1 Verification of thermal stability of enclosures |
Meets the product standard's requirements.
|
| 10.2.3.2 Verification of resistance of insulating materials to normal heat |
Meets the product standard's requirements.
|
| 10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects |
Meets the product standard's requirements.
|
| 10.2.4 Resistance to ultra-violet (UV) radiation |
Meets the product standard's requirements.
|
| 10.2.5 Lifting |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.2.6 Mechanical impact |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.2.7 Inscriptions |
Meets the product standard's requirements.
|
| 10.3 Degree of protection of assemblies |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.4 Clearances and creepage distances |
Meets the product standard's requirements.
|
| 10.5 Protection against electric shock |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.6 Incorporation of switching devices and components |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.7 Internal electrical circuits and connections |
Is the panel builder's responsibility.
|
| 10.8 Connections for external conductors |
Is the panel builder's responsibility.
|
| 10.9.2 Power-frequency electric strength |
Is the panel builder's responsibility.
|
| 10.9.3 Impulse withstand voltage |
Is the panel builder's responsibility.
|
| 10.9.4 Testing of enclosures made of insulating material |
Is the panel builder's responsibility.
|
| 10.10 Temperature rise |
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
|
| 10.11 Short-circuit rating |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
| 10.12 Electromagnetic compatibility |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
| 10.13 Mechanical function |
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
|