Eaton Moeller series xPole - PLN6 MCB. Miniature circuit breaker (MCB), 32 A, 1p+N, characteristic: B, MW
| Product Name |
Eaton Moeller series xPole - PLN6 MCB
|
| Catalog Number |
263167
|
| EAN |
4015082631673
|
| Product Length/Depth |
80 mm
|
| Product Height |
75 mm
|
| Product Width |
17.5 mm
|
| Product Weight |
0.123 kg
|
| Compliances |
RoHS compliant
|
| Certifications |
IEC/EN 60898
|
| Used with |
PLN6
Miniature circuit breaker |
| Amperage Rating |
32 A
|
| Voltage rating |
230 V AC
|
| Features |
Can be fitted with auxiliary accessories
Neutral conductor switches concurrently with the phase conductors |
| Frame |
45 mm
|
| Pollution degree |
2
|
| Lifespan, mechanical |
>10000 operating cycles
|
| Mounting Method |
Two lock-in position on DIN rail (EN/IEC 60715)
|
| Degree of protection |
IP20 (device)
IP40 (when installed in enclosure) |
| Rated impulse withstand voltage (Uimp) |
4 kV
|
| Functional group |
Overcurrent protection
|
| Terminal protection |
Touch-safe (EN 50274)
|
| Terminals (top and bottom) |
Screw-type with pressure plate
|
| Tripping characteristic |
B
|
| Ambient operating temperature - max |
75 °C
|
| Ambient operating temperature - min |
-25 °C
|
| Built-in depth |
65.5 mm
|
| Connectable conductor cross section (multi-wired) - max |
16 mm²
|
| Connectable conductor cross section (multi-wired) - min |
1 mm²
|
| Connectable conductor cross section (solid-core) - max |
16 mm²
|
| Connectable conductor cross section (solid-core) - min |
1 mm²
|
| Current limiting class |
3
|
| Frequency rating - max |
60 Hz
|
| Frequency rating - min |
50 Hz
|
| Internal resistance at room temperature (single-pole, 50 Hz) |
3 mΩ
|
| Nominal current |
25 A
|
| Direction of incoming supply |
Bidirectional
|
| Voltage rating (IEC/EN 60898-1) |
240 VAC
|
| Width in number of modular spacings |
1
|
| Voltage type |
AC
|
| Contact position indicator color |
Red = ON
Green = OFF |
| Mounting position |
As required
|
| Overvoltage category |
III
|
| Number of poles |
Single-pole + N
|
| Functions |
Overload protection
Short Circuit protection |
| Lifespan, electrical |
>4000 operating cycles
|
| Release characteristic |
B
|
| Type |
|
| Application |
Residential and commercial applications
|
| Mounting width |
17.7 mm
|
| Selectivity class |
3
|
| Number of poles (protected) |
1
|
| Number of poles (total) |
2
|
| Rated insulation voltage (Ui) |
440 V
|
| Rated operational current for specified heat dissipation (In) |
32 A
|
| Rated operational voltage (Ue) - max |
240 VAC
|
| Rated service short-circuit breaking capacity (IEC/EN 60898-1) - Ics |
6 kA
|
| Rated short-circuit breaking capacity (IEC/EN 60898-1) - Icn at 230 V |
6 kA
|
| Rated switching capacity (IEC/EN 60898-1) |
6 kA
|
| Terminal capacity |
1 mm² - 16 mm²
|
| Terminal capacity of screw terminals for main cable |
1 mm² - 16 mm²
|
| Tightening torque |
Max. 1.2 Nm
|
| Power loss |
5.7 W
|