Dokument herunterladen () von 20
Wir setzen um, was wirklich zählt.*

263638

Eaton Moeller series xPole - PF6/7 RCCB. Residual current circuit breaker (RCCB), 40A, 4 p, 100mA, type U

Allgemeine Spezifikation

Product Name
Eaton Moeller series xPole - PF6/7 RCCB
Catalog Number
263638
Product Length/Depth
72 mm
Product Height
80 mm
Product Width
70 mm
Product Weight
0.32 kg
Compliances
RoHS conform
Certifications
IEC/EN 61008
EAN
4015082636388
Model Code
PF7-40/4/01-U-DE

Produktspezifikationen

Used with
Residual current circuit breakers
PF7
Type U
Amperage Rating
40 A
Features
Additional equipment possible
Residual current circuit breaker
Selective protection
10.10 Temperature rise
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.12 Electromagnetic compatibility
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.13 Mechanical function
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
10.2.2 Corrosion resistance
Meets the product standard's requirements.
10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard's requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard's requirements.
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects
Meets the product standard's requirements.
10.2.4 Resistance to ultra-violet (UV) radiation
Meets the product standard's requirements.
10.2.5 Lifting
Does not apply, since the entire switchgear needs to be evaluated.
10.2.6 Mechanical impact
Does not apply, since the entire switchgear needs to be evaluated.
10.2.7 Inscriptions
Meets the product standard's requirements.
10.3 Degree of protection of assemblies
Does not apply, since the entire switchgear needs to be evaluated.
10.4 Clearances and creepage distances
Meets the product standard's requirements.
10.5 Protection against electric shock
Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and components
Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections
Is the panel builder's responsibility.
10.8 Connections for external conductors
Is the panel builder's responsibility.
10.9.2 Power-frequency electric strength
Is the panel builder's responsibility.
10.9.3 Impulse withstand voltage
Is the panel builder's responsibility.
10.9.4 Testing of enclosures made of insulating material
Is the panel builder's responsibility.
Fitted with:
Interlocking device
Frequency rating
50 Hz
Pollution degree
2
Mounting Method
DIN rail
Equipment heat dissipation, current-dependent
8.4 W
Rated impulse withstand voltage (Uimp)
4 kV
Rated short-time withstand current (Icw)
10 kA
Admissible back-up fuse overload - max
25 A gG/gL
Busbar material thickness
0.8 mm - 2 mm
Short-circuit rating
63 A (max. admissible back-up fuse)
Ambient operating temperature - max
60 °C
Ambient operating temperature - min
-25 °C
Built-in depth
69.5 mm
Connectable conductor cross section (multi-wired) - max
16 mm²
Connectable conductor cross section (multi-wired) - min
1.5 mm²
Connectable conductor cross section (solid-core) - max
35 mm²
Connectable conductor cross section (solid-core) - min
1.5 mm²
Fault current rating
100 mA
Heat dissipation capacity
0 W
Heat dissipation per pole, current-dependent
0 W
Degree of protection
IP20
Impulse withstand current
Surge-proof 5 kA
Number of poles
Four-pole
Leakage current type
A
Type
  • PF7
  • Residual current circuit breakers
  • Type U
Special features
Maximum operating temperature is 60 °C: Starting at 40 °C, the max. permissible continuous current decreases by 2.5% for every 1 °C
Application
Residual current circuit breaker - frequency converter-proof
Sensitivity type
Pulse-current sensitive, suitable for variable frequency drives
Rated fault current - max
0.1 A
Rated fault current - min
0.1 A
Rated insulation voltage (Ui)
440 V
Rated operational current for specified heat dissipation (In)
40 A
Rated operational voltage (Ue) - max
400 V
Rated residual making and breaking capacity
500 A
Static heat dissipation, non-current-dependent
0 W
Surge current capacity
5 kA
Width in number of modular spacings
4
Tripping time
Selective switch off
Rated short-circuit strength
10 kA

Produktspezifikation exportieren

Serial Number Verified :
Authenticated:
The product is verified as being authentic; however, this does not guarantee the condition or fit for purpose of the product.

Produkt authentifizieren

Geben Sie Ihre 16- bis 17-stellige Seriennummer ein
Die von Ihnen eingegebene Seriennummer sollte keine Sondercharachter enthalten. Die eingegebene Seriennummer ist nicht korrekt. Sie sollte 16- oder 17-stellig sein. Die von Ihnen eingegebene Seriennummer wurde nicht gefunden. Versuchen Sie es erneut oder Problem melden für weitere Unterstützung. Die eingegebene Seriennummer stimmt nicht mit dem Produkt überein. Überprüfen Sie die Seriennummer Ihres Produkts und versuchen Sie es erneut. Klicken Sie auf hier um zur Produktseite für die eingegebene Seriennummer zu gelangen Die Seriennummer ist bei Eaton als verdächtig vermerkt, bitte versuchen Sie es erneut oder Problem melden für weitere Unterstützung.
Seriennummer
Zurücksetzen Die Seriennummer ist bei Eaton als verdächtig vermerkt, bitte versuchen Sie es erneut oder Problem melden für weitere Unterstützung. Die Seriennummer wurde von Eaton nicht erkannt und ist ungültig. Bitte verwenden Sie dieses Formular, um Problem melden für weitere Unterstützung.
Geben Sie den 6-stelligen Authentifizierungscode ein
Das von Ihnen eingegebene Produkt ist verdächtig! Versuchen Sie es erneut oder Problem melden für weitere Unterstützung. Der von Ihnen eingegebene Authentifizierungscode stimmt nicht mit unseren Datensätzen für diese Seriennummer überein. Versuchen Sie es erneut oder Problem melden für weitere Unterstützung. Ungültiger Authentifizierungscode Die Länge muss 6 Zeichen betragen Problem melden für weitere Unterstützung. Authentifizierungscode ist erforderlich Problem melden für weitere Unterstützung.
Schließen Sie die Captcha Challenge ab, bevor Sie sich authentifizieren.
Kontaktieren Sie uns zur Meldung von Problemen
Authenticate before accessing Test Reports
x
Eine Sicherheitslücke melden
Bitte geben Sie Ihren vollständigen Namen ein.
x
Vielen Dank, Ihr Anliegen wurde eingereicht. Unser Produktteam wird sich in Kürze mit Ihnen in Verbindung setzen.
Hinweis: Wenn im .zip-Download Dateien fehlen, ist der Dateityp beim Massendownload nicht unterstützt.