Vidensøgning
Download dokument () af 20
We make what matters work*

062655
Modelkode: U-CI43X

Eaton xEffect Ci Enclosures Switch- & Controlgear Enclosure. Base, smooth sides, HxWxD=250x375x120mm

General specifications

Product Name
Eaton xEffect Ci Enclosures Switch- & Controlgear Enclosure
Catalog Number
062655
EAN
4015080626558
Product Length/Depth
150 mm
Product Height
250 mm
Product Width
375 mm
Product Weight
1.692 kg
Compliances
RoHS conform
Certifications
EN 61439-2
EN 62208
Model Code
U-CI43X

Yderligere oplysninger

Features
Cover with overpressure release
Protection class
II
RAL-number
7035
Special features
Distance frame for CI45... →#110103 Flanges →#024355 Smooth sides Without knockouts
Suitable for
Outdoor use
Lightning protection

Leveringsprogram

Accessory/spare part type
Individual enclosure bottoms
Color
Gray
Nominal current
1600 A
Type
Basic enclosure Enclosure bases xEnergy Safety Ci

Designverifikation iht. IEC/EN 61439

10.10 Temperature rise
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating
Is the panel builder's responsibility.
10.12 Electromagnetic compatibility
Is the panel builder's responsibility.
10.13 Mechanical function
Meets the product standard's requirements.
10.2.2 Corrosion resistance
Meets the product standard's requirements.
10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard's requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard's requirements.
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects
960 °C
10.2.4 Resistance to ultra-violet (UV) radiation
Not relevant to indoor installations.
10.2.5 Lifting
10 kg per enclosure with support frame and lifting aid met; assembled and secured as per the latest applicable instruction leaflet.
10.2.6 Mechanical impact
IK10
10.2.7 Inscriptions
Meets the product standard's requirements.
10.3 Degree of protection of assemblies
IP65, with cover
10.4 Clearances and creepage distances
Is the panel builder's responsibility.
10.5 Protection against electric shock
Protection class 2, therefore not applicable.
10.6 Incorporation of switching devices and components
Is the panel builder's responsibility.
10.7 Internal electrical circuits and connections
Is the panel builder's responsibility.
10.8 Connections for external conductors
Is the panel builder's responsibility.
10.9.2 Power-frequency electric strength
Ui = 1000 V AC
10.9.3 Impulse withstand voltage
8 kV
10.9.4 Testing of enclosures made of insulating material
Meets the product standard's requirements.

Technical data - electrical

Circuit integrity
Other

Technical data - mechanical

Base type
Plain
Built-in depth
200 mm
Cable entry type
Top and bottom
Drill as required
Transverse
Cover/door model
Closed
Cover/door type
Optional
None
Enclosure material
Plastic
Mounting method
Surface mounted (plaster)
Number of conduit inlets
0
Number of modules
1
Number of openings (flange plates)
0
Number of rows
0
Plate thickness (cabinet)
9 mm
Plate thickness (cover/door)
6 mm
Surface protection
Other
Unit type
Modular system
Width in number of modular spacings
15
Degree of protection
IP65
IK10
Other
Internal depth
100 mm

Verifikation af temperaturstigning i henhold til IEC 60890

Heat diss. ambient 35°C delta T: 20°C wall mount middle encl. top (IEC 60890)
17 W
Heat diss. ambient 35°C delta T: 35°C wall mount middle encl. top (IEC 60890)
34 W
Heat diss. ambient 35°C delta T:20°C wall mount individ. encl. top (IEC 60890)
19 W
Heat diss. ambient 35°C delta T:20°C wall mount starting encl. top (IEC 60890)
18 W
Heat diss. ambient 35°C delta T:35°C wall mount individ. encl. top (IEC 60890)
38 W
Heat diss. ambient 35°C delta T:35°C wall mount starting encl. top (IEC 60890)
36 W