Eaton Moeller series xEffect - FAZ-NA, FAZ-RT MCB. FAZ-NA, 2-pole, tripping characteristic: C, rated current In: 7 A, Switchgear for export to North America (UL-listed)
| Product Name |
Eaton Moeller series xEffect - FAZ-NA, FAZ-RT MCB
|
| Catalog Number |
102165
|
| EAN |
4015081020416
|
| Product Length/Depth |
105 mm
|
| Product Height |
75.5 mm
|
| Product Width |
35.4 mm
|
| Product Weight |
0.243 kg
|
| Compliances |
RoHS conform
|
| Certifications |
CSA-C22.2 No. 5-09
IEC/EN 60947-2 UL 489 UL (Category Control Number DIVQ) UL (File No. E235139) Specially designed for North America, suitable as BCPD CSA (File No. 204453) North America (UL listed, CSA certified) CSA (Class No. 1432-01) IEC 60947-2 CE marking UL 489, CSA C22.2 No. 5 EN45545-2 IEC 61373 |
| Model Code |
FAZ-C7/2-NA
|
| Current limiting class |
3
|
| Features |
Additional equipment possible
|
| Functions |
Current limiting circuit breaker
|
| Special features |
Ambient temperature hint: a 1 °C increase results in a 0.5% linear reduction of current carrying capacity
|
| Used with |
FAZ-NA
Miniature circuit breaker |
| Amperage Rating |
7 A
|
| Application |
|
| Number of poles |
Two-pole
|
| Number of poles (protected) |
2
|
| Number of poles (total) |
2
|
| Release characteristic |
C
|
| Tripping characteristic |
C
|
| Type |
|
| 10.10 Temperature rise |
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
|
| 10.11 Short-circuit rating |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
| 10.12 Electromagnetic compatibility |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
| 10.13 Mechanical function |
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
|
| 10.2.2 Corrosion resistance |
Meets the product standard's requirements.
|
| 10.2.3.1 Verification of thermal stability of enclosures |
Meets the product standard's requirements.
|
| 10.2.3.2 Verification of resistance of insulating materials to normal heat |
Meets the product standard's requirements.
|
| 10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects |
Meets the product standard's requirements.
|
| 10.2.4 Resistance to ultra-violet (UV) radiation |
Meets the product standard's requirements.
|
| 10.2.5 Lifting |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.2.6 Mechanical impact |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.2.7 Inscriptions |
Meets the product standard's requirements.
|
| 10.3 Degree of protection of assemblies |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.4 Clearances and creepage distances |
Meets the product standard's requirements.
|
| 10.5 Protection against electric shock |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.6 Incorporation of switching devices and components |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.7 Internal electrical circuits and connections |
Is the panel builder's responsibility.
|
| 10.8 Connections for external conductors |
Is the panel builder's responsibility.
|
| 10.9.2 Power-frequency electric strength |
Is the panel builder's responsibility.
|
| 10.9.3 Impulse withstand voltage |
Is the panel builder's responsibility.
|
| 10.9.4 Testing of enclosures made of insulating material |
Is the panel builder's responsibility.
|
| Ambient operating temperature - max |
75 °C
|
| Ambient operating temperature - min |
-25 °C
|
| Equipment heat dissipation, current-dependent |
2.8 W
|
| Heat dissipation capacity |
0 W
|
| Heat dissipation per pole, current-dependent |
0 W
|
| Rated operational current for specified heat dissipation (In) |
7 A
|
| Static heat dissipation, non-current-dependent |
0 W
|
| Breaking capacity |
10 kA (UL489)
|
| Direction of incoming supply |
As required
|
| Frequency rating - max |
60 Hz
|
| Frequency rating - min |
50 Hz
|
| Lifespan, electrical |
20000 operations
|
| Overvoltage category |
III
|
| Pollution degree |
2
|
| Rated impulse withstand voltage (Uimp) |
4 kV
|
| Rated insulation voltage (Ui) |
440 V
|
| Rated operational voltage (Ue) - max |
415 V
|
| Rated short-circuit breaking capacity (IEC 60947-2)- Icu at 230 V |
15 kA
|
| Rated short-circuit breaking capacity (IEC 60947-2)- Icu at 400 V |
15 kA
|
| Rated switching capacity (IEC/EN 60947-2) |
15 kA
|
| Selectivity class |
3
|
| Voltage rating |
277 V AC / 480 V AC
|
| Voltage rating (IEC/EN 60947-2) |
440 V
|
| Voltage rating (UL) |
480Y/277 V
|
| Voltage rating at DC |
60 V DC
|
| Voltage type |
AC
|
| Built-in depth |
70.5 mm
|
| Connectable conductor cross section (multi-wired) - max |
25 mm²
|
| Connectable conductor cross section (multi-wired) - min |
1 mm²
|
| Connectable conductor cross section (solid-core) - max |
25 mm²
|
| Connectable conductor cross section (solid-core) - min |
1 mm²
|
| Degree of protection |
IP20
UL/CSA Type: - IP20 (IEC) IP40 (when fitted) |
| Enclosure width |
105 mm
|
| Frame |
45 mm
|
| Mounting Method |
Top-hat rail IEC/EN 60715
|
| Mounting position |
As required
|
| Mounting width |
17.7 mm
|
| Mounting width per pole |
17.7 mm
|
| Terminal protection |
Finger and hand touch safe, DGUV VS3, EN 50274
|
| Terminals (top and bottom) |
Twin-purpose terminals
|
| Tightening torque |
UL: 2.8 Nm (25 lb-in) for AWG 10 - AWG 8
UL: 2.4 Nm (21 lb-in) for AWG 18 - AWG 12 UL: 4 Nm (36 lb-in) for AWG 6 Max. 2.4 Nm |
| Width in number of modular spacings |
2
|