Nulstil
Nulstil
Eaton Moeller series xEffect - FAZ-NA-DC MCB. Miniature circuit breaker (MCB), 8 A, 1p, characteristic: C, DC
| Product Name |
Eaton Moeller series xEffect - FAZ-NA-DC MCB
|
| Catalog Number |
113758
|
| EAN |
4015081132935
|
| Product Length/Depth |
105 mm
|
| Product Height |
75.5 mm
|
| Product Width |
17.7 mm
|
| Product Weight |
0.121 kg
|
| Compliances |
RoHS conform
|
| Certifications |
IEC 60947-2
UL 489, CSA C22.2 No. 5 EN45545-2 IEC 61373 |
| Model Code |
FAZ-C8/1-NA-DC
|
| Current limiting class |
3
|
| Features |
Additional equipment possible
|
| Functional group |
Overcurrent protection
|
| Functions |
Overload protection
Short Circuit protection |
| Internal resistance at room temperature (single-pole, 50 Hz) |
21 mΩ
|
| Amperage Rating |
8 A
|
| Application |
DC applications in industrial and commercial installations, utilities, OEM control panels, renewable energy systems, IT and data centre auxiliary circuits, railway and transportation systems, as well as branch and feeder circuit protection in UL-listed panels for North American installations.
|
| Nominal current |
8 A
|
| Number of poles |
Single-pole
|
| Number of poles (protected) |
1
|
| Number of poles (total) |
1
|
| Release characteristic |
C
|
| Tripping characteristic |
C
|
| Type |
|
| 10.10 Temperature rise |
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
|
| 10.11 Short-circuit rating |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
| 10.12 Electromagnetic compatibility |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
| 10.13 Mechanical function |
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
|
| 10.2.2 Corrosion resistance |
Meets the product standard's requirements.
|
| 10.2.3.1 Verification of thermal stability of enclosures |
Meets the product standard's requirements.
|
| 10.2.3.2 Verification of resistance of insulating materials to normal heat |
Meets the product standard's requirements.
|
| 10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects |
Meets the product standard's requirements.
|
| 10.2.4 Resistance to ultra-violet (UV) radiation |
Meets the product standard's requirements.
|
| 10.2.5 Lifting |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.2.6 Mechanical impact |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.2.7 Inscriptions |
Meets the product standard's requirements.
|
| 10.3 Degree of protection of assemblies |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.4 Clearances and creepage distances |
Meets the product standard's requirements.
|
| 10.5 Protection against electric shock |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.6 Incorporation of switching devices and components |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.7 Internal electrical circuits and connections |
Is the panel builder's responsibility.
|
| 10.8 Connections for external conductors |
Is the panel builder's responsibility.
|
| 10.9.2 Power-frequency electric strength |
Is the panel builder's responsibility.
|
| 10.9.3 Impulse withstand voltage |
Is the panel builder's responsibility.
|
| 10.9.4 Testing of enclosures made of insulating material |
Is the panel builder's responsibility.
|
| Ambient operating temperature - max |
55 °C
|
| Ambient operating temperature - min |
-25 °C
|
| Rated operational current for specified heat dissipation (In) |
8 A
|
| Direction of incoming supply |
Polarity dependent
|
| Overvoltage category |
III
|
| Pollution degree |
2
|
| Rated impulse withstand voltage (Uimp) |
4 kV
|
| Rated insulation voltage (Ui) |
440 V
|
| Rated operational voltage (Ue) - max |
250 V
|
| Rated service short-circuit breaking capacity (IEC/EN 60947-2) - Ics |
7.5 kA
|
| Rated short-circuit breaking capacity (IEC 60947-2)- Icu at 230 V |
10 kA
|
| Rated switching capacity (IEC/EN 60947-2) |
10 kA
|
| Selectivity class |
3
|
| Voltage type |
DC
|
| Built-in depth |
65.5 mm
|
| Connectable conductor cross section (multi-wired) - max |
25 mm²
|
| Connectable conductor cross section (multi-wired) - min |
1 mm²
|
| Connectable conductor cross section (solid-core) - max |
25 mm²
|
| Connectable conductor cross section (solid-core) - min |
1 mm²
|
| Degree of protection |
IP20
|
| Mounting position |
As required
|
| Terminals (top and bottom) |
Screw-type with pressure plate
|
| Width in number of modular spacings |
1
|