Eaton EU1E SmartWire-DT IP67 T-Connector analog module, one 0 - 20 mA analog input with power supply, one M12 I/O socket
| Product Name |
Eaton EU1E Accessory Input module
|
| Catalog Number |
174718
|
| EAN |
4015081712045
|
| Product Length/Depth |
85.6 mm
|
| Product Height |
20.1 mm
|
| Product Width |
56.9 mm
|
| Product Weight |
0.07 kg
|
| Certifications |
UL File No.: E170645
CSA UL IEC/EN 61131-2 |
| Model Code |
EU1E-SWD-1AX-2
|
| Electric connection type |
Screw connection
|
| Features |
Short-circuit protection (sensor supply)
Input signal, configurable Input, current Analog outputs configurable Overload protection (sensor supply) Fieldbus connection over separate bus coupler possible Analog inputs configurable Fieldbus connection over separate bus coupler possible |
| Functions |
For connection of analog I/O signals
Adjustable parameter settings |
| Current consumption |
46 mA, SmartWire-DT network
70 mA, Max. current consumption per M12 I/O plug, Sensor supply, SmartWire-DT network |
| Degree of protection |
IP69K
NEMA 4X |
| Mounting method |
Wall mounting/direct mounting
Mounting section (Clip M20) Screw fixing (M4) DIN rail Rail mounting possible |
| Mounting method |
Wall mounting/direct mounting
Mounting section (Clip M20) Screw fixing (M4) DIN rail Rail mounting possible |
| Overvoltage category |
II
|
| Pollution degree |
3
|
| Product category |
SmartWire-DT slave
|
| Repetition accuracy |
0.5 % (Analog inputs)
|
| Type |
Analog modules
|
| Voltage type |
DC
|
| Constant acceleration |
1 g, 8.4 - 150 Hz, according to IEC/EN 61131-2, Vibrations
|
| Constant amplitude |
3,5 mm, 5 - 8.4 Hz, according to IEC/EN 61131-2, Vibrations
|
| Drop and topple |
50 mm Drop height, Drop to IEC/EN 60068-2-31
|
| Height of fall (IEC/EN 60068-2-32) - max |
0.3 m
|
| Mounting position |
As required
|
| Shock resistance |
30 g, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 11 ms, 9 Impacts
|
| Air pressure |
795 - 1080 hPa (operation)
|
| Ambient operating temperature - min |
-25 °C
|
| Ambient operating temperature - max |
70 °C
|
| Ambient storage temperature - min |
-40 °C
|
| Ambient storage temperature - max |
70 °C
|
| Climatic proofing |
Damp heat, constant, to IEC 60068-2-3
Dry heat to IEC 60068-2-2 |
| Environmental conditions |
Condensation: permissible
|
| Operating temperature - min |
-25 °C
|
| Operating temperature - max |
70 °C
|
| Relative humidity |
5 - 95 % (non-condensing, IEC/EN 60068-2-30)
|
| Air discharge |
8 kV, according to IEC 61131-2, level 3, ESD
|
| Burst impulse |
1 kV, Signal cable, according to IEC/EN 61131-2, Level 3
2 kV, Supply cable, according to IEC/EN 61131-2, Level 3 1 kV, SmartWire-DT cable, according to IEC/EN 61131-2, Level 3 |
| Contact discharge |
4 kV, according to IEC/EN 61131-2, Level 2, ESD
|
| Electromagnetic fields |
10 V/m at 80 - 1000 MHz (according to IEC/EN 61131-2:2008)
3 V/m at 1.4 - 2 GHz (according to IEC/EN 61131-2:2008) 1 V/m at 2.0 - 2.7 GHz (according to IEC/EN 61131-2:2008) |
| Radiated RFI |
10 V (IEC/EN 61131-2:2008, Level 3)
|
| Radio interference class |
Class A (EN 55011)
|
| Surge rating |
0.5 kV, Surge power cables, Surge (IEC/EN 61131-2:2008, Level 1), EMC
1 kV, Surge I/O cables, Surge (IEC/EN 61131-2:2008, Level 1), EMC |
| Input current |
0 - 20 mA (Analog inputs)
|
| Power loss |
1.1 W
|
| Connection to SmartWire-DT |
Yes
|
| Connection type |
SWD-OUT: M12 socket (A-keyed), 5 pole
5-pin M12 socket (A-keyed), Supply and I/O sensor SWD-IN : M12 plug (A-keyed), 5 pole |
| Data transfer rate |
Setting automatically
2 MBit/s, SmartWire-DT |
| LED indicator |
Status indication of SmartWire-DT network: Green LED
|
| Protocol |
Other bus systems
|
| Station |
SmartWire-DT slave, SmartWire-DT network
|
| Conversions |
20 ms, Analog inputs
|
| Dielectric strength |
30 kV/mm, according to IEC 60243-1
|
| Input |
Current
Input (0 - 20 mA) |
| Input impedance |
< 250 Ω
|
| Number of inputs (analog) |
1
|
| Number of outputs (analog) |
0
|
| Resolution |
12 Bit (Analog inputs)
|
| Total error |
± 1 %, Inputs
|
| Explosion safety category for dust |
None
|
| Explosion safety category for gas |
None
|
| Potential isolation |
Input to input: no
Inputs for SmartWire-DT: no |
| Equipment heat dissipation, current-dependent Pvid |
0 W
|
| Heat dissipation capacity Pdiss |
0 W
|
| Heat dissipation per pole, current-dependent Pvid |
0 W
|
| Rated operational current for specified heat dissipation (In) |
0 A
|
| Static heat dissipation, non-current-dependent Pvs |
1.1 W
|
| 10.2.2 Corrosion resistance |
Meets the product standard's requirements.
|
| 10.2.3.1 Verification of thermal stability of enclosures |
Meets the product standard's requirements.
|
| 10.2.3.2 Verification of resistance of insulating materials to normal heat |
Meets the product standard's requirements.
|
| 10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects |
Meets the product standard's requirements.
|
| 10.2.4 Resistance to ultra-violet (UV) radiation |
Meets the product standard's requirements.
|
| 10.2.5 Lifting |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.2.6 Mechanical impact |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.2.7 Inscriptions |
Meets the product standard's requirements.
|
| 10.3 Degree of protection of assemblies |
Meets the product standard's requirements.
|
| 10.4 Clearances and creepage distances |
Meets the product standard's requirements.
|
| 10.5 Protection against electric shock |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.6 Incorporation of switching devices and components |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.7 Internal electrical circuits and connections |
Is the panel builder's responsibility.
|
| 10.8 Connections for external conductors |
Is the panel builder's responsibility.
|
| 10.9.2 Power-frequency electric strength |
Is the panel builder's responsibility.
|
| 10.9.3 Impulse withstand voltage |
Is the panel builder's responsibility.
|
| 10.9.4 Testing of enclosures made of insulating material |
Is the panel builder's responsibility.
|
| 10.10 Temperature rise |
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
|
| 10.11 Short-circuit rating |
Is the panel builder's responsibility.
|
| 10.12 Electromagnetic compatibility |
Is the panel builder's responsibility.
|
| 10.13 Mechanical function |
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
|