Download dokument () af 20
We make what matters work*

174719
Modelkode: EU1E-SWD-1XA-1

Eaton EU1E SmartWire-DT IP67 T-Connector analog module, one 0 - 10 V analog output with power supply, one M12 I/O socket

General specifications

Product Name
Eaton EU1E Analog module
Catalog Number
174719
EAN
4015081712052
Product Length/Depth
85.6 mm
Product Height
20.1 mm
Product Width
56.9 mm
Product Weight
0.07 kg
Certifications
UL
CSA
UL File No.: E170645
IEC/EN 61131-2
Model Code
EU1E-SWD-1XA-1

Features & Functions

Electric connection type
Screw connection
Features
Output signal configurable
Fieldbus connection over separate bus coupler possible
Analog outputs configurable
Overload protection (sensor supply)
Short-circuit protection (sensor supply)
Output, voltage
Analog inputs configurable
Fieldbus connection over separate bus coupler possible
Functions
For connection of analog I/O signals

General information

Current consumption
52 mA, SmartWire-DT network
70 mA, Max. current consumption per M12 I/O plug, Sensor supply, SmartWire-DT network
Degree of protection
IP69K
NEMA 4X
Mounting method
DIN rail
Screw fixing (M4)
Rail mounting possible
Mounting section (Clip M20)
Wall mounting/direct mounting
Mounting method
DIN rail
Screw fixing (M4)
Rail mounting possible
Mounting section (Clip M20)
Wall mounting/direct mounting
Overvoltage category
II
Pollution degree
3
Product category
SmartWire-DT slave
Repetition accuracy
0.5 % (Analog outputs)
Type
  • Analog modules
  • Analog outputs
Voltage type
DC

Ambient conditions, mechanical

Constant acceleration
1 g, 8.4 - 150 Hz, according to IEC/EN 61131-2, Vibrations
Constant amplitude
3,5 mm, 5 - 8.4 Hz, according to IEC/EN 61131-2, Vibrations
Drop and topple
50 mm Drop height, Drop to IEC/EN 60068-2-31
Height of fall (IEC/EN 60068-2-32) - max
0.3 m
Mounting position
As required
Shock resistance
30 g, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 11 ms, 9 Impacts

Climatic environmental conditions

Air pressure
795 - 1080 hPa (operation)
Ambient operating temperature - min
-25 °C
Ambient operating temperature - max
70 °C
Ambient storage temperature - min
-40 °C
Ambient storage temperature - max
70 °C
Climatic proofing
Dry heat to IEC 60068-2-2
Damp heat, constant, to IEC 60068-2-3
Environmental conditions
Condensation: permissible
Operating temperature - min
-25 °C
Operating temperature - max
70 °C
Relative humidity
5 - 95 % (non-condensing, IEC/EN 60068-2-30)

Electro magnetic compatibility

Air discharge
8 kV, according to IEC 61131-2, level 3, ESD
Burst impulse
1 kV, Signal cable, according to IEC/EN 61131-2, Level 3
2 kV, Supply cable, according to IEC/EN 61131-2, Level 3
1 kV, SmartWire-DT cable, according to IEC/EN 61131-2, Level 3
Contact discharge
4 kV, according to IEC/EN 61131-2, Level 2, ESD
Electromagnetic fields
10 V/m at 80 - 1000 MHz (according to IEC/EN 61131-2:2008)
3 V/m at 1.4 - 2 GHz (according to IEC/EN 61131-2:2008)
1 V/m at 2.0 - 2.7 GHz (according to IEC/EN 61131-2:2008)
Radiated RFI
10 V (IEC/EN 61131-2:2008, Level 3)
Radio interference class
Class A (EN 55011)
Surge rating
1 kV, Surge I/O cables, Surge (IEC/EN 61131-2:2008, Level 1), EMC
0.5 kV, Surge power cables, Surge (IEC/EN 61131-2:2008, Level 1), EMC

Electrical rating

Output current
Max. 10 mA
Output voltage
0 - 10 V (analog outputs)
Power loss
1.2 W
Short-circuit protection
Yes, Short-circuit proof, Analog outputs

Communication

Connection to SmartWire-DT
Yes
Connection type
SWD-OUT: M12 socket (A-keyed), 5 pole
SWD-IN : M12 plug (A-keyed), 5 pole
5-pin M12 socket (A-keyed), Supply and I/O sensor
Data transfer rate
2 MBit/s, SmartWire-DT
Setting automatically
LED indicator
Status indication of SmartWire-DT network: Green LED
Protocol
Other bus systems
Station
SmartWire-DT slave, SmartWire-DT network

Input/Output

Conversions
20 ms, Analog outputs
Number of inputs (analog)
0
Number of outputs (analog)
1
Output
0 - 10 V
Resolution
12 Bit (Analog outputs)
Total error
± 1 %, Outputs

Safety

Explosion safety category for dust
None
Explosion safety category for gas
None
Potential isolation
Between Outputs to SmartWire-DT: no

Design verification

Equipment heat dissipation, current-dependent Pvid
0 W
Heat dissipation capacity Pdiss
0 W
Heat dissipation per pole, current-dependent Pvid
0 W
Rated operational current for specified heat dissipation (In)
0 A
Static heat dissipation, non-current-dependent Pvs
1.2 W
10.2.2 Corrosion resistance
Meets the product standard's requirements.
10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard's requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard's requirements.
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects
Meets the product standard's requirements.
10.2.4 Resistance to ultra-violet (UV) radiation
Meets the product standard's requirements.
10.2.5 Lifting
Does not apply, since the entire switchgear needs to be evaluated.
10.2.6 Mechanical impact
Does not apply, since the entire switchgear needs to be evaluated.
10.2.7 Inscriptions
Meets the product standard's requirements.
10.3 Degree of protection of assemblies
Meets the product standard's requirements.
10.4 Clearances and creepage distances
Meets the product standard's requirements.
10.5 Protection against electric shock
Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and components
Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections
Is the panel builder's responsibility.
10.8 Connections for external conductors
Is the panel builder's responsibility.
10.9.2 Power-frequency electric strength
Is the panel builder's responsibility.
10.9.3 Impulse withstand voltage
Is the panel builder's responsibility.
10.9.4 Testing of enclosures made of insulating material
Is the panel builder's responsibility.
10.10 Temperature rise
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating
Is the panel builder's responsibility.
10.12 Electromagnetic compatibility
Is the panel builder's responsibility.
10.13 Mechanical function
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.

Eksportér produktspecifikation