Eaton Moeller® series M22 Contact element, Cage Clamp, Push-in, Front fixing, 1 NC, 24 V 1.5 A, 230 V 1.5 A
| Product Name |
Eaton Moeller® series M22 contact element
|
| Catalog Number |
180791
|
| EAN |
4015081759606
|
| Product Length/Depth |
40.2 mm
|
| Product Height |
10 mm
|
| Product Width |
14 mm
|
| Product Weight |
0.004 kg
|
| Certifications |
UL 508
CSA File No.: 012528 UL File No.: E29184 CSA IEC/EN 60947-5 UL CSA Class No.: 3211-03 CSA-C22.2 No. 94-91 UL Category Control No.: NKCR CE IEC 60947-5-1 CSA-C22.2 No. 14-05 |
| Catalog Notes |
Contacts with safety function, by positive opening to IEC/EN 60947-5-1
|
| Model Code |
M22-FK01
|
| Electric connection type |
Spring clamp connection
|
| Operating frequency |
3600 Operations/h
|
| Pollution degree |
3
|
| Climatic proofing |
Damp heat, cyclic, to IEC 60068-2-30
Damp heat, constant, to IEC 60068-2-78 Dry heat to IEC 60068-2-2 |
| Actuating force - max |
4.5 N
|
| Actuator travel and actuation force (DIN EN 60947-5-1) |
5.5 mm
|
| Ambient operating temperature - max |
70 °C
|
| Ambient operating temperature - min |
-25 °C
|
| Ambient storage temperature - max |
85 °C
|
| Ambient storage temperature - min |
-40 °C
|
| Force for positive opening - min |
20 N
|
| Knob travel |
5.8 mm
|
| Number of contacts (change-over contacts) |
0
|
| Number of contacts (normally closed contacts) |
1
|
| Number of contacts (normally open contacts) |
0
|
| Number of switches (fault signal) |
0
|
| Connection to SmartWire-DT |
No
|
| Rated impulse withstand voltage (Uimp) |
4000 V AC
|
| Rated conditional short-circuit current (Iq) |
1 kA
|
| Connection type |
Front fixing
Cage Clamp Push-in clamp |
| Mounting method |
Front fastening
|
| Overvoltage category |
III
|
| Degree of protection |
IP20
|
| Model |
Top mounting
|
| Lamp holder |
None
|
| Rated operational current (Ie) |
4 A at AC-15, 60 V
2 A at AC-15, 110 V |
| Lifespan, mechanical |
1,000,000 Operations (AC operated)
|
| Short-circuit protection |
FAZ-B4, Contacts, Max. short-circuit protective device, Fuseless
|
| Short-circuit protection rating |
Max. 4 A gG/gL, Fuse, Contacts
|
| Rated insulation voltage (Ui) |
250 V
|
| Rated operational current (Ie) at AC-15, 220 V, 230 V, 240 V |
1.5 A
|
| Rated operational current (Ie) at AC-15, 24 V |
4 A
|
| Rated operational current (Ie) at DC-13, 110 V |
0.4 A
|
| Rated operational current (Ie) at DC-13, 220 V, 230 V |
0.2 A
|
| Rated operational current (Ie) at DC-13, 24 V |
1.5 A
|
| Rated operational current (Ie) at DC-13, 60 V |
0.8 A
|
| Terminal capacity (flexible with ferrule) |
2 x (0.25 - 1) mm²
Use WAGO Variocrimp 4 crimping tool; please enquire for others |
| Terminal capacity (solid) |
2 x (0.2 - 1.5) mm²
2 x 1 (075 - 1.5) mm², Can be plugged without tools |
| Terminal capacity (solid/stranded AWG) |
2 x (24 - 16)
|
| Terminal capacity (flexible) |
2 x (0.25 - 1) mm², without ferrule
Insert with tool |
| Shock resistance |
50 g, Mechanical, according to IEC/EN 60068-2-27, Half-Sinusoidal shock 11 ms
|