Vidensøgning
Download dokument () af 20
We make what matters work*

189575
Modelkode: KLV-36UPP-F-2PXF-16PLI

Eaton xComfort KLV LV systems Final Distribution Boards. Assembled flush mounting compact distribution board, 3-row, flush sheet steel door

General specifications

Product Name
Eaton xComfort KLV pre-wired distribution board
Catalog Number
189575
EAN
4015081874606
Product Length/Depth
100 mm
Product Height
590 mm
Product Width
360 mm
Product Weight
13.2 kg
Compliances
RoHS conform
Certifications
IEC/EN 60670-24
IEC/EN 62208
Model Code
KLV-36UPP-F-2PXF-16PLI

Additional information

Cooker group
None
Features
Protection dual RCD
Protection high integrity
Protection incoming RCD
Protection split load
Fitted with:
12 SU empty section cover
3D adjustment element for mounting designed to adjust the mounting depth by up to 18 mm
Nail lugs
Wired and tested in conformity with EN 61439-3
Door/Frame
Linked to eight PLI-B16/1's, wired to 5-terminal block
Device support rails
Installation instructions
2 rows, each equipped with one PXF-40/4/003-A
Neutral and protective conductor terminals with KSK plug-in terminal technology
Cable retainer
Wall trough
Front cover
Imprintable sheet
Spirit level for leveling
Functions
Basic device
Extension possible
Number of light groups protected by 30 mA
2
Protected by
Miniature- / earth leakage circuit breaker
Protection class
II (totally insulated)
RAL-number
9016
Special features
  • IP30
  • Protection Class II
  • Plastic enclosure with sheet steel door, white (RAL 9016)

Delivery program

Application
Indoor (installation site)
Color
Traffic white (RAL 9016)
White
Number of phases
3
Type
  • Basic device
  • Installation distribution boards
  • KLV energy

Design verification as per IEC/EN 61439

10.10 Temperature rise
The requirements of the product standard have been met.
10.11 Short-circuit rating
The requirements of the product standard have been met.
10.12 Electromagnetic compatibility
The requirements of the product standard have been met.
10.13 Mechanical function
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
10.2.2 Corrosion resistance
Meets the product standard's requirements.
10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard's requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard's requirements.
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects
650 °C
10.2.4 Resistance to ultra-violet (UV) radiation
Not relevant to indoor installations.
10.2.5 Lifting
Does not apply to enclosures without lifting aids.
10.2.6 Mechanical impact
IK05
10.2.7 Inscriptions
Meets the product standard's requirements.
10.3 Degree of protection of assemblies
IP30
10.4 Clearances and creepage distances
Meets the product standard's requirements.
10.5 Protection against electric shock
Protection class 2, therefore not applicable.
10.6 Incorporation of switching devices and components
The requirements of the product standard have been met.
10.7 Internal electrical circuits and connections
The requirements of the product standard have been met.
10.8 Connections for external conductors
Is the panel builder's responsibility.
10.9.2 Power-frequency electric strength
Ui = 400 V AC
10.9.3 Impulse withstand voltage
4 kV
10.9.4 Testing of enclosures made of insulating material
Meets the product standard's requirements.

Design verification as per IEC/EN 61439 - technical data

Ambient operating temperature details
-5 °C - 40 °C

Technical Data - Electrical

Frequency rating
50 Hz
Frequency rating of contacts
50 Hz
Voltage rating
400 V AC

Technical Data - Mechanical

Built-in height
45 mm
Built-in width
251 mm
Cable entry postion
Cable entries on top and bottom, side, back plate
Closure type
Other
Cover/door color
White
Degree of protection
IP30
IK05 (impact resistance)
Enclosure material
Plastic
Installation type
Flush mounting
Material
Polystyren (plastic)
Sheet steel, powder-coated
Module rack type
Rail frame
Number of arc fault detection devices AFDD
0
Number of circuit breakers (earth leakage)
0
Number of direct groups
2
Number of groups (total)
16
Number of groups behind earth leakage switch
16
Number of module space units per row
12
Number of outgoing ways
16
Number of poles at main switch
0
Number of rows
3
Number of switches (earth leakage 30 mA)
2
Number of switches (earth leakage 300 mA)
0
PE and N terminal number and cross section
PE: 4 x (2.5 mm² - 25 mm²) + 28 x (0.5 mm² - 4 mm²)
N: 4 x (2.5 mm² - 25 mm²) + 28 x (0.5 mm² - 4 mm²)
Protective shrouding material
Plastic
Rocker color
White
Terminal type
Plug-in terminals
Width in number of modular spacings
12
Connection type
Push-in clamp
Mounting method
Flush mounting
Flush mounted (plaster)

Temperature-rise verification as per IEC 60890

Heat diss. ambient 35°C delta T:20°C flush mount individ. encl. top(IEC 60890)
20 W
Heat diss. ambient 35°C delta T:35°C flush mount individ. encl. top(IEC 60890)
43 W

Eksportér produktspecifikation