Vidensøgning
Download dokument () af 20
We make what matters work*

194711
Modelkode: KLV-PW-48-1PXL-1SPD-2PXF-16PLI

Eaton xComfort KLV LV systems Final Distribution Boards. Assembled compact distribution board, 4-rows, flush sheet steel door

General specifications

Product Name
Eaton xComfort KLV pre-wired distribution board
Catalog Number
194711
EAN
9010238060500
Product Length/Depth
96.5 mm
Product Height
714 mm
Product Width
359 mm
Product Weight
8.278 kg
Compliances
RoHS conform
Certifications
IEC/EN 61439-3
Model Code
KLV-PW-48-1PXL-1SPD-2PXF-16PLI

Additional information

Cooker group
None
Features
Protection dual RCD
Protection high integrity
Protection main switch
Protection incoming RCD
Protection split load
Fitted with:
Cable retainer
Wired and tested in conformity with EN 61439-3
Door/Frame
Front cover
Nail lugs
Neutral and protective conductor terminals with KSK plug-in terminal technology
2 residual current circuit-breaker PXF-40/4/003-A
Imprintable sheet
Installation instructions
1 surge protective device SPCT2-335-3+NPE
Wall trough
3D adjustment element for mounting designed to adjust the mounting depth by up to 18 mm
1 miniature circuit breaker PXL-C40/3
Device support rails
Empty section cover
Spirit level for leveling
16 Miniature circuit breaker PLI-B16/1
Functions
Over voltage protection
Basic device
Number of light groups protected by 30 mA
0
Protected by
Miniature- / earth leakage circuit breaker
Protection class
II (totally insulated)
RAL-number
9016
Special features
IP30 Protection Class II Plastic enclosure with sheet steel door, white (RAL 9016)

Delivery program

Application
Indoor (installation site)
Color
Traffic white (RAL 9016)
White
Number of phases
3
Type
Basic device Installation distribution boards KLV energy

Design verification as per IEC/EN 61439

10.10 Temperature rise
The requirements of the product standard have been met.
10.11 Short-circuit rating
The requirements of the product standard have been met.
10.12 Electromagnetic compatibility
The requirements of the product standard have been met.
10.13 Mechanical function
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
10.2.2 Corrosion resistance
Meets the product standard's requirements.
10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard's requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard's requirements.
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects
850 °C
10.2.4 Resistance to ultra-violet (UV) radiation
Not relevant to indoor installations.
10.2.5 Lifting
Does not apply to enclosures without lifting aids.
10.2.6 Mechanical impact
IK05
10.2.7 Inscriptions
Meets the product standard's requirements.
10.3 Degree of protection of assemblies
IP30
10.4 Clearances and creepage distances
Meets the product standard's requirements.
10.5 Protection against electric shock
Protection class 2, therefore not applicable.
10.6 Incorporation of switching devices and components
The requirements of the product standard have been met.
10.7 Internal electrical circuits and connections
The requirements of the product standard have been met.
10.8 Connections for external conductors
Is the panel builder's responsibility.
10.9.2 Power-frequency electric strength
Ui = 400 V AC
10.9.3 Impulse withstand voltage
4 kV
10.9.4 Testing of enclosures made of insulating material
Meets the product standard's requirements.

Design verification as per IEC/EN 61439 - technical data

Ambient operating temperature details
-5 °C - 40 °C

Technical data - electrical

Current rating of main switch
32 A
Frequency rating
50 Hz
Frequency rating of contacts
50 Hz
Voltage rating
400 V AC

Technical data - mechanical

Built-in height
45 mm
Built-in width
251 mm
Cable entry postion
Cable entries on top and bottom, side, back plate
Closure type
Other
Cover/door color
White
Degree of protection
IK05 (impact resistance)
IP30
Enclosure material
Plastic
Installation type
Hollow-wall mounting and flush mounting
Material
Polystyren (plastic)
Sheet steel, powder-coated
Module rack type
Rail frame
Number of arc fault detection devices AFDD
0
Number of circuit breakers (earth leakage)
0
Number of direct groups
2
Number of groups (total)
0
Number of groups behind earth leakage switch
2
Number of module space units per row
12
Number of outgoing ways
16
Number of poles at main switch
3
Number of rows
4
Number of switches (earth leakage 30 mA)
2
Number of switches (earth leakage 300 mA)
0
PE and N terminal number and cross section
N: 4 x (2.5 mm² - 25 mm²) + 28 x (0.5 mm² - 4 mm²)
PE: 4 x (2.5 mm² - 25 mm²) + 28 x (0.5 mm² - 4 mm²)
Protective shrouding material
Plastic
Rocker color
White
Terminal type
Screw terminals + Plug-in terminals
Type of over voltage protection device
Type 2
Width in number of modular spacings
12
Connection type
Push-in clamp
Mounting method
Hollow-wall mounting and flush mounting
Hollow wall
Flush mounted (plaster)
Flush mounting

Temperature-rise verification as per IEC 60890

Heat diss. ambient 35°C delta T:20°C flush mount individ. encl. top(IEC 60890)
45 W
Heat diss. ambient 35°C delta T:35°C flush mount individ. encl. top(IEC 60890)
48 W

Eksportér produktspecifikation