Eaton DB1 Variable frequency drive, 240 V AC, 1-phase, 10.9 A, IP20, NEMA Other, FS1, Radio interference
| Product Name |
Eaton DB1 Variable frequency drive
|
| Catalog Number |
199738
|
| EAN |
4015081988372
|
| Product Length/Depth |
90 mm
|
| Product Height |
185.98 mm
|
| Product Width |
127.98 mm
|
| Product Weight |
0.7 kg
|
| Certifications |
IEC/EN 61800-2
IEC/EN 61800-3 RoHS, ISO 9001 IEC/EN 61800-5-1 UL Category Control No.: NMMS, NMMS7 Certified by UL for use in Canada UL Listed UL File No.: E172143 UL report applies to both US and Canada UL 508C CSA-C22.2 No. 274 IEC 61000-3-2 CE marking |
| Model Code |
DB1-1M4D3FN-N2CC-PFC
|
| Mounting position |
As required
Depending on the cooling |
| Shock resistance |
15 g, Mechanical, According to IEC/EN 60068-2-27, 11 ms
|
| Apparent power at 230 V |
0.99 kVA
|
| Apparent power at 240 V |
1.03 kVA
|
| Braking torque |
Max. 30 % MN, Standard - Main circuit
Max. 100 % of rated operational current Ie, variable, DC - Main circuit |
| Altitude |
Above 1000 m with 1 % derating per 100 m
Max. 2000 m Max. 1000 m |
| Ambient operating temperature - max |
50 °C
|
| Ambient storage temperature - max |
60 °C
|
| Ambient operating temperature - min |
-10 °C
|
| Ambient storage temperature - min |
-40 °C
|
| Climatic proofing |
< 95 average relative humidity (RH), no condensation, no corrosion
|
| Number of inputs (analog) |
2
|
| Number of inputs (digital) |
4
|
| Number of outputs (analog) |
1
|
| Number of outputs (digital) |
1
|
| Number of relay outputs |
1 (parameterizable, N/O, 6 A (250 V, AC-1) / 5 A (30 V, DC-1))
|
| 10.10 Temperature rise |
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
|
| 10.11 Short-circuit rating |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
| 10.12 Electromagnetic compatibility |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
| 10.13 Mechanical function |
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
|
| 10.2.2 Corrosion resistance |
Meets the product standard's requirements.
|
| 10.2.3.1 Verification of thermal stability of enclosures |
Meets the product standard's requirements.
|
| 10.2.3.2 Verification of resistance of insulating materials to normal heat |
Meets the product standard's requirements.
|
| 10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects |
Meets the product standard's requirements.
|
| 10.2.4 Resistance to ultra-violet (UV) radiation |
Meets the product standard's requirements.
|
| 10.2.5 Lifting |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.2.6 Mechanical impact |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.2.7 Inscriptions |
Meets the product standard's requirements.
|
| 10.3 Degree of protection of assemblies |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.4 Clearances and creepage distances |
Meets the product standard's requirements.
|
| 10.5 Protection against electric shock |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.6 Incorporation of switching devices and components |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.7 Internal electrical circuits and connections |
Is the panel builder's responsibility.
|
| 10.8 Connections for external conductors |
Is the panel builder's responsibility.
|
| 10.9.2 Power-frequency electric strength |
Is the panel builder's responsibility.
|
| 10.9.3 Impulse withstand voltage |
Is the panel builder's responsibility.
|
| 10.9.4 Testing of enclosures made of insulating material |
Is the panel builder's responsibility.
|
| Fitted with: |
Internal DC link
IGBT inverter PC connection Additional PCB protection PFC (Power Factor Compensation) Radio interference suppression filter |
| Cable length |
C1 ≤ 1 m, maximum motor cable length
C3 ≤ 10 m, maximum motor cable length C2 ≤ 3 m, maximum motor cable length 10 m, screened, maximum permissible cable length |
| Communication interface |
OP-Bus (RS485), built in
Modbus RTU, built in CANopen®, built in |
| Connection to SmartWire-DT |
No
|
| Degree of protection |
IP20
NEMA Other |
| Number of slots |
1 (expansion)
|
| Product Category |
Variable frequency drives
|
| Protection |
Finger and back-of-hand proof, Protection against direct contact (BGV A3, VBG4)
|
| Protocol |
CAN
MODBUS Other bus systems |
| Radio interference class |
C2, C3: depending on the motor cable length, the connected load, and ambient conditions. External radio interference suppression filters (optional) may be necessary.
C1: for conducted emissions only |
| Suitable for |
Branch circuits, (UL/CSA)
|
| Frame size |
FS1
|
| Input current ILN at 150% overload |
10.9 A
|
| Leakage current at ground IPE - max |
3.5 mA (at 110 V)
|
| Mains switch-on frequency |
Maximum of one time every 30 seconds
|
| Mains voltage - max |
230 V
|
| Mains voltage - min |
110 V
|
| Operating mode |
PM motors
Synchronous reluctance motors U/f control Sensorless vector control (SLV) Speed control with slip compensation BLDC motors |
| Output frequency - max |
500 Hz
|
| Output frequency - min |
0 Hz
|
| Output voltage (U2) |
230 V AC, 3-phase
|
| Rated frequency - max |
62 Hz
|
| Rated frequency - min |
48 Hz
|
| Rated operational current (Ie) at 150% overload |
4.3 A
|
| Rated operational power at 220/230 V, 50 Hz, 1-phase |
0.75 kW
|
| Rated operational voltage |
115 V AC, 1-phase
230 V AC, 1-phase |
| Resolution |
0.1 Hz (Frequency resolution, setpoint value)
|
| Short-circuit protection rating |
110 A, UL (Class CC or J), Safety device (fuse or miniature circuit-breaker), Power Wiring
|
| Starting current - max |
175 %, IH, max. starting current (High Overload), For 3.75 seconds every 600 seconds, Power section
|
| Supply frequency |
50/60 Hz
|
| System configuration type |
AC supply systems with earthed center point
|
| Voltage rating - max |
240 V
|
| Assigned motor current IM at 220 - 240 V, 60 Hz, 150% overload |
4.3 A
|
| Assigned motor current IM at 230 V, 50 Hz, 150% overload |
4.3 A
|
| Assigned motor power at 230/240 V, 60 Hz, 1-phase |
1 HP
|