Eaton easyPOW Power supply unit, 100-240VAC/24VDC, 1.25A, 1-phase, controlled EASY400-POW
| Product Name |
Eaton easyPOW power supply unit
|
| Catalog Number |
212319
|
| EAN |
4015082123192
|
| Product Length/Depth |
58 mm
|
| Product Height |
90 mm
|
| Product Width |
72 mm
|
| Product Weight |
0.185 kg
|
| Certifications |
IEC 60068-2-6
IEC 60068-2-27 IEC/EN 61000-4 EN 55011 EN 55022 |
| Model Code |
EASY400-POW
|
| Features |
Proof against sustained short circuit, hickup mode, approx. 2 Hz (Output current 24 V DC)
Overload proof (by current limitation) |
| Number of phases |
1
|
| Degree of Protection |
IP20 (according to IEC/EN 60529, EN 50178, VBG 4)
|
| Mounting Method |
Screw fixing using fixing brackets ZB4-101-GF1 (accessories)
Top-hat rail fixing (according to IEC/EN 60715, 35 mm) |
| Product category |
Accessories
|
| Used with |
easyE4
|
| LED indicator |
Status Indication of 24 V DC output voltage: Continuous green light LED
|
| Power consumption |
35 W typ.
|
| Mounting position |
Horizontal
Vertical |
| Shock resistance |
15 g, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 11 ms, 18 Impacts
|
| Altitude |
Max. 2000 m
|
| Ambient operating temperature - min |
-25 °C
|
| Ambient operating temperature - max |
55 °C
|
| Ambient storage temperature - min |
-40 °C
|
| Ambient storage temperature - max |
70 °C
|
| Air discharge |
8 kV, according to IEC/EN 61000-4-2, Level 3, ESD
|
| Burst impulse |
2 kV, according to IEC/EN 61000-4-4, Level 3
|
| Contact discharge |
6 kV, according to IEC/EN 61000-4-2, Level 3, ESD
|
| Electromagnetic fields |
10 V/m (according to IEC EN 61000-4-3)
|
| Immunity to line-conducted interference |
10 V (according to IEC/EN 61000-4-6)
|
| Surge rating |
0.5kV, outgoer cables symmetrical, EASY…DC, IEC/EN 61000-4-5, level 2, 24 V EMC
2 kV, Supply cables, symmetrical, power pulses (Surge), EMC 6 kV, Surge voltage (EN 50178), 24 V, EMV |
| Terminal capacity (flexible with ferrule) |
0.2/2.5 mm²
|
| Terminal capacity (flexible with ferrule AWG) |
22 - 12
|
| Terminal capacity (solid) |
0.2/4 mm²
|
| Terminal capacity (solid AWG) |
22 - 12
|
| Tightening torque |
0.6 Nm, Screw terminals
|
| Protection class |
2 (IEC/EN 60536)
|
| Current limitation |
1.5 A, effectiveness of current limitation, 24 V DC, output current
|
| Insulation resistance |
According to EN 50178
|
| Potential isolation |
SELV (VDE 0100 Part 410; IEC 60364-4-41, HD 384.4.41 S2) EN 60950, EN 50178 (primary/secondary)
|
| Input current at AC - max |
0.6 A
|
| Input voltage at AC 50 Hz - min |
85 V
|
| Input voltage at AC 50 Hz - max |
264 V
|
| Input voltage at DC - min |
0 V
|
| Input voltage at DC - max |
0 V
|
| Inrush current |
18 A (at 25 °C, 230 V)
|
| Mains failure bridging |
> 20 ms (at 115 V, according to IEC/EN 61000-4-11)
> 40 ms (at 230 V, according to IEC/EN 61000-4-11) |
| Efficiency |
83 %
|
| Output |
Parallel switching
|
| Output current at AC, 50 Hz - max |
1.25 A
|
| Output voltage |
± 2 % (Effect with 25 - 100 % load change)
± 1 % (Effect of input voltage) |
| Output voltage at AC 50 Hz - max |
18 V
|
| Output voltage at DC - min |
0 V
|
| Output voltage at DC - max |
24 V
|
| Rated output power |
30 W
|
| Voltage tolerance |
± 3 %, Rated output voltage
|
| Equipment heat dissipation, current-dependent Pvid |
0 W
|
| Heat dissipation capacity Pdiss |
0 W
|
| Heat dissipation per pole, current-dependent Pvid |
0 W
|
| Rated operational current for specified heat dissipation (In) |
0 A
|
| Static heat dissipation, non-current-dependent Pvs |
5 W
|
| 10.2.2 Corrosion resistance |
Meets the product standard's requirements.
|
| 10.2.3.1 Verification of thermal stability of enclosures |
Meets the product standard's requirements.
|
| 10.2.3.2 Verification of resistance of insulating materials to normal heat |
Meets the product standard's requirements.
|
| 10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects |
Meets the product standard's requirements.
|
| 10.2.4 Resistance to ultra-violet (UV) radiation |
Meets the product standard's requirements.
|
| 10.2.5 Lifting |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.2.6 Mechanical impact |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.2.7 Inscriptions |
Meets the product standard's requirements.
|
| 10.3 Degree of protection of assemblies |
Meets the product standard's requirements.
|
| 10.4 Clearances and creepage distances |
Meets the product standard's requirements.
|
| 10.5 Protection against electric shock |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.6 Incorporation of switching devices and components |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.7 Internal electrical circuits and connections |
Is the panel builder's responsibility.
|
| 10.8 Connections for external conductors |
Is the panel builder's responsibility.
|
| 10.9.2 Power-frequency electric strength |
Is the panel builder's responsibility.
|
| 10.9.3 Impulse withstand voltage |
Is the panel builder's responsibility.
|
| 10.9.4 Testing of enclosures made of insulating material |
Is the panel builder's responsibility.
|
| 10.10 Temperature rise |
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
|
| 10.11 Short-circuit rating |
Is the panel builder's responsibility.
|
| 10.12 Electromagnetic compatibility |
Is the panel builder's responsibility.
|
| 10.13 Mechanical function |
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
|