Vidensøgning
Download dokument () af 20
We make what matters work*

231269
Modelkode: M22-ASI

Eaton Moeller® series M22 AS-Interface module, 2I, 1Q, screw connection

General specifications

Product Name
Eaton Moeller® series M22 AS-interface connection
Catalog Number
231269
EAN
4015082312695
Product Length/Depth
40 mm
Product Height
30 mm
Product Width
40 mm
Product Weight
0.023 kg
Certifications
UL File No.: E29184
CE
CSA
CSA-C22.2 No. 14-05
DIN EN 50295
UL
UL 508
IEC/EN 60947
CSA Class No.: 3211-03
CSA File No.: 012528
UL Category Control No.: NKCR
IEC/EN 60947-5
CSA-C22.2 No. 94-91
Model Code
M22-ASI

Actuator

Bezel color
Titanium
Fitted with:
AS-Interface connector as insulation piercing terminal

Climatic environmental conditions

Ambient operating temperature - max
55 °C
Ambient operating temperature - min
-25 °C
Climatic proofing
Damp heat, cyclic, to IEC 60068-2-30
Damp heat, constant, to IEC 60068-2-78

Communication

Connection to SmartWire-DT
No

Design verification

10.10 Temperature rise
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.12 Electromagnetic compatibility
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.13 Mechanical function
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
10.2.2 Corrosion resistance
Meets the product standard's requirements.
10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard's requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard's requirements.
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects
Meets the product standard's requirements.
10.2.4 Resistance to ultra-violet (UV) radiation
Meets the product standard's requirements.
10.2.5 Lifting
Does not apply, since the entire switchgear needs to be evaluated.
10.2.6 Mechanical impact
Does not apply, since the entire switchgear needs to be evaluated.
10.2.7 Inscriptions
Meets the product standard's requirements.
10.3 Degree of protection of assemblies
Does not apply, since the entire switchgear needs to be evaluated.
10.4 Clearances and creepage distances
Meets the product standard's requirements.
10.5 Protection against electric shock
Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and components
Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections
Is the panel builder's responsibility.
10.8 Connections for external conductors
Is the panel builder's responsibility.
10.9.2 Power-frequency electric strength
Is the panel builder's responsibility.
10.9.3 Impulse withstand voltage
Is the panel builder's responsibility.
10.9.4 Testing of enclosures made of insulating material
Is the panel builder's responsibility.
Equipment heat dissipation, current-dependent Pvid
0 W
Heat dissipation capacity Pdiss
0 W
Heat dissipation per pole, current-dependent Pvid
0 W
Rated operational current for specified heat dissipation (In)
0 A
Static heat dissipation, non-current-dependent Pvs
1.3 W

Electrical rating

No-load current
30 A
Output voltage
24 V DC (-15/+10 %)
Power consumption
40 mA
Rated operational voltage
26.5 - 31.6 V DC (AS-Interface specification)

General information

Degree of protection
IP20
Input
2 Inputs (22 V/5 mA, protected against short-circuit)
Inputs for 2 contact elements (M22-K01 (N/C), M22-K10 (N/O))
Mounting position
As required
Output
1 (normally 19 V/8 mA) Output, protected against short-circuit
Output for 1 LED element: M22-LED-...
Product category
Accessories

Eksportér produktspecifikation

Bemærk: Hvis fil(er) mangler i .zip-download, understøttes filtypen ikke ved bulk download.